(2) Emergency lighting required by Sentence (1) shall be
(a) designed to provide illumination for a duration of at least
(i) 2-hr in buildings whose highest floor level is more than 18m above grade, and
(ii) 1/2-hr in buildings whose highest floor level is not more than 18m above grade,
(b) supplied by a source of energy separate from the primary electrical supply for the building, and
(c) designed to be automatically actuated when the power to the building is interrupted.
(3) Illumination from emergency lighting shall be an average of at least 10 lx at floor or tread level, or 1 watt/m2 of floor space."
When activated, the emergency lighting must provide continuous illumination in these areas for the duration of time specified in Sentence (2). The minimum illumination of 10 lx is considered adequate to see the stair treads in an exit.
Where there is a dispute between the owner and the fire department regarding lighting levels, the fire department should ensure site verification before initiating enforcement action.
Also, Sentence (3) permits an option of incandescent lighting of at least 1 watt/m2 of floor space as an alternative to a minimum lighting intensity measured at the floor or tread level. The intent of this alternative is to allow the owner, and also the inspector, the ability to assess the existing lighting level without the need for light measuring devices. It is based on the premise that the light source is evenly distributed and not restricted in any way.
(2) An existing fire alarm system shall be deemed to be in compliance with Sentence (1) where the system
(a) complies with Article 9.6.4.2. to 9.6.4.9., and
(b) operates in accordance with Article 3.2.4.4. of the Building Code."
Existing fire alarm and detection systems are acceptable if they comply with the requirements contained in this subsection.
It is intended that an upgraded fire alarm system that utilizes components of the original system would not require compliance with Sentence 9.6.4.1.(1). The upgraded system must, however, satisfy the requirements of Sentence 9.6.4.1.(2) and also maintain the level of performance provided by the original system.
The operation of the system must conform to Article 3.2.4.4. of the Building Code and must be reflected in an approved Fire Safety Plan as required in Section 2.8.
The intent of a fire alarm system under Article 9.6.4.1. is to alert all occupants of a building to a fire emergency so that evacuation procedures can be initiated. The audibility of the fire alarm should be such that it can be heard throughout the building.
This matter could also be resolved under Section 2.8 of the Ontario Fire Code, which contains requirements for fire safety and evacuation planning. A cooperative effort involving the occupants, landlord and fire service to develop a workable fire safety and evacuation plan, taking into consideration any limitations by fire alarm signal devices and building construction features would satisfy the intent of the Fire Code with respect to audibility. Where such measures are not effective a Fire Marshals Order may be issued under Section 18, to resolve the audibility issue.
(a) be located at the main street entrance to the building or
a location that is accessible to the fire department and that is
approved, and
(b) indicate all floors with not more than one floor per zone indicated.
(2) Despite Clause (1)(b), existing annunciator zone indication that is
compatible with the fire safety plan required under Section 2.8.2. and that is
approved may be used."
(2) The voice communication system required by Sentence (1) shall
(a) consist of loudspeakers operated from the central alarm and control
facility or other location that is accessible to the fire department
and supervisory staff required under Subsection 2.8.2. and that is
approved, (b) provide a clear verbal signal throughout the
building except for elevator cars, and
(c) provide for automatic silencing of the fire alarm devices when the
loudspeakers are in use.
(3) Approved existing public address systems compatible with the fire
safety plan required under Subsection 2.8.2. and capable of communicating
instructions to the building occupants shall be deemed to be in
compliance with Sentences (1) and (2)."
The intent of a voice communication system under this Article is to provide an
audible verbal signal clearly heard, in common areas of the building (except
for elevator cars) and within the dwelling units. The occupants of the dwelling
units should be aware of these locations (identified in the Fire Safety
Plan).
Existing intercom systems may be approved by the Chief Fire Official for use
as a voice communication system as long as they are compatible with the fire
safety plan and are capable of communicating instructions to the building
occupants. The following are some criteria that could be considered in
determining the acceptability of an existing system.
1. The intercom system should provide sufficient clarity and volume for
instructions to be easily heard in each suite, and in all public areas of the
building (e.g. corridors, stairways, elevator lobby and recreational areas).
Where the intercom system within each suite is only clearly audible within a
few feet of the speaker then a pre-message tone should be provided to notify
the suite occupants of an impending message. Telephone intercom systems may
need additional speakers in the suites to provide satisfactory audibility.
2. The intercom system should be specified in the building fire safety plan as
a voice communication system, with appropriate instructions on its proper use
in a fire emergency. This should include instructions for suite occupants on
how the in-suite intercom functions to provide information and instructions
during a fire.
