May 2007
Fire Code Supplement FCS-1 comes into force on November
21, 2007.
©Copyright
Reproduction of this document for commercial or
advertising purposes is prohibited without the written
permission from the Office of the Fire Marshal, Ministry
of Community Safety and Correctional Services.
This document prescribes, for the purposes of Subsection
1.2.2. in Division A of the Fire Code, the objectives
and functional statements that have been attributed to
acceptable solutions set out in Division B of the Fire
Code.
Objectives, functional statements and acceptable
solutions referred to in this document are those defined
in Article 1.4.1.2. of the Fire Code.
The objectives referred to in this document are those
set out in Part 2 of Division A of the Fire Code.
The functional statements referred to in this document
are those set out in Part 3 of Division A of the Fire
Code.
For the purposes of compliance with the Fire Code, as
provided in Clause 1.2.2.1.(1)(b) of Division A, the
objectives and functional statements attributed to the
acceptable solutions in Division B shall be the
objectives and functional statements set out in Tables 2
to 9.
Where objectives and functional statements have not been
attributed to an acceptable solution in Tables 2 to 9,
the provisions of Clause 1.2.2.1.(1)(b) of Division A of
the Fire Code do not apply and compliance with the Fire
Code must be achieved by complying with the acceptable
solution specified in Division B of the Fire Code. Refer
to Sentence 1.2.2.1.(3) of the Fire Code for additional
details.
For the purposes of Tables 2 to 9, a notation made by the following mark “ … ” identifies text contained in the Fire Code that is included for the purposes of the attribution but is omitted from the table for brevity. A notation made by the following mark “ __ ” identifies text contained in the Fire Code that is deliberately excluded for the purposes of the attribution.
| Accceptable Solution | Objectives and Functional Statements |
|---|---|
| SECTION 2.1 | GENERAL |
| Subsection 2.1.1. | Scope and Application |
| 2.1.1.1. | Note1 |
| 2.1.1.2. | Note1 |
| 2.1.1.3. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
|
Subsection 2.1.2. |
Classification of Buildings or Parts of Buildings by Major Occupancy |
| 2.1.2.1. | Note1 |
|
2.1.2.2. |
[F01-OS1.1,OS1.2,OS1.5,OP1.1,OP1.2] [F03-OS1.2,OS1.5,OP1.2] [F04-OS1.3,OP1.3] |
| 2.1.2.3. | [F02-OS1.2] |
| SECTION 2.2 | FIRE SEPARATIONS |
| Subsection 2.2.1. | Major Occupancies |
| 2.2.1.1. | [F03-OS1.2,OP1.2] |
| Subsection 2.2.2. | Rooms and Spaces |
| 2.2.2.1. | [F03-OS1.2,OP1.2] |
| Subsection 2.2.3. | Closures |
| 2.2.3.1. | [F82-OS1.2,OP1.2] |
| 2.2.3.2. (1) | [F82-OS1.2,OP1.2] |
| 2.2.3.3. | Note1 |
