6.1 Buildings Not Requiring On-Site Fire Protection Water Supply
- A building does not require an on-site
water supply for fire fighting if the building satisfies the criteria set
out in Section 6.1 (b) or Section 6.1 (c), provided that:
- the building is serviced by a municipal
water supply system that satisfies Section 6.3 (b) of this guideline, or
- the fire department can respond with a
transportable water supply of sufficient quantity to allow them to
conduct an effective search and rescue of the building, determined on
the basis of other guidelines or standards such as NFPA 1231, "Standard
on Water Supplies for Suburban and Rural Fire Fighting" (please
refer also to Sections 9.1 to 9.3 of this guideline).
- A building does not require an on-site
water supply for fire fighting where all the following criteria are met:
- the building area is 200 m² or less,
- the building height is 2 storeys or
less,
- the building does not have a Group B
occupancy (care or detention),
- the building does not require a
sprinkler system or a standpipe and hose system,
- the limiting distance from the property
line is at least 13 m if the building has an F-1 (high hazard
industrial) occupancy, and
- the building constitutes no significant
environmental contamination potential under fire conditions.
- A building that exceeds 200 m² in
building area or 2 storeys in building height may not require an on-site
water supply for fire fighting where it has an F-3 occupancy with an
insignificant combustible loading (such as found in cement plants, steel
stock storage sheds, etc.), as determined by the Chief Building Official.
6.2 Sprinklered Buildings
For sprinklered buildings, NFPA 13, "Standard
for the Installation of Sprinkler Systems", as referenced by Article
3.2.5.13. of the Building Code, shall be used to obtain sprinkler and hose
stream water requirements (see also Section 8.1 of this guideline).
6.3 Buildings Requiring On-Site Fire Protection Water Supply
- Except for sprinklered buildings and as
required by Sections 6.3 (c) and 6.3 (d), new buildings shall be provided
with a supply of water available for fire fighting purposes not less than
the quantity derived from the following formula:
where Q = minimum supply of water in litres (L)
K = water supply coefficient from Table 1
V = total building volume in cubic metres
STot = total of spatial
coefficient values from property line exposures on all sides, as obtained
from the formula:
|
STot = 1.0
+ [(SSide1) + (SSide2) + (SSide3) +
... etc.] |
where SSide
values are obtained from Figure 1, as modified by Sections 6.3 (e) and 6.3
(f) of this guideline, and
STot need not exceed 2.0
(see also Section 7.0 of this guideline)
- Except as provided in Section 6.3 (d),
water supply flow rates shall not be less than that specified in Table 2.
Where the water supply is from a municipal or industrial water supply
system, then the required flow rate shall be available at a minimum
pressure of 140 kPa.
- Except as provided in Section 6.3 (d),
the minimum fire protection water supply "Q" required in Section 6.3 (a)
shall not be less than what is needed to provide the minimum flow rate
specified in Table 2 for a duration of 30 minutes.
- In elementary and secondary schools, the
water supply determined in accordance with Sections 6.3 (a) and 6.3 (b)
may be reduced. The level of reduction to be applied should be at the
discretion of the local jurisdictional authority and should not exceed
30%. Factors to consider should include fire department response time,
fire department resources and the size and complexity of the school
building
(see Section 9.10 of this guideline for additional information).
Table 1: Water
Supply Coefficient - K
| |
Classification by Group or Division in Accordance with Table 3.1.2.1
of the Ontario Building Code |
| TYPE O
CONSTRUCTION |
A-2
B-1
B-2
B-3
C
D
|
A-4
F-3 |
A-1
A-3
|
E
F-2
|
F-1 |
Building is
of noncombustible construction with fire separations and
fire-resistance ratings provided in accordance with Subsection 3.2.2.
of the OBC, including loadbearing walls, columns and arches.
|
10 |
12 |
14 |
17 |
23 |
Building is
of noncombustible construction or of heavy timber construction
conforming to Article 3.1.4.6. of the OBC. Floor assemblies are fire
separations but with no fire-resistance rating. Roof assemblies,
mezzanines, loadbearing walls, columns and arches do not have a
fire-resistance rating.
|
16 |
19 |
22 |
27 |
37 |
Building is
of combustible construction with fire separations and fire-resistance
ratings provided in accordance with Subsection 3.2.2. of the OBC,
including loadbearing walls, columns and arches. Noncombustible
construction may be used in lieu of fire-resistance rating where
permitted in Subsection 3.2.2. of the OBC.
|
18 |
22 |
25 |
31 |
41 |
Building is
of combustible construction. Floor assemblies are fire separations but
with no fire-resistance rating. Roof assemblies, mezzanines,
loadbearing walls, columns and arches do not have a fire-resistance
rating.
