Office of the Fire Marshal |
OFM-TG-03-2007 |
![]() |
|
|
Outdoor Patio Fire Safety |
O
|
|
|
|
|
September 2007 |
5.1 Occupant Load Concerns
5.2 Determining Maximum Allowable Occupant Load
5.3 Sources of Ignition
5.4 Fencing and/or Barriers
5.5 Draperies, Awnings and Enclosures
5.6 Means of Egress
5.7 Fire Protection Equipment
5.8 Off Season Use of Outdoor Patios
5.9 Fire Safety Planning
7.1 Ontario Fire Code
7.2 Inspection Order
7.3 Other Agencies and Legislation
This guideline was developed to assist fire officials in assessing fire
safety issues associated with outdoor patios at restaurants, pubs, bars and
other similar assembly occupancies. The guideline provides suggestions for
enhanced communication and coordination with other agencies and discusses fire
safety enforcement strategies. This guideline is intended for guidance only and
is not to be considered a statement of law in this area.
At the first sign of warm weather in the spring, people begin to congregate
at outdoor patios associated with restaurants or pubs. After being cooped up
through the winter months, we like to leave the confines of a building and sit
outdoors at a patio to take in the sun and fresh air, and share a meal, drink or
conversation with others.
This can pose some challenges for property owners and the fire service when it
comes time to consider the fire safety of these spaces, particularly in light of
their seasonal nature. Numerous factors can impact on fire safety in these
outdoor patios, as well as on the fire safety of the adjacent indoor spaces.
Often the fire service only becomes aware of these premises when asked by a
building owner or manager to determine the allowable occupant load. This is one
facet that an owner must address when applying to the Alcohol and Gaming
Commission of Ontario (AGCO) for a licence to serve liquor at an outdoor patio.
Although the fire service is not mandated to determine occupant load, they can
have an important role to play to ensure fire safety in these spaces where the
public congregates. This guideline addresses many of the fire safety concerns
associated with outdoor patios.
Unless otherwise noted in this guideline, references to the Fire Code relate to
Division B of the Ontario Fire Code.
The words and phrases used in this guideline and in Division A of the Fire Code have the following meanings:
Outdoor patios may pose a significant fire risk to the public. Building owners and operators have an obligation to ensure the adequacy of fire safety precautions and compliance with the Fire Protection and Prevention Act and the Fire Code at their premises, and to ensure that appropriate measures are implemented to mitigate any fire safety risk. Factors for consideration and issues to be addressed may include the following:
Fire departments may want to identify facilities within their jurisdictions that
incorporate outdoor patios, and conduct inspections to ensure the adequacy of
fire safety precautions.
Fire departments may also want to use public education tools and community media
contacts to alert operators and the public to potential fire hazards associated
with outdoor patios. The public should be provided with local contact
information and encouraged to report any fire safety concerns to the municipal
fire department.
Outdoor patios associated with assembly occupancies take many forms. Some
configurations are of lower risk from a fire safety perspective, while others
may present a wide range of fire safety concerns for patrons both inside and
outside a building.
Three basic configurations are provided to illustrate various fire safety
challenges. The primary distinction between these configurations relates to
egress arrangements.
Scenario One:

Identifying Features:
Fire Safety Factors:
In this configuration, the patio occupants are
able to move quickly away from the patio in the event of an emergency, provided
the patio is located at or close to grade. Their ability to safely exit the
patio may be affected by outdoor furniture arrangements, steps, local grade
variations, patio enclosures, etc. The patio has no impact on safe egress of the
building’s occupants. A building permit may be required because of the fence or
patio construction, the potential exposure of the patio occupancy on the
building, or the egress arrangements from the patio.
Determination of an occupant load for this space may not be warranted, and some
fire departments may choose to not be involved in this situation.
A fire department may choose to comment on fire safety issues such as portable
heaters, barbeques etc., particularly in the vicinity of the exit path. There
may also be exposure issues in cases where the exterior wall has multiple
openings (e.g. windows). More details are included in Section 5.0 Fire Safety
Issues.
Scenario Two:

Identifying Features:
Fire Safety Factors:
In this configuration, one of the required egress routes from the building is
through the patio, which introduces the possibility of prolonged evacuation
times. As a result, determination of occupant load for the patio may be
appropriate to prevent this from occurring. The ability of building and patio
occupants to safely exit the patio area may be affected by outdoor furniture
arrangements, steps, local grade variations, visibility of the exit path, etc.