| 2.2.3.4. | [F82-OS1.4,OP1.4] |
| 2.2.3.5. (1) | [F82-OS1.2,OP1.2] |
| (2) | Note1 |
| 2.2.3.6. | RESERVED |
| 2.2.3.7. | [F82-OS1.2,OP1.2] |
| 2.2.3.8. | [F81-OS1.2,OS1.4,OP1.2,OP1.4] |
| SECTION 2.3 |
INTERIOR FINISHING, FURNISHING AND DECORATIVE MATERIALS |
| Subsection 2.3.1. | General |
| 2.3.1.1. (1) | [F02-OS1.2,OP1.2] |
| (2) | Note1 |
| 2.3.1.2. | [F02-OS1.2,OP1.2] |
| Subsection 2.3.2. | Textile Flammability |
| 2.3.2.1. (1) | [F02-OS1.2,OS1.5,OP1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 2.3.2.2. | [F82-OS1.2,OS1.5,OP1.2] |
| SECTION 2.4 | FIRE HAZARDS |
| Subsection 2.4.1. | Combustible Materials |
|
2.4.1.1. (1) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2,OP3.1] |
| (2) |
[F01-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] |
| (3) | Note1 |
| (4) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| (5) | [F02-OS1.2,OP1.2] |
| (6) |
[F01-OS1.1] [F02-OS1.2,OP3.1] |
| 2.4.1.2. | Note1 |
| 2.4.1.3. (1) | [F01-OS1.1,OP1.1] |
| (2) |
Note1 Applies to the following text in the Fire Code: “combustible materials shall not be stored with ashes in the same receptacle”. [F01-OS1.1] |
| (3) | [F03-OS1.2,OP1.2] |
| 2.4.1.4. (1) | [F03-OS1.2,OP1.2] |
| 2.4.1.5. | [F01-OS1.1,OP1.1] |
| 2.4.1.6. | [F43-OS1.2,OP1.2] |
| Subsection 2.4.2 | RESERVED |
| Subsection 2.4.3. | Smoking |
| 2.4.3.1. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F02-OS1.2,OP1.2] |
| 2.4.3.2. | [F81-OS1.1,OP1.1] |
| Subsection 2.4.4 | Open Flames |
| 2.4.4.1. (1) | [F01-OS1.1,OP1.1] |
| (2) | Note1 |
| (3) | [F01-OS1.1,OP1.1] |
| 2.4.4.2. (1) | Note1 |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
| (4) | [F02,F12-OS1.2,OP1.2] |
| 2.4.4.3. | [F01-OS1.1,OP1.1] |
| Subsection 2.4.5. | Use of Hazardous Materials |
| 2.4.5.1. | [F01-OS1.1,OP1.1] |
| 2.4.5.2. | Note1 |
| Subsection 2.4.6. | Electrical Hazards |
| 2.4.6.1. | [F01-OS1.1,OP1.1] |
| Subsection 2.4.7. | Vacant Buildings |
| 2.4.7.1. | [F34-OS1.1,OP1.1] |
| SECTION 2.5 |
FIRE DEPARTMENT ACCESS TO BUILDINGS |
| Subsection 2.5.1. | General |
| 2.5.1.1. (1) | Note1 |
| 2.5.1.2. (1) | [F12-OS1.2,OP1.2] |
| (2) | [F12-OS1.2,OP1.2] |
| 2.5.1.3. | [F12-OS1.2,OP1.2] |
| 2.5.1.4. | [F12-OS1.2,OP1.2] |
| SECTION 2.6 | SERVICE EQUIPMENT |
| Subsection 2.6.1. |
Heating, Ventilating and Air-Conditioning |
| 2.6.1.1. | [F01-OS1.1,OP1.1] |
| 2.6.1.2. | [F01-OS1.1,OP1.1] |
|
2.6.1.3. |
[F01,F82-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
|
2.6.1.4. (1) |
[F01,F82-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| (2) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
| (3) |
[F82-OS1.1,OS1.2,OS1.3,OP1.1, OP1.2,OP1.3] |
| 2.6.1.5. | [F82-OS1.1,OP1.1,OS1.2,OP1.2] |
| 2.6.1.6. | RESERVED |
|