|
23 |
28 |
32 |
39 |
53 |
Column 1
|
2 |
3 |
4 |
5 |
6 |
Table 2: Minimum Water Supply Flow Rates
|
Building Code, Part 3
Buildings |
Required Minimum Water
Supply Flow Rate (L/min.) |
| One-storey building with building area
not exceeding 600m² (excluding F-1 occupancies) |
1800 |
| All other buildings
|
2700 (If Q
£ 108,000L)(1)
3600 (If Q > 108,000L and
£ 135,000L)(1)
4500 (If Q > 135,000L and
£ 162,000L)(1)
5400 (If Q > 162,000L and
£ 190,000L)(1)
6300 (If Q > 190,000L and
£ 270,000L)(1)
9000 (If Q > 270,000L)(1)
|
| |
|
Note: (1) Q=KVSTot as
referenced in Section 3(a)
- Where a masonry wall with a minimum fire-resistance rating of 2 hours
and no unprotected openings is provided as an exterior wall, the spatial
coefficient "SSide" for this side of the new building may be
considered equal to 0. This exterior masonry wall shall be provided with a
minimum 150 mm parapet.
- Firewalls that divide a structure into two or more buildings may be
given similar consideration when evaluating the exposure of the buildings
to each other.
- The spatial coefficient "SSide" may be considered equal to
0 when the exposed building is on the same property and is less than 10 m²
in building area.
6.4 Additions to Existing Buildings
- Except as permitted in Sections 6.4 (b) and 6.4 (c), additions to
existing buildings shall be provided with a fire protection water supply
as required in Sections 6.3 (a) to 6.3 (f) (see Section 8.2 of this
guideline for additional information).
- Buildings with new additions falling into any one of the following
criteria do not require an additional water supply for fire fighting:
- the expanded building complies with all the requirements of
Section 6.1 (a),
- the new addition does not exceed 100 m² in building area, or
- the new addition exceeds 100 m² but does not exceed 400 m² in
building area, contains an assembly, business and personal services,
mercantile or low hazard industrial occupancy, is of noncombustible
construction, does not result in a significant increase in exposure to
other existing buildings, has no combustible storage or process, and
is separated from the existing building by a minimum 1 hr fire-rated
separation.
- Where a firewall is provided between the new addition and the
existing building, the fire protection water supply may be determined in
accordance with Sections 6.1 (a) and 6.3 (a), using only the building
volume of the new addition.
NOTE: Consideration should be given to designing
the water supply to the more stringent requirements of the two separated
buildings.
7.1 What is the "K" factor and how were these values developed?
The K factor, also known as water supply coefficient, is a value that
takes into account typical compartmentalization of buildings,
combustibility of construction, combustible loading of the building
occupancy and evacuation responses by the building occupants.
These factors were developed using the "occupancy hazard classification
numbers" and "construction classification numbers" in NFPA 1231, adjusting
them to fall within the occupancy classifications of buildings within the
Building Code, and then modifying them so that the final units of the
equation are in litres. Table 1 of this guideline lists K values according
to the type of construction and occupancy classification.
7.2 What volume is included in "V"?
All spaces below and above grade within a building, measured to the
underside of the roof deck, should be included in the volume (cubic metres)
for the fire protection water supply formula. An exception may be made to
exclude a non-combustible crawl space (with no combustible services) below
a non-combustible floor, located under the lowest building floor area, if
it will not be developed in the future or used as a storage area.
7.3 How are "exposures" measured?
Exposure distances from a new building are measured from the exterior
building faces to the property lines of the building. The distance from
the face of the building to the property line shall be determined in
accordance with Sentence 3.2.3.1.(3) of the Building Code. When facing a
street, the property line shall be deemed to be the centre of the street.
When facing an existing building (exceeding 10 m² in building area) on
the same property, the exposure distance (for use in Figure 1) shall be
the greater of either the "limiting distance" of the new building face as
obtained from Sentence 3.2.3.1.(1) of the Building Code, or the mid-point
between the two buildings.
7.4 How are spatial coefficient values obtained from Figure 1?
Once the exposure distance for each building face has been determined,
these values can be located along the horizontal arm at the bottom of
Figure 1. By following straight up from these points, the graph line may
be intersected providing a spatial coefficient value (SSide)
along the left vertical arm of Figure 1. Exposure distance values of at
least 10 m (except F-1 occupancies, which require a minimum of 13.0 m)
result in a spatial coefficient value of 0.
7.5 How are multiple exposures calculated?
Where a new building has exposures on more than one side, the
percentage increase in the fire protection water supply due to the
exposures on each side should be totaled to reflect all exposure
protection requirements. For example, if exposure to one side results in a
50% increase in water volume (i.e. SSide1 = 0.50), and exposure
to another side results in a 25% increase in water volume (i.e. SSide
2 = 0.25), then the total increase in water volume for exposure protection
is 75%. The spatial coefficient STot is then 1.0 + 0.50 + 0.25
= 1.75. It should be noted that STot need not exceed 2.0.
7.6 What is the rationale for the minimum 30 minute water
supply duration and what new buildings will be most affected by this
requirement?