Other potential fire safety issues should be considered for the safe egress of
patrons, such as portable heaters, barbeques, etc., particularly in the vicinity
of the egress route.
Clearly this scenario may pose some additional fire safety concerns. More
details are included in Section 5.0, Fire Safety Issues.
Scenario Three:

Identifying Features:
Note: This scenario could also apply to a rooftop patio, which is accessed
through the building.
In this configuration, the required egress route
from the patio area is through the building, which introduces the possibility of
extended evacuation times unless the building exits have been sized to
accommodate both inside and outside occupancies. As a result, the occupant load
for the patio may need to be restricted, the interior occupant load may need to
be restricted and/or the interior exits may need to be increased. The ability of
building and patio occupants to safely exit through the building may be affected
by interior and exterior furniture arrangements, steps, etc.
Other potential fire safety issues should be considered for the safe egress of
patrons, such as portable heaters, barbeques etc., particularly in the vicinity
of the egress route.
Clearly this scenario may pose some additional fire safety concerns. More
details are included in Section 5.0, Fire Safety Issues.
The Fire Code specifies criteria for determining occupant load in a building
that contains an assembly occupancy. It does not specify such criteria for
outdoor spaces of assembly. However, as illustrated in the scenarios, there are
instances where the occupants on the outdoor patio may affect the safety of the
indoor occupants. As well, the designated indoor egress routes provided for them
might also affect the safety of the outdoor occupants.
Where patio occupants enter the building, either for reasons of convenience or
comfort (i.e. to use restrooms or access interior services) or for the purposes
of exiting the premises, consideration needs to be given to the maximum
allowable interior occupant load. For instance, the influx of patio occupants in
the event of inclement weather needs to be considered. The Fire Code does not
permit an operator of an establishment to increase the occupant load beyond the
capacity of the exits.
The owner must anticipate this situation, and
ensure that the allowable occupant load is not exceeded. The owner might choose
to limit the combined indoor and outdoor occupant load, based on the indoor exit
capacity, and allow the people to migrate between the interior and exterior.
Another approach is to advise the occupants located on the outdoor patio that in the event of inclement weather they would be asked to leave,
as they could not be safely accommodated inside. The owner’s means of ensuring
that the premises will not exceed the maximum allowable load should be
documented. This information could be maintained as part of the building Fire
Safety Plan. As well, the maximum allowable occupant load for the interior space
should be posted in a conspicuous location. There may also be merit in posting a
separate occupant load sign for the patio adjacent to the patio access.
5.2 Determining Maximum Allowable Occupant Load
Although the Fire Code does not identify a method for calculating occupant load
for outdoor space, the same criteria that are used for interior occupant load
calculations could be used.
Occupant load is calculated on the basis of use of the space and available exit
widths. When determining the occupant load based on use, general use or design
use calculations may be involved. The maximum allowable occupant load is the
lesser of the calculations based on use and available exit widths.
Calculation of occupant load on the basis of use
generally involves dividing the floor area, or part of the floor area, measured
in square metres, by the applicable “area per person” factors identified in
Table 2.7.1.A of the Fire Code. (Applicable Fire Code wording is stated in
Appendix A.)
Depending on the situation, the floor area may be the area of the room, group of
rooms, suite, portion of the floor or the total floor area. The factors listed
in Table 2.7.1.A of the Fire Code give due consideration to the typical
furnishings and fixtures associated with a specific use. The floor area
generally considers the space that is occupied, and does not include the
ancillary spaces designed and provided to support the useable space, such as
closets, cloak rooms, washrooms, corridors, exits etc.
As an alternate to using the “area per person” factors previously described, an
occupant load may also be determined on the basis of a specific layout or
designed use of the space.
For instance, a restaurant patio space may have a fixed seating arrangement that
would accommodate an occupant load that differs from that determined by using
the general use factor.
A professional engineer or architect usually conducts this type of calculation,
but “design” is not a defined term in the Fire Code.
Calculation of the occupant load on the basis of
available exit widths involves dividing the aggregate width of access to
exit or exit door openings (measured in millimetres) by the applicable “width
per person” factors that are stated for access to exits and exits in Articles
3.3.1.16. and 3.4.3.2. of Division B of the Ontario Building Code. (Applicable
Building Code requirements are stated in Appendix B.)