2.6.1.7. |
[F01-OS1.1] [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| 2.6.1.8. | [F82-OS1.2,OP1.2] |
|
2.6.1.9. |
[F01-OS1.1,OP1.1] [F81-OS1.1,OS1.2,OP1.1,OP1.2] |
|
2.6.1.10. (1) |
[F01-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] |
| 2.6.1.11. | [F43,F81-OS1.1,OP1.1] |
|
2.6.1.12. (1)
|
[F01-OS1.1] [F02,F03,F12-OS1.2,OP1.2] [F81-OS1.4,OP1.4] |
| (2) | Note1 |
| (3) | Note1 |
|
2.6.1.13. |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] [F81-OP1.4] [F82-OS1.2,OS1.4,OP1.2] |
| 2.6.1.14. (1) | [F12-OS1.2,OP1.2] |
| (2) | Note1 |
| Subsection 2.6.2. | Solid-Fuel-Burning Appliances |
|
2.6.2.1. |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] |
|
2.6.2.2. |
[F01-OS1.1,OP1.1] [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| Subsection 2.6.3. | Incinerators |
| 2.6.3.1. (1) |
[F01-OS1.1,OP1.1,OP3.1] [F81-OS1.1,OP1.1] |
| (2) |
Note1 Applies to the following text in the Fire Code: “the flue venting an incinerator shall not serve as the chute conveying waste material to the incinerator”. [F01-OS1.1,OP3.1] |
|
2.6.3.2. |
[F01-OS1.1,OP1.1,OP3.1] [F82-OS1.2,OP1.2] |
| 2.6.3.3. (1) | [F82-OS1.1,OP1.1] |
| (2) | [F01,F82-OS1.1,OP1.1] |
| 2.6.3.4. (1) | [F01,F02,F03,F81-OS1.1,OS1.2,OP1.1,OP1.2,OP3.1] |
| (2) | Note1 |
| Subsection 2.6.4. | Electrical Equipment Vaults |
| 2.6.4.1. | Note1 |
| 2.6.4.2. | [F34-OS1.1,OP1.1] |
| SECTION 2.7 | SAFETY TO LIFE |
| Subsection 2.7.1. | Means of Egress |
| 2.7.1.1. | [F10-OS1.5] |
| 2.7.1.2. | [F10-OS1.5] |
| 2.7.1.3. | [F10-OS1.5] |
| 2.7.1.4. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | [F10-OS1.5] |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| (7) | [F10-OS1.5] |
| 2.7.1.5. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| 2.7.1.6. (1) | Note1 |
| (2) | [F10-OS1.5] |
| (3) | [F10-OS1.5] |
| (4) | Note1 |
| (5) | [F10-OS1.5] |
| (6) | [F10-OS1.5] |
| (7) | [F10-OS1.5] |
| (8) | Note1 |
|
2.7.1.7. (1) |
[F10,F30-OS1.5] [F12-OS1.2,OP1.2] |
| (2) | [F82-OS1.5] |
| 2.7.1.8. (1) |
[F10-OS1.5] [F12-OS1.2,OP1.2] [F82-OS1.2,OS1.5,OP1.2] |
| (2) |
[F10-OS1.5] [F12-OS1.2,OP1.2] [F82-OS1.2,OS1.5,OP1.2] |
| 2.7.1.9. (1) | [F10-OS1.5] |
| (2) | Note1 |
| (3) | [F10-OS1.5] |
| (4) | Note1 |
| (5) | [F10-OS1.5] |
| (6) | [F10-OS1.5] |
| Subsection 2.7.2. | Door Hardware |
| 2.7.2.1. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | [F10-OS1.5] |
| (4) | Note1 |
| (5) | Note1 |
| 2.7.2.2. (1) | [F10-OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| Subsection 2.7.3. | Exit Lighting and Emergency Lighting |
| 2.7.3.1. | [F10,F82-OS1.5] |
| 2.7.3.2. | [F10-OS1.5] |
| 2.7.3.3. (1) | [F10,F82-OS1.5] |
| (2) | [F10,F82-OS1.5] |
| (3) | [F10,F82-OS1.5] |
| (4) | [F10,F82-OS1.5] |
| (5) | [F10,F82-OS1.5] |