The minimum 30 minute fire protection water supply duration
requirements as stated in Section 6.3 (b) recognizes life safety concerns
by providing a dependable and immediately available fire protection water
supply for fire department use. It is intended that the duration be long
enough to allow complete search and rescue of any building by the fire
department. This minimum fire protection water supply should also give the
fire department a reasonable opportunity to control and/or extinguish a
small fire upon their arrival, thereby preventing its growth and spread to
adjacent buildings and limit any negative environmental impact. This
minimum 30 minute duration requirement also allows a reasonable time for
the fire department to arrange for supplementary water supplies using a
water shuttle system for most buildings.
Concerns for minimum fire protection water supply volumes are mostly
relevant for building sites not serviced by municipal water supply
systems, where an on-site fire protection water supply has to be provided.
Building sites serviced by municipal water supply systems are usually
provided with sufficient water volumes for their fire protection needs.
This guideline focuses on water supply flow rates at minimum pressures for
these buildings. It should be noted however that some municipalities have
fairly limited water supply storage capacities and should therefore be
evaluated when a new "high demand" building is to be constructed.
7.7 How do exterior 2hour rated masonry walls with parapets and
no unprotected openings and interior firewalls influence exposure, and
thus water supply calculations?
Interior firewalls and exterior masonry walls fire rated for 2 hours,
with parapets and no unprotected openings, are expected to remain in place
during the period that fire exposure is greatest. Exposure to adjacent
buildings is reduced to a point where additional exposure protection water
may not be needed.
Judgment by the Chief Building Official should be used in determining
the design of exterior 2 hour fire-rated masonry walls and interior
firewalls with regard to exposures. The usual 150 mm (6 inch) parapet may
not be considered adequate exposure protection where a new building
exposes a much higher existing building in close proximity. Rather than
having to increase the water supply due to exposure, a higher parapet may
be sufficient protection. In situations where parapet design or other
methods do not provide adequate exposure protection for the existing
building, then additional exposure fire protection water may be required.
Where firewalls divide a new facility into separate buildings, the fire
protection water supply should be sized to the building with the greatest
water supply demand.
7.8 What would be the impact on fire protection water supply
requirements for a new building if an existing exposed property has its
own on-site fire protection water supply?
Where a new building exposes an existing property provided with its own
independent on-site fire protection water supply, the Chief Fire Official
may deduct this water supply from the quantity needed by the new building
due to this exposure. This neighbouring water supply should be accessible
to the fire department to protect exposed buildings.
The Chief Fire Official should be satisfied that the two property
owners will properly maintain their respective fire protection water
supplies for the life of their buildings. This agreement may require
approval from the municipality and may be subject to criteria provided by
the Building Code Commission.
8.1 Regarding sprinklered buildings, where in NFPA 13 are hose
stream requirements specified?
NFPA 13 contains the hose stream requirement for sprinklered buildings
in the "Occupancy Hazard Fire Control Approach" section (in Chapter 5 of
1992 to 1998 NFPA 13 editions). Within, is a table entitled "Hose Stream
Demand and Water Supply Duration Requirements". This table provides total
inside and outside hose stream requirements and duration for each hazard
classification of sprinkler system design.
A sprinkler contractor designing a sprinkler system for a building will
determine the minimum water supply requirements for the sprinkler system.
Using the duration period obtained from the above referenced table, the
contractor will add the sprinkler and hose stream requirements and
calculate the total fire protection water supply required for the
building.
8.2 Where new additions are added to existing buildings
that do not have an on-site water supply, what volumes of water are
considered adequate for life safety and exposure?
Whereas Part 11 of the Building Code indicates that only the addition
to an existing building is required to conform to Part 3 of the code, this
might in reality not be adequate to deal with life safety and exposure
where fire protection water supply needs are concerned.
When an addition is added to an existing building and water supply
calculations are based only on the volume of the addition, the fire
protection water supply provided on-site might not be adequate to allow
full search and rescue throughout the entire building. As well, exposure
to neighbouring buildings from the new addition may not be reflective of
the nature and size of a potential fire in the enlarged building.
Calculations using the entire volume of an expanded building therefore are
the only accurate indication of fire protection water supply needs.
8.3 Does this guideline apply to buildings that are being
renovated under Part 11 of the Building Code?
Part 11 of the Building Code should be reviewed to determine the
conditions under which Article 3.2.5.7. applies. This is found in the
Compliance Alternative tables in Part 11.
Where Article 3.2.5.7. does apply, the existing water supply should be
evaluated to determine if it is sufficient for the renovated building.
Some discretion may be used by the building official if the water supply
for the renovated building is not significantly greater than the existing
water supply.
9.1 Can water transported by the fire department be
satisfactory to protect small buildings?