Where a room or floor area has more than one egress or exit door, the door
widths are added together, or aggregated, prior to
dividing by the “width per person” factor.
Where the “width per person” factor refers to a slope with a gradient of 1 in 8,
this means that the horizontal distance is 8 times the vertical dimension. In
other words, the gradient rises 1 vertical unit for every 8 units of horizontal
distance.

The maximum allowable occupant load of a floor space or room is the
lesser of the calculations based on
use of the space and
available exit widths from that space.
To ensure that emergency egress is not impeded, the Fire Code also places an
overall “cap” on the occupant load. In the case of dining, alcoholic beverage
and cafeteria space, at no time can the occupant load exceed the number
calculated on the basis of 0.60 m2 of floor space per person, and 0.40 m2 of
floor space per person for all other uses.
These caps are intended to prevent situations where the occupants are unable to
get to the means of egress because the placement of furnishings/occupants, even
though the means of egress themselves are adequate.
In addition, there may be other requirements imposed by other agencies such as
the Alcohol Gaming Commission of Ontario (AGCO) that will affect the allowable
occupant load. These requirements should never permit an occupant load that
exceeds that allowed by the Fire Code or Building Code (see Section 7.3, Other
Agencies and Legislation).
A wide variety of ignition sources may exist on outdoor patios, including
candles or similar open flames, temporary wiring and cooking and heating
appliances. Careful placement and use of these products, particularly barbeques
and patio heaters, are required to ensure the safety to occupants both inside
and outside the building. Aspects to consider include the following:
Appliances:
Other Ignition Sources:
Enclosures can take many forms for outdoor patios. Patio demarcation may be
limited to floor markings only, or may be comprised of some kind of physical
barrier that may restrict visibility, such as privacy fencing. This may include
a swinging gate with latching hardware in the enclosure. Assessment of each
situation may be required to ensure that building occupants are able to move out
of the building, through the patio, along with the patio occupants, through
openings that open in the direction of exit travel with appropriate release
hardware, to a safe location during a fire emergency.
Other agencies may have additional requirements that need to be considered. For
instance, AGCO requires outdoor patios to have a fence or other vertical barrier
to delineate the perimeter of the patio where alcohol is being served. The
required height of a fence facing the street is 1.06 metres (3.5 feet). Side
screens may be up to 2.0 metres (6.5 feet) above the grade or platform level,
and should not be entirely opaque. There may also be requirements that address
needs of visually impaired persons, to meet barrier free design, or to meet
planning and zoning requirements (See Section 7.3, Other Agencies and
Legislation).
5.5 Draperies, Awnings, and Enclosures
The use of canopies, awnings, curtains, or rain screens may present a fire
hazard, depending upon the extent of the enclosure and the materials used.
Enclosures can impede the dissipation of combustion products, which can be very
hot, and increases the risk of carbon monoxide poisoning. Further, they can
obstruct the movement of people away from the patio in the event of an
emergency. They may also present an exposure hazard to the building when there
are openings in the adjacent building wall. The Building Code would typically
not require provision of sprinklers.
Outdoor patio enclosures can also “evolve” over time. Table umbrellas may be
replaced with awnings or full overhead protection, to which side panels may be
added to block wind or rain. At some point the outdoor space takes on the
appearance of an indoor space, requiring similar fire safety considerations.
In addition, these add-ons may be subject to requirements of other agencies such
as building, property standards and by-law enforcement departments, and
provisions of the Smoke Free Ontario Act, and the
associated regulation may apply (see Section 7.3, Other Agencies and
Legislation).
To ensure the safe egress of people from an outdoor patio, a clear path must be maintained. This is particularly critical where required exit doors from a building open into/through the outdoor patio space. The outdoor patio arrangements must allow indoor patrons to evacuate through the patio space to a safe place way from the building, without restrictions or delay (e.g. such as a gate that does not swing in the direction of exit travel or should have release hardware).
Generally, an outdoor patio does not have the same need for fire protection features required inside buildings. The need to provide fire and life safety devices, such as emergency lighting, fire extinguishers, and fire alarm devices such as bells and manual pull stations requires case by case assessment. As well, an occupant load increase may have impact on the safety features of the adjacent building, as related to exiting provisions, fire alarm systems, fire alarm signals to the fire department, etc., that requires case by case assessment.
