Requirements in Section 9.9 Hotels with Compliance Date of January 1, 2010
(refer to Article 9.1.3.1.)

Code Reference

What is Required

Compliance Date

Hotels constructed prior to Sept.1, 1971 Hotels constructed after Aug. 31, 1971

CONTAINMENT (REQUIRED TO CONTROL FIRE SPREAD)

9.9.2.6.

  fire separation of hotel buildings from adjacent buildings not containing a hotel Jan. 1, 2010 required now

9.9.2.8.

(1) fire separation of guest suites Jan. 1, 2010 required now
self-closers on guest suite doors Jan. 1, 2010 Jan. 1, 2010
  (2) fire separation of corridors serving guest suites Jan. 1, 2010 Jan. 1, 2010

9.9.2.14.

(3),(4) sprinklering of linen and refuse chutes Jan. 1, 2010 Jan. 1, 2010

MEANS OF EGRESS

9.9.3.3.

(1) number of exits from floor areas required now required now
  (2) 2 exits from floor areas in buildings 4 storeys and higher Jan. 1, 2010 Jan. 1, 2010
  (3),(4) number of exits from 3rd storey of a 3 storey building Jan. 1, 2010 Jan. 1, 2010
  (5),(6) minimum distance between exits Jan. 1, 2010 Jan. 1, 2010

9.9.3.5.

  distance of travel to an exit within a floor area Jan. 1, 2010 required now

9.9.3.6.

(2) safe discharge locations for exits Jan. 1, 2010 required now

9.9.3.7.

(1) restriction on fire escapes above 6th floors Jan. 1, 2010 required now

FIRE ALARM AND DETECTION

9.9.4.2.

(2)(b),(c),(4) fire detectors at top of elevator shaft and exit stairways Jan. 1, 2010 Jan. 1, 2010