Smaller buildings (2 storeys or less in building height and with a
building area of 200 m² or less) may be adequately protected by the fire
department using proper pre-planning methods and transported fire
protection water supplies. NFPA 1231 "Standard on Water Supplies for
Suburban and Rural Fire Fighting" provides methods to assist the fire
department with this pre-planning. Where the fire department does not have
the equipment necessary for proper water shuttle system to adequately
protect these smaller buildings as per NFPA 1231, an on-site fire
protection water supply should be considered.
9.2 What extra precautions, if any, should be taken for
institutional occupancies?
Buildings with Group B, Division 1, 2 and 3 occupancies should be
treated in a special manner with respect to fire protection water
supplies. The occupants of these buildings require direct supervisory
assistance for phased evacuation during a fire. This could result in a
prolonged search and rescue by the fire department. If this type of
building is located in areas not serviced by municipal water mains, the
fire protection water supply that the fire department is capable of
transporting to the site may not be adequate for the duration of this
search and rescue period. Only a properly sized on-site fire protection
water supply will provide the hose stream duration that the fire
department needs. Alternatively, sprinkler protection could be provided.
9.3 What provisions should be made where fire department
response is slow or nonexistent?
For new buildings constructed in areas where fire department response
is not expected in a reasonable time, sprinklers should be installed to
help ensure safe evacuation. In locations where a fire department
pumper truck is not available,
consideration should be given to installing a private water supply. The
water supply should be capable of providing a minimum 700 kPa (100 psi)
water pressure at the required flow rate to permit fire fighters or other
persons trained in the use of fire hoses, to effectively use a
"fog-nozzle" hose spray on the fire. This type of hose spray is most
effective at controlling fires. Alternatively, sprinkler protection could
be provided.
9.4 How should an outdoor reservoir be designed to take ice
formation into account?
When designing an open, unheated reservoir to provide a fire protection
water supply as required in this guideline, a 600 mm ice depth allowance
should be included in the water volume calculations. Where local winter
temperature conditions result in a greater ice depth (as typically found
on local lakes or ponds), this should be factored into the volume
calculations.
9.5 What provisions should be made to ensure that water
reservoir supplies do not drop to unsafe levels as a result of evaporation
or leakage?
A make-up water supply should be provided to maintain the design volume
of fire protection water supply reservoirs. Storage tanks should be
provided with limit switches, pressure gauges or water level gauges to
monitor volume.
If make-up water supply for open water supply reservoirs is provided by
natural refill methods (i.e. water table seepage) and periods of drought
are common, the reservoir capacity should be increased to take into
account the reduced water table levels expected from the evaporation of
water.
9.6 What standards should be used to provide an acceptable
water supply design?
Tanks should conform to NFPA 22 "Water Tanks for Private Fire
Protection" and the local fire department should be consulted to
determine appropriate connections for their pumping equipment.
Fire main installations should conform to NFPA 24 "Private Fire
Service Mains and Their Appurtenances".
On-site fire pump installations should conform to NFPA 20 "Standard
for the Installation of Centrifugal Fire Pumps".
Standards such as NFPA 13D "Installation of Sprinkler Systems in
One- and Two-Family Dwellings and Mobile Homes" and NFPA 13R "Installation
of Sprinkler Systems in Residential Occupancies Up To and Including Four
Stories" may be used where appropriate for the type of building
covered by these standards. These other standards should be acceptable to
the local jurisdictional authority in addition to NFPA 13 "Standard
for the Installation of Sprinkler Systems".
For new buildings that present a special hazard to a community as a
result of their size, occupancy or economic importance, the Fire
Underwriters Survey Guide should be used to determine suitable water
supply and hydrant siting.
9.7 For evaluation of the fire protection water supply and
associated fire hydrants, are there other considerations in addition to
those set out in the Building Code?
Impounded fire protection water supply for a remote building shall be
accessible to the fire department to allow the use of suction lines for
drafting either directly from the impounded water source, or from a dry
hydrant supplied from the impounded water source. This water source or
hydrant shall be located to comply with Sentence 3.2.5.7.(2) of the
Building Code.
Where at least two widely separated private fire hydrants are required
to protect a building and water is to be supplied from a single on-site
fire protection water supply (e.g. reservoir), it is acceptable to provide
a fire department pumper connection adjacent to the water supply to allow
a pumper truck to pump into an underground "dry" main feeding the two
remote hydrants. This arrangement permits fire fighters to attach hoses
directly to the hydrants or to use a second pumper truck to draw boosted
water from these hydrants.
Existing water flow test information being used to determine the
adequacy of the municipal or private water supply for fire protection of a
new building should be evaluated with regard to the age of the test.
Consideration should also be given to whether the flow test was conducted
during high or low demand periods and whether the possibility that future
development in the area will significantly affect the supply. A current
hydrant flow test at the proposed construction site will provide the most
accurate information.
When dealing with new buildings serviced by municipal or industrial
pressurized fire protection water systems, this guideline specifies a
minimum water flow rate at 140 kPa pressure. This pressure is the accepted
minimum that most fire departments will allow service mains to be drawn
down to. Water main and/or booster pump damage could occur from cavitation
at pressures below this level.
