Office of the Fire Marshal |
OFM-TG-01-2002 |
![]() |
|
|
USE OF SCHOOLS |
O
|
|
|
|
|
January 2002 |
| SECTION PAGE |
| Abstract |
| 1.0 SCOPE |
| 2.0 SUBMISSION FOR APPROVAL |
| 3.0 SCHOOL BOARD SUBMISSION COVER LETTER |
| 4.0 WYD FIRE SAFETY PROCEDURES |
| 4.1 School Custodian |
| 4.2 Supervisory Staff |
| 4.3 Fire Wardens |
| 5.0 SITE AND FLOOR PLANS |
| 6.0 FIRE EMERGENCY PROCEDURES |
| 7.0 SCHOOL DESIGNATION FORM |
| 8.0 FIRE PROTECTION EQUIPMENT |
| APPENDICES |
| Appendix A - School Board submission Cover Letter |
| Appendix B - Fire Emergency Procedures |
| Appendix C - School Designation Form |
| January, 2002 |
| OFM Section: Fire Safety Standards at (416) 325-3100 |
The reproduction of this guideline for non-commercial purposes is permitted and encouraged. Permission to reproduce the guideline for commercial purposes must be obtained from the Office of the Fire Marshal, Ontario. |
This guideline has been prepared in cooperation with the following
organizations.
Utilization of existing facilities for activities that were not
originally anticipated in their design is becoming more prevalent as a
means of optimizing resources available to local communities. With the
World Youth Day 2002 event occurring in the Greater Toronto area and
surrounding municipalities during July, 2002, the World Youth Day
organization will have need for a number of schools to be used to
provide temporary sleeping accommodation for the people (pilgrims)
attending this event.
The Building and Development Branch, Ministry of Municipal Affairs and
Housing has indicated that the Change of Use provisions in the Ontario
Building Code were not intended for short term, temporary change of use
and would not be appropriate for this event. Assessment of this
temporary use should be carried out through an approval process under
Article 2.1.2.2. of the Ontario Fire Code.
This guideline is intended to assist school boards, the World Youth Day
organization and fire officials in the assessment of facilities to
provide temporary sleeping accommodation and sets out criteria to use in
ensuring that safeguards are in place and fire safety responsibilities
are established.
This guideline has been established to aid school board officials,
World Youth Day organizers and fire officials in the assessment of
school facilities for temporary sleeping accommodation during World
Youth Day 2002 (WYD). Sleeping accommodation will be needed from July 22
to 29, 2002.
Since sleeping accommodation is not normally considered in the design of
schools, Article 2.1.2.2. of the Ontario Fire Code would be applicable
to the temporary use.
Article 2.1.2.2. of the Fire Code states:
The Article prohibits an owner from using their facility for a purpose
other than for which it was designed without first obtaining approval
from the authority having jurisdiction, this being the Chief Fire
Official (CFO) in the municipality. Further, the Article provides the
authority for the CFO to approve the use of schools and other designated
facilities for temporary use such as sleeping accommodation. Prior to
granting approval, the CFO must be satisfied that appropriate measures
are taken in the form of fire safety systems and procedures to provide
an adequate level of life safety for the occupants who may be in the
facility at the time.
The guideline provides criteria that should be considered in determining
the suitability and approval of the facility for sleeping accommodation,
including the installation of fire safety devices and establishment of
fire safety procedures for school board personnel, WYD volunteers and
pilgrims. There are some minimum requirements that must be provided in
the facility before consideration can be contemplated and these are
identified in Part A on the School Designation Form (see
Appendix C).
Although the guideline has been developed for the WYD event, the
principles and procedures can be adapted for use in the assessment of
assembly facilities for sleeping accommodation for similar events.
The submission for approval must be made to the Chief Fire Official
(CFO) of the local municipal fire department. It is the owner's
responsibility (in this case the school board) to ensure that the
submission contains sufficient information for the CFO to make a
decision. It is also important to note that it is the owner's
responsibility to comply with all the conditions of the approval.
Prior to making the submission, it is important that the school board
meet with the local municipal fire officials to determine any additional
requirements that may be necessary for the application.
The submission for approval for temporary use should include the
following:
Each of these items is covered in more detail in the following sections.
The cover letter must be prepared by the school board identifying the
reason for the application, the period of time for the temporary use,
the accompanying documentation, and confirmation that the information
provided has been reviewed by the appropriate senior staff member.
For your convenience, a draft letter is attached in
Appendix A.
In order to ensure an adequate on site response to a fire emergency
that may occur in the facility during the temporary use, sufficient
human resources must be present in each location. These persons should
include the school custodian, at least two supervisory personnel from
the WYD organization and a pilgrim from each sleeping area to act as
fire warden for their area. Where a single sleeping area, such as a
gymnasium, has an occupant load greater than 50 persons, there must be
at least one fire warden for each 50 pilgrims.
On the first day of occupancy, fire wardens must be selected and an
initial meeting held with the school custodian, supervisory staff and
fire wardens. The duties for these individuals must be discussed and a
full fire drill held, with all occupants participating. The school
custodian, supervisory staff and fire wardens must be familiar with the
means to manually activate the fire alarm system. During the fire drill,
the occupants should become familiar with their evacuation routes and
understand where they are to meet once outside.
Duties and responsibilities for these persons must include the details
identified in subsections 4.1 to 4.3 in this guideline.