5.8 Off Season Use of Outdoor Patios
The storage of stacked patio furniture, umbrellas, planters, etc. during the off-season may pose an exposure hazard to the adjacent building or occupants. Assessment should consider the type, amount and area of storage, and the exterior wall construction. Generally, outdoor furnishings may be safely located against an exterior masonry wall that has no windows or overhang. The Building Code would typically not require provision of sprinklers.
The building fire safety plan is an appropriate document in which to record fire
safety details associated with outdoor patios. As with assembly occupancies in
buildings, records should be retained for acceptable table and chair/furnishing
arrangements, egress markings, clearances to appliances and combustibles etc.
Where an allowable occupant load for the patio has been determined, it may be
worthwhile to document any associated terms and conditions. For instance, the
methods by which the owner will control interior/exterior movement of people
during inclement weather to ensure that the occupant load is not exceeded should
be described. Related to this, clarification of staff training to deal with
outdoor patio evacuation in the event of an emergency is warranted.
There may be any number of conditions set by other agencies. The interests of
the municipal building, property standards, and/or zoning departments may be
involved, beyond the scope of fire safety, for such aspects as the size of a
patio, setbacks from street, proximity to residential areas, permanence of
fencing, fencing materials, allowable signage, accessibility and lighting,
number of washrooms, control of noise issues, etc.
Consequently, it is important to liaise with other officials within the
municipality to ensure that there is consistency in dealing with areas of mutual
interest.
A co-ordinated approach to deal with outdoor patios has numerous benefits,
including:
1. Comply with the applicable
acceptable solutions of Division B, or
2. Implement an approved alternative solution that will achieve at least the minimum level of
performance required by the applicable acceptable solution(s).
As previously noted, outdoor patios are not specifically addressed in the
Fire Code. There are many factors that impact on the fire safety of these
outdoor spaces and each situation should be assessed on the specific
circumstances.
It is appropriate to consider the principles contained in the Fire Code as part
of this assessment, even though the specific requirements may not directly
apply. For instance, the Fire Code includes requirements for buildings that can
provide guidance for fire safety concerns such as textile flammability,
accumulation of combustible materials, control of ignition sources, electrical
hazards, safe use of appliances and provision of fire protection. Similarly,
occupant load calculations for an outdoor space could consider the same criteria
that are used for occupant load calculations in buildings.
Sections 19 and 21 of the Fire Protection and Prevention
Act, 1997 (FPPA) provide authority for an assistant to the Fire Marshal
or fire chief to inspect land and premises and take measures to ensure fire
safety. This may include issuing an Inspection Order.
Where a specific situation poses a risk to the public and is not directly
addressed by the provisions contained in the Fire Code, sections 15 and 21 of
the FPPA, 1997 may be used to effect remedial work.
7.3 Other Agencies and Legislation
While this guideline specifically addresses Fire Code requirements, it is
important to note that other regulatory bodies/agencies may also have
requirements applicable to outdoor patios.
The Alcohol and Gaming Commission of Ontario (AGCO) has mandated requirements
under the Liquor Licence Act and its regulations
that relate to various facets of licensing, including the preparations of floor
plans and determination of occupant load for indoor and outdoor areas of
establishments.
The Building Code Act and the Building Code apply to
buildings where construction or a change of use occurs. A building permit may be
required for the construction of an outdoor patio that is connected to or
otherwise has an impact on the health and safety features of an existing
building. An occupant load increase may result in the need for additional safety
features related to exiting provisions, fire alarms systems, fire alarm signals
to the fire department, etc.
The Smoke Free Ontario Act, S. O. 1994 c.10, and associated
regulation O.Reg. 48/06 may also have an impact on outdoor patios,
depending upon the extent of enclosure.
In some municipalities a coordinated licensing process to deal with outdoor
patio space exists, which allows zoning, property standards, building, fire
and/or health officials to have an opportunity for input.
The Office of the Fire Marshal website can be found at
www.ofm.gov.on.ca. It
contains a variety of useful technical guidelines for fire safety planning and
other safety related materials.
For Smoke-Free Ontario information, please link with
http://www.mhp.gov.on.ca/english/health/smoke_free/legislation.asp
For information about the Alcohol and Gaming Commission, please link with
www.agco.on.ca. From the home page, go to the “Alcohol” heading to find
information about liquor licences, and associated application forms and floor
plan guide.