3. The intercom system shall automatically silence the fire alarm system when
it is being used to deliver instructions/information.
4. Control of the intercom system should be from the main entrance/lobby area,
and have the capability to override the normal intercom use of the system.
5. The intercom system should have an emergency power supply capable of
operating the intercom system for a period of at least 2 hours.
It should be noted that the intercom system would not require electrical
supervision for faults or grounds, and it would not be required to have zone
controlled communication. As well, if the intercom system is deemed to be used
in a continuous manner similar to paging systems, the frequency of testing
waiver as provided in OFC Sentence 6.3.2.3.(3) pertains.
9.6.4.5. ANNUCIATOR PANEL
9.6.4.5. "(1) An annunciator panel shallIntent:
A fire alarm system annunciator panel is primarily used by
firefighters to locate the fire. The panel must be located such that it is
visible immediately upon entering the building. The entire building must be
indicated on the panel by fire zones that do not cover more than one floor per
zone. The operation of any fire alarm system device within a zone must
activate the corresponding zone indicator light. The Chief Fire Official may
approve existing annunciator panels.
Other Resources:
NFPA 101, CAN/ULC-S524
Application:
Q1 Are exit stairs required to be separately zoned and what can be done
if the panel cannot accommodate any more zones?
A1 The exit stairs need not be zoned separately. However, the zone
which includes the stairs should be clearly identified on the annunciator
panel. It may be acceptable to include the exit stair in an existing zone such
as the top floor.
9.6.4.7. VOICE COMMUNCATION SYSTEM
9.6.4.7. "(1) A voice communication system shall be provided where the
vertical distance between the floor of the top storey and grade
exceeds 36m.Intent:
One of the recommendations resulting from the Webber inquiry on
"Fire Safety in Highrise Buildings" was that buildings greater than 12 storeys
in building height be provided with one-way voice communication. It is
primarily intended to supply information to the occupants, such as where the
fire is located and which evacuation route to take. A secondary use would be
by the firefighters to coordinate suppression efforts. The system must meet
the requirements of Sentence 9.6.4.7.(2) except that an existing public address
system may be approved by the Chief Fire Official.Other Resources:
NFPA 72F, ULC-S524, Fire Safety in Highrise Buildings;
OFC 9.6.4.7., 6.3.1.4.; OBC 3.2.4.22.(1)(b); Commentary on Changes to the OFC,
Retrofit Sections 9.5 and 9.6, ULC-S536, NFPA 101, Fire Alarm Signalling
Systems, Fire Alarm Systems - A Reference Manual
Application:
Q1 If a building has an existing fire alarm system and requires a voice
communication system, must it be installed in accordance with the Building
Code?
A1 No, the voice communication system may be installed in accordance
with Sentence (2) of this Article.
Q2 Can an alternative measure of enhancing the fire alarm system by
providing smoke detectors in the corridors be considered in lieu of installing
a voice communication system?
A2 A voice communication system is intended to provide a means of
communicating instructions to the occupants during a fire emergency. This may
include instructions on what exit to use or to stay in place and not attempt to
evacuate. The smoke detectors in the corridor may provide earlier warning of a
fire condition but would do little to communicate instructions to the
occupants. Emergency procedures requiring evacuation depend on immediate
response by the occupants. Practical experience has shown that evacuation of a
highrise building requires much more time and often occurs during suppression
efforts by firefighters. The alternative provision proposed is not considered
to provide an equivalent level of safety.
Q3 Is the audibility level of voice communication systems addressed in
the Fire Code?
A3 The system should provide a verbal signal clearly heard in all
occupied areas of the building and within the means of egress. The Ontario Fire
Code does not specifically address the required sound level of a voice
communication system. A voice communication system is not intended to alert
the occupants to an emergency. It is used to transmit instructions to the
occupants during a fire emergency after they have been alerted by the fire
alarm system. The instructions may include the location of the fire and
whether they should or should not evacuate the building, and which evacuation
route to be taken. A secondary use would be by the firefighters, to coordinate
suppression efforts.
Q4 What criteria should be used to determine if an existing intercom
system is adequate for use as a voice communication system in a highrise
residential building?
A4 Existing residential buildings are often provided with intercom
systems to notify the occupants of visitors attempting to gain entry into the
building. Some of these systems use the suite phone system and some use a wall
speaker/microphone in each suite. The in-suite wall intercom systems are often
used as a component of the building voice communication system but are usually
separate from the fire alarm system.