9.8 Can this guideline be used for Part 9 of the Building
Code?
The Building Code does not currently require that Part 9 buildings be
provided with an adequate water supply for fire fighting. However, this
guideline may be used on a voluntary basis to provide a suitable fire
protection water supply for these buildings.
The Water Supply Adequacy Committee recommends that an on-site fire
protection water supply as required by this guideline be provided for
multi-unit residential (Group C) type buildings (i.e. hotels, motels,
apartments, townhouse complexes, etc.) that fall within Part 9 of the
Building Code. These buildings inherently have delayed building
evacuation, resulting in more extensive search and rescue operations, and
will likely benefit from an on-site fire protection water supply.
9.9 How are standpipes and hose systems affected by these
requirements?
Where a building requires a standpipe and hose system under the
Building Code, the standpipe system should continue to be designed to
Article 3.2.9.2. The standpipe will draw from the required water supply
specified in this guideline, still leaving a significant fire protection
water supply for exterior hose stream use.
9.10 Can the water supply requirements of this guideline be
reduced in buildings with an established fire safety plan that can ensure
a rapid building evacuation?
Elementary and secondary schools have a record of well-established and
practiced fire safety plans, which allow complete school evacuations
within 4 minutes. Because of this and the inherent high level of
supervision in these types of facilities, a reduction of up to 30% in the
fire protection water supply requirements as set out for unsprinklered
buildings in this guideline, may be given. However, caution should be used
if the duration of water supply is reduced to less than 30 minutes, unless
other compensating features are also provided.
Another factor that should be considered is accessibility for disabled
students and teachers within the general school population. A delayed
evacuation may be expected for these occupants of the building. This could
result in prolonged search and rescue operations by the fire department
and should be considered when determining water supply reductions.
9.11 Can the water supply requirements of this guideline be
reduced if alternate fire suppression methods are proposed?
Alternate fire suppression methods may result in reduced water supply
requirements when compared to design parameters set out in this guideline.
Questions should be directed to the local authority that has jurisdiction
over these matters.
Alternative fire suppression methods being considered for allowing a
reduction in the water supply requirements of this guideline are,
foam/water extinguishing systems, carbon dioxide extinguishing systems or
dry chemical extinguishing systems. Exterior water curtain (deluge)
systems may be considered in lieu of fire protection water supply
requirements for exposure purposes.
PROBLEM #1
A new apartment building is to be constructed in your municipality. The
building will measure 30 m by 25 m, with 3 m between floors, and consists
of 3 storeys plus a basement used for storage and laundry facilities.
Parking will be outside. The building is to be of combustible construction
and is to conform to Article 3.2.2.47. of the Building Code (1997
edition). An attic space is also provided in this building with a 750 m³
volume. A 30 minute fire separation is provided between the third floor
and the attic space. The building is not to be sprinklered nor provided
with a standpipe system.
The building is located on a corner lot and faces 2 streets (see
diagram). Property lines are located 5 m to the south and 7.5 m to the
east of the proposed building. All of the buildings are serviced by
municipal water mains and hydrants. What is the required minimum flow rate
of the municipal main for an adequate fire protection water supply?
SOLUTION - PROBLEM #1
- Determine building classification:
Residential apartment is Group C.
- Check parameters of Section 6.1 to determine whether the
building requires an on-site water supply:
Building exceeds 200 m², is two storeys in building height with
significant combustibles and is not a Part 9 building under the Building
Code, therefore needs a water supply evaluation.
- Calculate Q=KVSTot:
- Determine K from Table 1.
Based on building construction and classification, the water supply
coefficient K=18.
- Calculate the building volume, V= L × W × H.
Use total height of building, 3 storeys plus basement, and attic space
(750 m³) (3 m between floors × 4 floors =12 m).
V= (30m × 25m × 12m) + 750 m³ = 9750 m³
- Determine STot from Figure 1.
Consider each side of the building.
The north and west sides of the building each face a street and the
distance to the centre of the streets exceed 10 m, therefore SSide
will be equal to 0.0 on both sides.
The property line is 5 m to the south of the building. From Figure 1,
SSide is equal to 0.5, meaning that a 50% increase in the
volume of water will be required to protect this side.
The property line to the east of the building is 7.5 m. From Figure 1,
SSide is equal to 0.25, meaning that a 25% increase in the
volume of water will be required to protect this side.
Therefore, because of the exposure on the south and east sides of the
building, it will be necessary to increase the total volume of the
water by 75% (the sum of all the spatial coefficients from each side).
i.e. STot = 1 + (total of spatial coefficients)
= 1+ ( 0.5 + 0.25 )
= 1.75 (Note: STot need not exceed 2.0)
therefore, Q = KVSTot
= 18 × 9750 × 1.75
= 307,125 L
Determine the water supply flow rate:
From Table 2, (since the building either exceeds 1 storey or its area is
greater than 600 m², and the calculated Q is greater than 270,000 L) the
required minimum water supply flow rate from the municipal system would
be 9000 L/min. This flow rate is required at 140 kPa in accordance with
Section 6.3 (b).