The Ministry of Municipal Affairs and Housing Ontario Buildings Branch website
can be accessed at
http://www.ontario.ca/buildingcode for related
materials, including Building Code Commission rulings related to patios.
Occupant load
2.7.1.4. (1) The number of persons occupying a room or floor space in an
assembly occupancy shall not exceed the
occupant load for the intended use as
determined in Sentence (2).
(2) The occupant load for any room or floor space
shall be the lower of
(a) the occupant load as calculated in accordance with Sentences (3) to (7), or
(b) the occupant load for which means of egress are provided as determined by
the Building Code.
(a) the number of fixed seats, or
(b) the number of persons
(5) Where fixed bench-type seats without arms are provided, the occupant load shall be based on a seat width of 450 mm per person.
(6) The occupant load of a room in which a dance floor is situated shall be based on that portion of the room that is not occupied by the dance floor except where the occupant load is determined using Subclause (3)(b)(i).
(7) At no time shall the maximum occupant load determined in Sentences (2) to (6) exceed the occupant load calculated on the basis of
(a) 0.60 m2 of floor space per person in dining,
alcoholic beverage and cafeteria space, and
(b) 0.40 m2 of floor space per
person for all other uses.
TABLE 2.7.1.A.
Forming Part of Article 2.7.1.4.
| Type of Use of Building or Floor Area or Part Thereof | Area per Person in m2 |
| Space with fixed seats | See Clause (3) (a) |
| Space with nonfixed seats | 0.75 |
| Stages for theatrical performances | 0.75 |
| Space with nonfixed seats and tables | 0.95 |
| Standing space | 0.40 |
| Stadia and grandstands | 0.60 |
| Bowling alleys, pool and billiard rooms | 9.30 |
| Classrooms | 1.85 |
| School shops and vocational rooms | 9.30 |
| Reading or writing rooms or lounges | 1.85 |
| Dining, alcoholic beverage and cafeteria space | 1.10 |
| Laboratories in schools | 4.60 |
| Exhibition halls other than those classified in mercantile occupancy | 2.80 |
Posting occupant load
2.7.1.5. (1) When the occupant load as determined in Article 2.7.1.4. is more than 60 persons, the occupant load shall be posted in a conspicuous location.
(2) When the occupant load has been determined using Subclause 2.7.1.4.(3)(b)(i),
a permanent sign indicating the occupant load shall be posted in a conspicuous
location.
3.3.1.16. Capacity of Access to Exits
(1) The capacity of an access
to exit shall be based on the occupant load
of the portion of the floor area served.
(2) In an access to exit
the required width of ramps with a slope not more than 1 in 8, doorways, and
corridors shall be based on not less than 6.1 mm per person.
(3) In an access to exit
the required width of a ramp with a slope more than 1 in 8 shall be based on not
less than 9.2 mm per person.
(4) In an access to exit
from a floor area used or intended to be used for
patients or residents in a Group B, Division 2 or Division 3
occupancy, the required width of corridors,
doorways, and ramps shall be based on not less than 18.4 mm per person.
(5) The capacity of stairs in an
access to exit shall conform to the requirements for stairs in Article
3.4.3.2.(1) to (3).
3.4.3.2. Exit Width
3.4.3.2. Exit Width
(1) Except as permitted by Sentence (3), the minimum aggregate required width of exits serving floor areas intended for assembly occupancies, residential occupancies, business and personal services occupancies, mercantile occupancies, and industrial occupancies shall be determined by multiplying the occupant load of the area served by
(a) 6.1 mm per person for ramps with a slope not more than 1 in 8, doorways,
corridors and passageways,
(b) 8 mm per person for a stair consisting of steps whose rise is not more than
180 mm and whose run is not less than 280 mm, or
(c) 9.2 mm per person for
(i) ramps with a slope more than 1 in 8, or
(ii) stairs, other than stairs conforming to Clause (b).
(3) The minimum required width of means of egress serving a Group A, Division 4 occupancy shall be determined by multiplying the occupant load of the area served by
(a) 1.8 mm per person for
(i) aisles,
(ii) stairs other than
exit stairs, and
(iii) ramps and passageways in vomitories and
exits, and
(b) 2.4 mm per person for exit stairs.