Office of the Fire Marshal |
OFM-TG-02-1998 |
![]() |
|
|
FIRE ALARM
|
O
|
|
|
|
|
June 1998 |
The reproduction of this guideline for non-commercial purposes
is permitted and encouraged. Permission to reproduce the guideline
for commercial purposes must be obtained from the Office of the
Fire Marshal, Ontario.
1. Scope
2. Background
Option 2: The Fire Alarm Signal Provides 55 - 59 dBA
Option 3: In-Suite Fire Alarm Signal Devices
Option 4: Conduct An Acoustical Evaluation
5. Additional Information
Appendix A: Sound Level Measurement
A.2 Measurement Method
A.3 Selecting The Test Suite
A.4 Ambient Sound Level Measurements
June, 1998
OFM Section: Fire Safety Standards at (416) 325-3100
The reproduction of this guideline for non-commercial purposes is permitted and encouraged. Permission to reproduce the guideline for commercial purposes must be obtained from the Office of the Fire Marshal, Ontario.
The Building Code includes a requirement that the sound pressure
level for a fire alarm system in residential sleeping rooms be
not less than 75 dBA. Although the Fire Code does not prescribe
specific sound pressure levels for fire alarm systems in existing
buildings, fire safety plan requirements are based on the premise
that occupants will be alerted to a fire alarm condition in the
building. This document was developed to provide guidance to fire
departments and building owners in achieving fire alarm audibility
levels consistent with fire safety plan objectives, provide for
consistency of application and ensure compatibility with the provisions
of the Building Code. The guideline describes the methodology
and criteria for the evaluation of existing fire alarm signal
levels and the necessary upgrades.
1.0 Scope
This guideline has been established for the assessment of fire
alarm audibility in existing buildings of residential occupancy
where there is concern that the signal from the fire alarm system
may not be heard intelligibly throughout the floor area in which
the audible devices are installed. The guideline provides consistent
methodology and criteria for the evaluation of existing alarm
signal levels and the necessary upgrades.
This guideline does not apply to fire alarm system installations
in new construction. Reference should be made to the Building
Code for appropriate requirements.
2.0 Background
The Building Code applies to new construction (including additions),
renovations and change of use. The 1997 Building Code adopted
a requirement that the sound pressure level in a sleeping room
of residential occupancy shall be not less than 75 dBA when any
intervening doors between the audible signal device and the sleeping
room are closed. The 75 dBA provision is based on measurements
taken in an unfurnished and unoccupied suite. The Building Code
also requires that the sound pressure level not exceed 100 dBA
beyond a prescribed distance from the audible signal device.
The Fire Code applies to existing buildings. Currently, the Fire Code does not prescribe specific sound pressure levels in existing buildings with respect to fire alarm audibility. However, Section 2.8 of the Fire Code requires that a fire safety plan be prepared, approved and implemented in every residential building where the occupant load exceeds 10 persons. The fire safety plan must include procedures that occupants are expected to follow upon hearing the fire alarm. Fire alarm audibility is therefore an inherent component of fire safety planning and evacuation.
This document was developed to provide guidance to fire departments and building owners in achieving the intended objective of the Fire Code with respect to fire alarm audibility, provide for consistency of application and ensure compatibility with the provisions of the Building Code.
Compliance with any one of the following four options is deemed to provide an acceptable audibility level in an existing building of residential occupancy.
For example, the plan may include provisions for voice messages, floor wardens, a buddy system or telephone network to supplement the fire alarm signals. In no case should the procedures involve actions that would expose occupants to unnecessary risk in the event of a fire. The fire safety plan should also include regular educational programs for the occupants and training for supervisory staff to reinforce the special procedures that have been identified.
| Fire Alarm Signal Sound Level (dBA) |
Maximum Ambient Sound Level (dBA) |
|---|---|
55 | 40
|
56 |
42
|
57 |
44
|
58 |
46
|
59 |
48
|
Option 4: Conduct An Acoustical Evaluation
A professional engineer specializing in acoustical evaluation shall evaluate the fire alarm signal audibility using octave band measurements of the fire alarm and ambient sound levels. The report must conclude whether or not the fire alarm signals can be heard intelligibly throughout the building with all supporting data and rationalization provided. Alarm sound pressure levels of less than 55 dBA should only be permitted where compensating measures are present and are fully documented and acceptable to the Chief Fire Official.
4.0 Corrective Action
Where there are residential suites in the building that do
not meet the fire alarm audibility acceptability criteria established
in this guideline, the owner should take the following corrective
actions:
Audible signal devices installed to comply with this guideline must not exceed the sound pressure level as prescribed in the Building Code.
Where the owner has not taken corrective action to achieve compliance with this guideline and the fire alarm audibility poses a risk to the safety of the occupants, the fire department may issue an order under the Fire Protection and Prevention Act, 1997.
For additional information on this guideline, please contact your
local fire department or the Office of the Fire Marshal at (416)
325-3100.
The sound level meter shall have a measurement range that permits readings as low as 35 dBA and shall be calibrated immediately before and after the audibility measurements are taken. The use of a quality meter is important to minimize any measurement errors. ANSI S1.4-1971 "Specification for Sound Level Meters" is one standard that can provide guidance on the subject.
A.2 Measurement MethodThe meter is to be held approximately 1.5 meters above the floor and at least 0.5 meters away from hard reflecting surfaces. The meter should also be held as far away as practical from the body of the person taking the measurement.
The meter is to be set to the "A" weighted measurement scale and to the fast response setting. The measurement is to be made in the approximate centre of the most acoustically remote bedroom of the residential suite. The suite door, bedroom door and any intervening doors are to be closed. The bedroom windows are to be closed. The measurements in the bedroom are to be made within a one meter radius of the centre of the room.
Sound meters must be used per the manufacturer's instructions. The number and type of measurements taken may vary. Two common methods are described below.
An integrating type sound level meter provides calculated Equivalent Sound Level (Leq) readings. The meter takes sample measurements once per second and over a 20 second sample period. Ensure that intermittent noises do not occur during the sample period.
Non-Integrating Type MeterA non-integrating type sound level meter requires a series of separate measurements to be taken. It is recommended that four measurements be obtained. The average of the three closest readings should be recorded. Visual averaging of meter readings may be performed in lieu of the above.
The suite selected for the sound measurements should be representative of the lowest fire alarm system audibility. This will generally be the suite with the greatest number of bedrooms, the one located at the far end of a corridor, or the one located in the far corner of the building. Wall to wall carpeting may also significantly reduce fire alarm audibility. It may be necessary to conduct exploratory measurements to identify the suite or suites that represent the lowest audibility levels in the building. The selected suite or suites should be fully furnished at the time of the tests.
A.4 Ambient Sound Level MeasurementsPrecautions are necessary to achieve consistent ambient sound level measurements. Temporary or intermittent sound sources such as a flushing toilet, running shower, stereo, television, traffic or exterior construction noise may cause peaks and valleys in sound levels. Ambient sound level measurements should be recorded when these sounds are absent or are at their lowest level. The building HVAC system should be running during the test with the fan speed set on high. Portable air conditioners installed within the suite should be in the off position during the tests. Occupants of the suite under test should refrain from talking or from other activities that may affect the readings. Measurements should be taken during a normal workday period.