Compliance Schedule for Section 9.9 Hotels
(refer to Article 9.1.3.1.)
|
Code Reference |
What is Required |
Compliance Date |
||
| Hotels constructed prior to Sept.1, 1971 | Hotels constructed after Aug. 31, 1971 | |||
|
BUILDING AUDIT |
||||
|
9.9.1.2. |
preparation and retention of a building audit by owner |
Jan. 1, 2008 |
Jan. 1, 2008 |
|
|
CONTAINMENT (REQUIRED TO CONTROL FIRE SPREAD) |
||||
|
9.9.2.1. |
(1)-(5), (7),(8) | required fire separation design | required now | required now |
| (6) | floor assemblies constructed as fire separations | Jan. 1, 2012 | required now | |
|
9.9.2.2. |
fire-rating of buildings up to 3 storeys | Jan. 1, 2012 | required now | |
|
9.9.2.3. |
fire-rating of buildings up to 4 storeys | Jan. 1, 2012 | required now | |
|
9.9.2.4. |
fire-rating of buildings greater than 4 storeys and up to 6 storeys | Jan. 1, 2012 | required now | |
|
9.9.2.5. |
fire-rating of buildings greater than 6 storeys | Jan. 1, 2012 | required now | |
|
9.9.2.6. |
fire separation of hotel buildings from adjacent buildings not containing a hotel | Jan. 1, 2010 | required now | |
|
9.9.2.7. |
criteria for interconnected floor spaces | Jan. 1, 2012 | required now | |
|
9.9.2.8. |
(1) | fire separation of guest suites | Jan. 1, 2010 | required now |
| self-closers on guest suite doors | Jan. 1, 2010 | Jan. 1, 2010 | ||
| (2) | fire separation of corridors serving guest suites | Jan. 1, 2010 | Jan. 1, 2010 | |
|
9.9.2.9. |
fire separation between major occupancies | Jan. 1, 2012 | Jan. 1, 2012 | |
|
9.9.2.10. |
(1)-(6) | closures (e.g. doors) in fire separations (including self-closers and latches) | required now | required now |
| (7),(8) | fire dampers in ducts at fire separations | Jan. 1, 2012 | Jan. 1, 2012 | |
|
9.9.2.11. |
fire separation of laundry, storage and service rooms | required now | required now | |
|
9.9.2.12. |
(1)-(4), (6),(7) | fire separation of fuel-fired appliances | required now | required now |
| (5) | combustion air for fuel-fired appliances |
July 1, 2008 |
July 1, 2008 |
|
|
9.9.2.13. |
fire separation of vertical service spaces | Jan. 1, 2012 | Jan. 1, 2012 | |
|
9.9.2.14. |
(1),(2) | fire separation of refuse and linen chutes | required now | required now |
| (3),(4) | sprinklering of linen and refuse chutes | Jan. 1, 2010 | Jan. 1, 2010 | |
|
9.9.2.15. |
(1),(2), (4) | protection of guest suite floors against smoke movement from non-residential floors | required now | required now |
| (3) | protection of guest suite floors against smoke movement from other guest suite floors | Jan. 1, 2012 | Jan. 1, 2012 | |
|
9.9.2.16. |
construction material and flame spread for pipes, ducts and plenums and associated insulation materials | required now | required now | |
|
9.9.2.17. |
restrictions on air handling equipment at exit separations | required now | required now | |
9.9.2.18. |
restrictions on stairs or corridors as exhaust air plenums | required now | required now | |
9.9.2.19. |
design and fire protection of commercial cooking equipment | required now | required now | |
9.9.3.1. |
determination of occupant load for floor areas | required now | required now | |
|
9.9.3.2. |
(1) | safe discharge location for egress routes | required now | required now |
| (2) | dead end corridor limitations | Jan. 1, 2012 | required now | |
| (3) | areas served by a dead end corridor | Jan. 1, 2012 | Jan. 1, 2012 | |
| (4)-(11) | capacity and number of egress routes | required now | required now | |
|
9.9.3.3. |
(1) | number of exits from floor areas | required now | required now |
| (2) | 2 exits from floor areas in buildings 4 storeys and higher | Jan. 1, 2010 | Jan. 1, 2010 | |
| (3),(4) | number of exits from 3rd storey of a 3 storey building | Jan. 1, 2010 | Jan. 1, 2010 | |
| (5),(6) | minimum distance between exits | Jan. 1, 2010 | Jan. 1, 2010 | |
9.9.3.4. |
minimum width of exits | required now | required now | |
9.9.3.5. |
distance of travel to an exit within a floor area | Jan. 1, 2010 | required now | |
|
9.9.3.6. |
(1),(3)-(6) | fire separation for exit stairs | required now | required now |
| (2) | safe discharge locations for exits | Jan. 1, 2010 | required now | |
|
9.9.3.7. |
(1) | restriction on fire escapes above 6th floors | Jan. 1, 2010 | required now |
| (2)-(6) | fire escape and exterior exit stairway design | required now | required now | |
9.9.3.8. |
exit and access to exit door swing and hardware | required now | required now | |
9.9.3.9. |
emergency access from exit stairways into floor areas | required now | required now | |
9.9.3.10. |
design of exit signs | required now | required now | |
9.9.3.11. |
interior wall and ceiling finishes for exits and access to exits | required now | required now | |
9.9.3.12. |
interior wall and ceiling finishes in assembly areas | required now | required now | |
9.9.3.13. |
lighting levels in exits and access to exits | required now | required now | |
9.9.3.14. |
emergency lighting levels in exits, access to exits and assembly area | required now | required now | |
9.9.4.1. |
buildings that require a fire alarm system | required now | required now | |
|
9.9.4.2. |
(1),(2)(a),(3) | location of fire detectors as part of fire alarm systems | required now | required now |
| (2)(b),(c),(4) | fire detectors at top of elevator shaft and exit stairways | Jan. 1, 2010 | Jan. 1, 2010 | |
9.9.4.3. |
location of manual pull stations | required now | required now | |
9.9.4.4. |
location for fire alarm signalling devices (e.g. horns and bells) | required now | required now | |
9.9.4.5. |
fire alarm annunciator panels | required now | required now | |
9.9.4.6. |
shut down of air handling system on fire alarm activation | required now | required now | |
9.9.4.7. |
trouble signal and trouble lights for fire alarm systems | required now | required now | |
9.9.4.8. |
operation of single-stage and two-stage fire alarm systems | required now | required now | |
9.9.4.9. |
restriction on number of fire alarm systems in a building | required now | required now | |
9.9.4.10. |
electrical supervision of fire alarm systems | required now | required now | |
9.9.4.11. |
emergency power for fire alarm systems | required now | required now | |
9.9.4.12. |
design standards for fire alarm system installation | required now | required now | |
9.9.4.13. |
smoke alarm installation in guest suites | July 1, 2008 | July 1, 2008 | |
9.9.4.14. |
voice communication systems in high buildings | Jan. 1, 2012 | Jan. 1, 2012 | |
9.9.5.1. |
fire fighting access routes | Jan. 1, 2012 | Jan. 1, 2012 | |
9.9.5.2. |
standpipe and hose systems | Jan. 1, 2012 | required now | |
9.9.5.3. |
firefighters' elevators in high buildings | Jan. 1, 2012 | Jan. 1, 2012 | |
9.9.5.4. |
sprinkler installation design | required now | required now | |
9.9.5.5. |
emergency power for fire alarms, firefighters' elevators and emergency lighting | Jan. 1, 2012 | Jan. 1, 2012 | |