4.1 School Custodian
The custodian must be on duty at all times that the building is occupied
and be familiar with the school and its emergency equipment and systems.
Regular daily duties:
Emergency duties in event of fire or alarm:
4.2 Supervisory Staff
The supervisory staff must be readily identifiable to both the occupants
of the facility and, in the case of an emergency, to the responding fire
department. It is recommended that the supervisory staff wear a
reflective vest.
Regular duties:
Emergency duties in event of fire or alarm
4.3 Fire Wardens
Regular daily duties:
Emergency duties:
Site and floor plans of the facility must be prepared and submitted
with the application. The plans must indicate the rooms and areas where
sleeping will be taking place and the egress routes intended for use by
the occupants. A safe outside assembly area must be identified on the
site plan for the pilgrims to gather in the event of an emergency
evacuation.
A copy of the evacuation routes showing the exits from the building must
be posted in each sleeping room.
A pilgrim information sheet must be prepared for distribution to each
pilgrim at check-in, providing information on the emergency procedures
and fire safety precautions. In addition, a copy of the information
sheet must be posted in each sleeping room.
A sample information sheet is attached in Appendix
B. The sheet must be available in the appropriate languages as may
be necessary for each facility.
The school designation form should be completed and accompany the
application. This form will identify the facility, provide the name of
the contact person for the school board, indicate that the minimum
requirements for use have been met and establish the occupant load for
the facility.
A copy of the form is attached in Appendix C.
Approved single station smoke alarms must be provided in each
sleeping room and sleeping area. In large sleeping areas, such as a
gymnasium, where the ceiling height may be such that it would reduce the
effectiveness of the smoke alarms, the smoke alarm may be omitted. In
these cases, a smoke alarm is required in the corridor leading to the
gymnasium where the corridor is not already equipped with smoke
detectors connected to the fire alarm system.
Approved carbon monoxide detectors must be provided in rooms and
corridors beside service rooms containing fuel-fired appliances and in
the room directly above the service rooms.
These devices may be battery operated.
In the event that a smoke alarm or carbon monoxide detector activates,
the fire alarm emergency procedures must be initiated.
SCHOOL BOARD SUBMISSION COVER LETTER
| SCHOOL BOARD LETTERHEAD |
FIRE DEPARTMENT
| RE: | SCHOOL NAME SCHOOL ADDRESS TEMPORARY USE FOR SLEEPING ACCOMMODATION WORLD YOUTH DAY 2002 JULY 22-29, 2002 |
On behalf of the (school board), we are submitting an application to
permit temporary use of the above noted school for sleeping
accommodation for the period from July 22, 2002 to July 29, 2002.
Accompanying this application, please find attached fire safety
procedures for designated persons, site plan, floor plans indicating the
proposed sleeping areas in the school, the fire safety procedures for
pilgrims and the school designation form.
The school board will comply with the "WYD Fire Safety Procedures"
identified in Section 4 of the "Use of Schools For Sleeping
Accommodation Guideline".
All of the information has been prepared and reviewed for accuracy by:
Yours truly,
(Director of physical plant)
Upon discovery of fire
Upon hearing fire alarm
NOTE:
FIRE SAFETY PRECAUTIONS
| WORLD YOUTH DAY 2002
(WYD) - School Designation Form Temporary Use of Schools for Sleeping Accommodation |
|||||||||||
| School Name:
|
School Board (S.B.):
|
||||||||||
| Address:
|
S.B. contact person:
|
||||||||||
| Phone number: | |||||||||||
| A. Minimum requirements Yes | Yes | ||||||||||
| Mechanical/ Natural ventilation __ | WYD Fire Safety Procedures __ | ||||||||||
| Carbon monoxide
detectors provided in rooms and corridors adjacent to service rooms containing fuel-fired appliances __ |
Fire Alarm System __ Battery operated smoke |
||||||||||
| B1. Sprinklered schools __ [maximum 45 m (150 ft) travel distance to an exit] # of rooms ___ *Net area ______ # of gyms ____ Net area ______ (Hazardous classrooms excluded)Occupant load based on4.6 m² (50 sq. ft.) per person. OCCUPANT LOAD BASED ON SAFETY FEATURES = ________ Note: |
B2. Unsprinklered
schools_
maximum 30 m (100 ft) travel distance to an exit] Protected exits (Hazardous classrooms excluded) OCCUPANT LOAD BASED ONSAFETY FEATURES = ________ Note: |
B3. Unsprinklered schools
__ [maximum 30 m (100 ft) travel distance to an exit] Unprotected exits [Occupancy limited to 1st storey only] # of rooms ____ *Net area ______ # of gyms _____ Net area ______ (Hazardous classrooms excluded) OCCUPANT LOAD BASED ON SAFETY FEATURES =________ Note: |
|||||||||
C. Washrooms including urinals -
number of persons of each sex
|
|||||||||||
| TOTAL OCCUPANT LOAD (lesser of B1, B2, B3 or C) = | |||||||||||
| FOR ASSIGNMENT PURPOSES
ONLY: School barrier-free accessible YES NO Showers available YES NO |
Prepared by: (Signature): Date: |
||||||||||
| WORLD YOUTH DAY 2002 |
| Process for designation of schools used for sleeping accommodation |
|
| Operating Conditions |
|