blank space

Fire Safety Commission Decision Summary

DECISION NO. 2002A006-137 (2002A007-138; 2003A001-139)
Date:  February 25, 2003


SUBJECT MATTER

The issue before the tribunal was a premises being used as a rooming operation located in a high-rise building regulated by Section 9.6 of the Fire Code. The fire department served an inspection order, which identified remedial work. The inspection order was appealed and modified by the Fire Marshal’s Delegate. The owner subsequently appealed this decision to the Fire Safety Commission.


GENERAL DESCRIPTION OF PREMISES

This is an 8-storey high residential condominium building containing 175 residential units. Each suite is two storeys and has a balcony on each level. The suites and public corridors are separated from adjacent areas by masonry fire separations. Reportedly, the building is provided with smoke control measures in the exit stairwells. Centrally located gas-fired furnaces deliver heat to residential units through steel ducts.

The building is served by exit stairwells that lead directly to the outside. Exit signs and emergency lighting are provided in corridors and exit stairwells. Each suite is provided with suite entrance doors on both of its levels.

The building is provided with a zoned, single-stage fire alarm system that is monitored by an outside agency. Smoke or heat detection is provided in the stairwells and service rooms. Alarm devices are provided in the corridors and in each suite located above the upper level entrance door. Manual pull stations are provided at each exit. An annunciator panel is located in the main lobby. The fire alarm system is provided with emergency power from a generator. A single-station smoke alarm is provided on each level of each residential suite.

The building is provided with a standpipe system that provides coverage throughout, and automatic sprinkler protection is provided in the garage. Fire department connections for these systems are located close to the main building entrance and close to street hydrants. Fire department access is provided to all sides of the building. Hose cabinets contain portable fire extinguishers. A “yellow hat” firefighter's elevator provides access to all levels.

The suite at issue is located in the west section of the building with the main suite entrance door on the 2nd floor. It contains three bedrooms on its lower level and four bedrooms on its upper level. One bedroom door is provided with a keyed passage set. The other bedroom doors are provided with chains that require keys to disengage them on the hallway side. Each level has a bathroom and the shared kitchen is located on the lower level.

The walls separating the bedrooms from adjacent areas within the suite are constructed of studs protected on both sides by drywall membranes. Other interior walls are masonry or drywall construction. Some bedroom walls have openings provided with plastic sliding panels used for ventilation purposes.

Bedroom and bathroom doors are a hollow wood type that are less than 45 mm thick, and are supported on wood frames. Bedroom doors are provided with self-closing devices and latches. Bathroom doors are provided with latches. Sliding doors provide access to the hall closet on the upper level. The kitchen is open to the surrounding area.

Each level is provided with a 12A, 5BC rated portable fire extinguisher.


REASON FOR APPEAL

The owner claimed that the inspection order is invalid and that the premises do not operate as a rooming house.


APPELLANT'S POSITION

The owner indicated that he has complied with some of the conditions as set out in the Inspection Order but is waiting for the outcome of the hearing decision.


RESPONDENT'S POSITION

The fire department identified the unit as being used as a rooming house, and having inadequate fire safety measures when compared with Section 9.3 of the Fire Code.


COMMISSION RULING

The Commission ruled that the Review Decision of the Fire Marshal’s Delegate be upheld and ordered that the work shall be completed to the satisfaction of the fire department before June 30, 2003. The decision reads as follows:

  1. To ensure that occupants have safe egress routes in the event of a fire in the unit
    1. the bedrooms on each level shall open onto a corridor that is separated from adjacent rooms and areas by fire separations that have a minimum 30 minute fire resistance rating. Each corridor shall lead directly to a door opening onto a building corridor;
    2. the upper level shall be separated from the lower level by a fire separation having a minimum 30 minute fire resistance rating; and
    3. openings in the fire separation referred to in (a) and (b) shall be protected with closures having a minimum 20 minute fire protection rating. Doors used as closures shall be provided with self-closing devices.

  2. To ensure that a fire occurring in a bedroom is prevented from spreading to adjacent areas before occupants in those areas have an opportunity to more to safety
    1. each bedroom shall be separated from adjacent rooms and areas by fire separations having a minimum 30 minute fire resistance rating; and
    2. openings in the fire separation referred to in (a) shall be protected with closures having a minimum 20 minute fire protection rating. The openings with the sliding ventilation panels are unacceptable since they compromise the integrity of the fire separations. Doors used as closures shall be provided with self-closing devices.

  3. To ensure that occupants are provided with early detection of a fire condition
    1. smoke alarms shall be installed in each bedroom;
    2. smoke alarms shall be installed on the ceiling of each level adjacent to the stairwell;
    3. smoke alarms referred to in (a) and (b) shall conform to CAN/ULC-S531, “Smoke Alarms”;
    4. smoke alarms referred to in (a) and (b) shall be installed by permanent connections to an electrical circuit and shall not have a disconnect switch between the overcurrent device and the smoke alarm; and
    5. battery-operated smoke alarms are permitted in lieu of the permanent connections referred to in (d).

  4. To ensure that occupants on one level are aware of a fire on the other level the smoke alarms referred to in 3(b) shall be:
    1. interconnected so that the activation of one smoke alarm will sound a similar signal in the other smoke alarm;
    2. audible throughout the level they are located on; and
    3. listed for use in an interconnected installation.

  5. Service existing fire extinguishers.

  6. Emergency lighting having an average illumination of at least 10m lx at floor level or 1 watt/m2 of floor space shall be provided in corridors, in locations approved by the fire department, and shall be:
    1. designed to provide illumination for a duration of 30 minutes;
    2. supplied by a source of energy separated from the primary electrical supply for the condominium; and
    3. designed to be automatically actuated when the power to the condominium is interrupted.

Alternative measures to Items 1, 2, 3 and 4 may be approved by the fire department in consideration of existing construction and alternatives permissible under Section 9.3, 9.5 and 9.6 of the Fire Code.


REASONS

Based on the evidence presented, the tribunal believed that the property was occupied as a boarding, lodging and rooming house as defined in Section 9.3 of the Ontario Fire Code, within a building that is governed by Section 9.6 of the Ontario Fire Code. At the time of the inspections, lodging was provided for more than three persons in return of remuneration or the provision of services or both, and lodging rooms do not have both bathrooms and kitchen facilities for the exclusive use of individual occupants.

The tribunal also believes that the public is entitled to a minimum level of fire safety in any building in the province of Ontario.