PROBLEM #2
A single storey warehouse and distribution centre, classified as a low
industrial hazard occupancy, is to be built in an area
not serviced by a municipal water supply.
The building is to be 1500 m² in area, 4 m high and of noncombustible
construction conforming to Subsection 3.1.5. of the Building Code. This
building falls within Article 3.2.2.80. of the Building Code. Storage
commodities vary, but in general are farm implements in wood crates.
The warehouse faces one street to the north, with property lines 30 m
to the east and 7.5 m to the west. An existing building is located on
the same property and will be 20 m to the south of the proposed new
warehouse. The new warehouse building will have 10% unprotected openings
in its south face.
There is a similar type warehouse that has its own 20,000 litre
on-site fire protection water supply located to the west. This water
supply is determined by the fire department to be reliable and
accessible. How much water will be required on site for fire protection
of the proposed building?
SOLUTION - PROBLEM #2
- Determine building classification:
Proposed low hazard warehouse building is Group F-3.
- Check parameters of Section 6.1 to determine whether the
building requires an on-site water supply:
Building is a Part 3 building (under the Building Code) as it exceeds
600 m²in area and has a significant combustible loading, therefore it
needs an on-site water supply.
- Calculate Q=KVSTot:
- Determine K.
From Table 1, based on building construction and classification, the
water supply coefficient K=19.
- Calculate the building volume, V= Area × H = (1500 × 4) = 6000
m³
- Determine STot from Figure 1 by considering each side
of the building.
On the east side of the proposed building the distance to the
property line exceeds 10 m so no increase in water volume is
necessary.
The proposed building faces a street on the north side with
distance to the centre of the street 10 m away. No increase in the
water volume will be required due to lack of exposure on this side.
The proposed building faces an existing building on the same
property, 20 m to the south. The 10% unprotected openings in the
south building face of the proposed building results in a "limiting
distance" of 2.5 m using Table 3.2.3.1.A. of the Building Code.
Since the mid-point between the two buildings on the same property
(10 m) is greater than the limiting distance of the south face of
the new building, the 10m is deemed the exposure distance. No
increase in water volume will therefore be needed from exposure on
this side.
The property line to the west is 7.5 m from the exterior wall,
which means a 25% increase in the volume of water to protect the
property on that side. However, the neighbour's warehouse has its
own reliable 20,000 litre fire protection water supply, so this can
be used to reduce the exposure needs. Exposure calculations should
be completed to evaluate the neighbouring water supply, therefore:
STot = 1 + total of spatial coefficients
= 1 + (0.25 ) = 1.25
and, Q = KVSTot
= 19 × 6000 × 1.25 = 142,500 L
Of this amount, 28,500 L (142,500 - 114,000 = 28,500) is required
for exposure, of which 20,000 L is already provided on the exposed
property. Therefore, an additional 8,500 L should be added to the
on-site water supply to make up the shortfall in exposure
protection. Therefore, Q= 122,500 L (114,000 + 8,500 = 122,500).
4. Determine the water supply flow rate:
From Table 2, since the building area exceeds 600 m² and the
calculated Q is greater than 108,000 L but less than 135,000 L, the
required minimum water supply flow is 3600 L/min. However, in
accordance with Section 6.3 (b) it must also be confirmed that 3600
L/min. can be delivered for a minimum of 30 minutes. Since a 34 minute
duration is achieved (122,500 ÷ 3600 = 34 minutes), this is
satisfactory.
PROBLEM #3
An existing 400 m² single storey (with basement) school is being
provided with a 400 m² addition of noncombustible construction. The
existing building is of combustible construction with a 45 minute
rated roof and basement ceiling (structural supports rated as well),
while the new addition is of noncombustible construction as well and
meets the requirements of Article 3.2.2.25. of the Building Code. Both
the new and existing buildings are provided with full basements, 2.5 m
in height. The ground floor has a ceiling height of 3.0 m. An attic
space is provided in both buildings, each with a volume of 800 m². A 1
hour fire rated separation is to be provided between the new and
existing structures.
No water mains or hydrants are located in the area. A hose
standpipe is voluntarily being provided throughout the entire
building, with a booster pump. Distances to the property lines are as
indicated on the accompanying sketch. An all volunteer fire department
with limited equipment is located within 20 minute response of the
building site.
What size pond is needed on site (assuming no freezing
temperatures), to ensure minimum life safety requirements?
SOLUTION - PROBLEM #3
- Determine building classification:
School building is Group A-2.
- Go to Section 6.4 (a) (iii) of this guideline. This section
indicates that a single storey, noncombustible addition with an
assembly occupancy, up to 400 m² in building area, with no
combustible storage or process and separated from the existing
building by a minimum 1 hour fire separation does
not require additional water supplies
for fire fighting purposes.