| (6) | [F10,F82-OS1.5] |
| Subsection 2.7.4. | Indoor Public Amusement Areas |
| 2.7.4.1. (1) |
[F01-OS1.1] [F02-OS1.2] [F10-OS1.5] |
| (2) |
[F01-OS1.1] [F02-OS1.2] |
| 2.7.4.2. (1) | [F10,F36-OS1.5] |
| SECTION 2.8 | EMERGENCY PLANNING |
| Subsection 2.8.1. | General |
| 2.8.1.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| 2.8.1.2. (1) | [F12-OS1.2,OS1.4,OS1.5,OP1.2,OP1.4] |
| (2) | [F12-OS1.2,OS1.4,OS1.5] |
| (3) | Note1 |
| 2.8.1.3. | [F12-OS1.2,OS1.4,OS1.5,OP1.2,OP1.4] |
| Subsection 2.8.2. | Fire Safety Plan |
|
2.8.2.1. (1)(a)(i) |
[F11-OS1.5] [F13-OS1.2,OS1.5,OP1.2] |
| (ii) | [F13-OS1.2,OS1.5,OP1.2] |
| (iii) | [F11-OS1.5] |
| (iv) | [F10-OS1.5] |
| (v) | [F12,F36-OS1.5] |
| (vi) | [F02-OS1.2,OP1.2] |
| (b) | [F12-OS1.2,OS1.5,OP1.2] |
| (c) | [F12-OS1.2,OS1.5,OP1.2] |
| (d) | [F12-OS1.2,OS1.5,OP1.2] |
| (e) | [F10,F12-OS1.5] |
| (f) | [F01-OS1.1,OP1.1] |
| (g) | [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| (h) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] [F10,F11,F36-OS1.5] [F12-OS1.2,OS1.5] [F13-OS1.2,OS1.5,OP1.2] [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| (2) | Note1 |
| (3) | [F12-OS1.2,OS1.5,OP1.2] |
| (4) | Note1 |
| (5) | Note1 |
|
2.8.2.2. (1) |
[F01-OS1.1] [F02-OS1.2] [F12-OS1.2,OS1.4,OS1.5] |
| (2) |
[F01-OS1.1] [F02-OS1.2] [F12-OS1.2,OS1.4,OS1.5] |
|
2.8.2.3. (1) |
[F2,F3,F12,F13-OS1.2,OS1.5,OP1.2] [F11-OS1.5] |
| 2.8.2.4. |
[F01-OS1.1] [F02-OS1.2,OP1.2] [F10,F11-OS1.5] [F12,F13-OS1.2,OS1.4,OS1.5,OP1.2,OP1.4] [F82-OS1.1,OS1.2,OS1.4,OS1.5,OP1.1, OP1.2,OP1.4] |
| 2.8.2.5. (1) | [F10-OS1.5] |
| (2)(a) | [F10-OS1.5] |
| (b) | [F12-OS1.2,OS1.5,OP1.2] |
| (3) | [F13-OS1.2,OP1.2] |
| Subsection 2.8.3. | Fire Drills |
|
2.8.3.1. (1) |
[F10-OS1.5] [F12-OS1.2,OS1.5,OP1.2] |
| (2) | Note1 |
|
2.8.3.2. (1) |
[F10-OS1.5] [F12-OS1.2,OS1.5,OP1.2] |
| (2) |
[F10-OS1.5] [F12-OS1.2,OS1.5,OP1.2] |
| (3) | Note1 |
| SECTION 2.9 | TENTS AND AIR-SUPPORTED STRUCTURES |
| Subsection 2.9.1. | General |
| 2.9.1.1. | Note1 |
| 2.9.1.2. | Note1 |
| Subsection 2.9.2. | Materials |
| 2.9.2.1. | [F82-OS1.2,OS1.5,OP1.2] |
| Subsection 2.9.3. | Fire Hazards and Control |
| 2.9.3.1. | [F02-OS1.2] |
| 2.9.3.2. | [F01-OS1.1,OP1.1] |
| 2.9.3.3. (1) | Note1 |
|
2.9.3.4. (1) |
[F10-OS1.5] [F12-OS1.2,OS1.5] |
|
2.9.3.5. |
[F11-OS1.5] [F13-OS1.2,OP1.2] |
| SECTION 2.10 | DAY CARE CENTRES |
| Subsection 2.10.1. | Application |
| 2.10.1.1. (1) | Note1 |
| (2) | Note1 |
| Subsection 2.10.2. | Combustible Materials |
| 2.10.2.1. | [F02-OS1.2,OP1.2] |
| 2.10.2.2. | [F02,F03-OS1.2,OP1.2] |
| 2.10.2.3. |
Note1 Applies to the following text in the Fire Code: “Flammable liquids and combustible liquids shall be stored in conformance with Part 4”.