- The municipal jurisdictional authority however, may also wish to
take into consideration the ability of the local fire department to
provide an effective water supply shuttle system to this school by
using NFPA 1231 as a reference. If equipment is not available to
provide effective amounts of water supply, then an on-site water
supply may be the best choice. Please refer also to Section 6.1 (a)
(ii) of this guideline.
- If an on-site water supply is chosen, it may be sized by
calculating Q = KVSTot:
- Although Part 11 of the Building Code would only size the
on-site water supply based on the addition, the fire department
should determine if this is sufficient for their search and rescue
needs.
- Assuming the entire building volume is selected to determine
Q, determine K.
From Table 1, based on building construction and classification,
the water supply coefficient for the existing building is K=18 and
for the new addition K=16.
- Calculate the building volume, V = L × W × H
VExisting = (400 × 3) + (400 × 2.5) + 800 = 3000
m³
VAddition = (400 × 3) + (400 × 2.5) + 800 = 3000
m³
Determine STot.
From Figure 1, since no property lines are less than 10 m away,
all SSide = 0.0, no additional water volume is needed
for exposures and therefore STot=1.0
Q = KVSTot
= (KVSTot)Existing + (KVSTot)Addition
= (3000 × 18 × 1.0) + (3000 × 16 × 1.0)
= 102,000 L
This is the required pond size, assuming a means to maintain
the water level and no freezing concerns. Note that Section 6.3
(d) also allows a reduction in the water supply and flow rate for
schools. This reduction may not be considered due to the volunteer
fire department with limited equipment.
Determine the water flow rate:
From Table 2, since the building area exceeds 600 m² and the
calculated Q is less than 108,000 L, the required minimum water
supply flow is 2700 L/min. However, in accordance with Section 6.3
(b) it must also be confirmed that 2700 L/min. can be delivered for
a minimum of 30 minutes. Since a 38 minute duration is achieved
(102,000 ÷ 2700 = 38), this is satisfactory. Note if the water
supply was sized only to the addition, then a 54,000 litre pond,
allowing a 30 minute duration at a flow rate of 1800 L/min. would be
required. However, at 2700 L/min., which is a reasonable flow rate
for the entire structure, this provides only 20 minute duration.
PROBLEM #4
A 300 m² single storey restaurant is to be constructed of
noncombustible construction in a town with a marginal water supply
due to old mains and poor grid system. The municipal water reservoir
is sized for 4,546,000 L (1.0 million Imperial gallons). The
building will have a 3.5 m high ceiling. No hose standpipe or
sprinklers are planned. Is the existing street supply adequate?
Property lines are located 11 m to the east and 20 m to the
south. Street centreline distances are 10 m to the north and west.
The fire department routinely arrives at a fire scene in this
part of town with a tanker/pumper truck carrying enough water (4500
L) for two 38 mm hoses adequate for 5 minutes of discharge. The
hydrant at the street can provide 1500 L/min. at 140kPa.
SOLUTION - PROBLEM #4
- Determine building classification:
Restaurant building is Group A-2 occupancy.
- Check parameters of Section 6.1 to determine whether
building requires an on-site water supply:
The building falls within Part 3 of the Building Code.
The building area is more than 200 m² and is not an F-3 occupancy.
- Compare existing water supply with required water
supply:
As the building does not exceed 600 m², the required water supply
flow rate from Table 2 for this size building is 1800 L/min.
Provided public water supply from hydrant at street is 1500
L/min at 140 kPa (adequate volume of supply).
Transported water supply by fire department is 4500 L.
The required water supply shortfall from the public supply is
(1800 − 1500) = 300 L/min. The transported water supply by the
fire department will last 15 minutes if used at a flow rate of 300
L/min (4500 ÷ 300 = 15 minutes) to make up the shortfall from the
public supply.
- Solutions to make up water supply shortfall:
Option #1 - As the total water supply that is
deemed adequate for this new building is 1800L/min x 30 minutes =
54000 L, and the provided water supply is (1500 × 30) + 4500 =
49500 L, then an additional on-site water supply of 4500 L could
be provided.
Option #2 - Provide an additional
transportable water supply source (i.e. tanker truck) of 4500 L.
Option #3 - The municipal authority may
determine that 1650 L/min is satisfactory based on building
occupancy and layout, and the restaurant's fire safety plan. The
municipal authority may also determine that "life safety" is no
longer a significant concern after 15 minutes in this type of
occupancy and the remaining public water supply is satisfactory
for exposure concerns.
PROBLEM #5
A new 4 storey plastics extrusion plant (F-2 occupancy) is being
constructed in a town with a marginal water supply. The
flat-roofed building will cover a 500 m² area and be 12.0 m in
overall height. Construction is to be combustible and in
conformance with Article 3.2.2.70. of the Building Code. The roof
and floor separations have a fire-resistance rating of 45 minutes.
Exposure includes property lines 2 m and 3.5 m away and street
centrelines 9 m and 15 m away to the west and north. What is the
required water supply from the street mains for this new building?
SOLUTION - PROBLEM #5
- Determine building classification:
Group F-2 occupancy.
- Check parameters of Section 6.1 to determine whether
building requires an on-site water supply:
The building is a Part 3 building (under the Building Code) as
it meets dimensional parameters (i.e. more than 3 storeys).
- Calculate Q = KVSTot:
- Determine K.
From Table 1, based on building construction and
classification, the water supply coefficient K=31.
- Calculate the building volume, V = L × W × H = 500 × 12 =
6000 m³
- Determine STot from Figure 1 (consider each
side of the building).
The street centreline to the north is more than 10 m away
thereby providing no exposure concerns.
The street centreline to the west is 9 m away thereby
resulting in an SSide of 0.1.
The P/L to the east is 2 m away resulting in an SSide
of 0.5.
The P/L to the south is 3.5 m away, resulting in an SSide
of 0.5.
Therefore the resulting total of spatial coefficient
values is:
STot = 1+ (0.1 + 0.5 + 0.5)
= 1 + (1.1)
= 2.1
However as STot need not exceed 2.0, assume STot
= 2.0.
- Therefore, Q = KVSTot = 31 × 6000 × 2.0 =
372,000 L.
It should be confirmed that the municipal reservoir has this
reserve fire fighting water supply capacity.
Determine the water supply flow rate:
From Table 2, this type of building requires a minimum fire
protection water supply flow rate of 9000 L/min at 140 kPa.
Water flow tests on street hydrants at the building site should
confirm this minimum flow.
PROBLEM #6
A 200 m² single storey flammable liquids storage and paint
mixing room is being constructed on the southwest corner of this
existing remote 600 m², single storey metal parts fabricating
and treating plant. The property line is no closer than 60 m
from the building in the south, east and west directions. The
centreline of the highway to the north is 12 m. An existing
22,730 L (5,000 Imperial gallons) fire protection water supply
is currently provided on-site, with a dry hydrant to provide
fire department draft from this reservoir.
The building is located in an area surrounded by agricultural
lands used for growing cash crops, and lakes used to provide
potable water for the local communities.
The existing building has interior hoses but no sprinklers.
The new addition is to be separated from the existing building
by a 2 hour firewall, but is not to be sprinklered. The addition
is to be 4 m in height and of noncombustible, non-rated
construction. The walls of the addition at right-angles to the
existing building are blank masonry, while the masonry walls of
the existing building at right-angles to the addition have 10%
openings. Is the existing water supply sufficient for the
addition or the existing building.
SOLUTION - PROBLEM #6:
- Determine new building classification:
Group F-1 occupancy.
- Check parameters of Section 6.4 for this addition:
Section 6.4 (c) deals with firewalls separating additions from
existing buildings. Check parameters of Section 6.1 to
determine whether the addition requires an on-site water
supply. The addition has an F-1 occupancy and is therefore a
Part 3 (Building Code) building. Because the chemical
occupancy of the addition may result in a significant adverse
environmental potential to the local aquifer, the addition
does not fall within Section 6.1. Therefore check Sections 6.2
and 6.3.
- Addition is not to be sprinklered so Section 6.2
does not apply.
- From Section 6.3, calculate Q for the addition
using Q=KVSTot:
- Determine K.
From Table 1, based on building construction and
classification, the water supply coefficient K=37.
- Calculate the building volume, V = L × W × H = 200 × 4 =
800 m³.
- Determine STot from Figure 1 (consider each
side of the building).
The P/L to the east, west and south exceeds 13 m
resulting in SSide values of 0 in each direction.
To the north, the limiting distance to the south exposed
wall of the existing building from the blank west wall of
the addition is determined from Sentence 3.2.3.1.(1). of the
Building Code. Because of the blank masonry wall, the
limiting distance is 0.
Therefore the resulting total of spatial coefficient
values is:
STot = 1 + ( 0 + 0 + 0 + 0 ) = 1.0
- Therefore, Q= KVSTot
= 37
× 800 × 1.0
= 29,600 L
Determine the water supply flow rate:
From Table 2, F-1 occupancy buildings require a minimum fire
protection water supply flow rate of 2,700 L/min. The existing
on-site fire protection water supply of 22,730 L (5,000
Imperial gallons) can provide this flow rate for 8 minutes.
Since a minimum 30 minute duration in water supply is
needed, an additional 58,250 L of on-site water supply is
needed for the addition to make up the shortfall
(81,000-22,750 L).
The existing building may also be evaluated to determine if
water supply requirements for that portion would be higher.
The owner may decide to provide additional water to meet the
higher demand.
Under the Building Code the existing building also has to
be evaluated to determine that exposure has not increased due
to the location of the addition.