[F01,F34-OS1.1] |
| Subsection 2.10.3. | Staffing |
| 2.10.3.1. | [F12-OS1.5] |
| SECTION 2.11 | INSULATION AND RE-INSULATION |
| Subsection 2.11.1. | General |
| 2.11.1.1. | Note1 |
| 2.11.1.2. | [F02-OS1.2,OP1.2] |
| 2.11.1.3. | [F03-OS1.2,OP1.2] |
| SECTION 2.12 | COVERED MALLS |
| Subsection 2.12.1. | General |
|
2.12.1.1. (1) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] [F10-OS1.5] |
| (2) | Note1 |
| 2.12.1.2. | [F02-OS1.2,OP1.2] |
| 2.12.1.3. (1) | [F03-OS1.2,OP3.1] |
| (2) | Note1 |
| 2.12.1.4. | Note1 |
| 2.12.1.5. |
[F11-OS1.5] [F12-OS1.2,OS1.5,OP1.2] [F13-OS1.2,OP1.2] |
| 2.12.1.6. | Note1 |
| 2.12.1.7. | [F01,F81-OS1.1,OP1.1] |
| SECTION 2.13 | INSTALLATION OF SMOKE ALARMS |
| Subsection 2.13.1. | Scope |
| 2.13.1.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| Subsection 2.13.2. | Installation |
| 2.13.2.1. (1) | [F11,F81-OS1.4,OS1.5] |
| (2) | [F11-OS1.5] |
| (3) | [F11-OS1.5] |
| (4) |
Note1 Applies to the following text in the Fire Code: “Smoke alarms __ shall have no disconnect switch between the overcurrent device and the smoke alarm”.
[F11-OS1.5] |
| (5) | Note1 |
| (6) | Note1 |
| (7) | Note1 |
| SECTION 2.14 | OUTDOOR PUBLIC AMUSEMENT AREAS |
| Subsection 2.14.1. | General |
| 2.14.1.1. | Note1 |
| 2.14.1.2. (1) |
[F01-OS1.1] [F02-OS1.2] [F10-OS1.5] |
| (2) |
[F01-OS1.1] [F02-OS1.2] |
| 2.14.1.3. | [F01-OS1.1] |
| 2.14.1.4. (1) | [F10,F36-OS1.5] |
| 2.14.1.5. (1)(a) |
[F11-OS1.2,OS1.5] [F13-OS1.2,OS1.5,OP1.2] |
| (b) | [F10-OS1.5] |
| (c) | [F12-OS1.2,OS1.5,OP1.2] |
| (d) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| (2) | Note1 |
| SECTION 2.15 | PORTABLE OXYGEN SYSTEMS |
| Subsection 2.15.1. | General |
| 2.15.1.1. | Note1 |
|
2.15.1.2. |
[F01-OS1.1] [F02,F03-OS1.2,OP1.2] |
| Accceptable Solution | Objectives and Functional Statements |
|---|---|
| SECTION 3.1 | GENERAL |
| Subsection 3.1.1. | Scope |
| 3.1.1.1. | Note1 |
| SECTION 3.2 | WOOD PRODUCTS |
| Subsection 3.2.1. | Woodworking Plants |
| 3.2.1.1. | Note1 |
| 3.2.1.2. | [F01-OS1.1,OP1.1] |
| 3.2.1.3. | Note1 |
| 3.2.1.4. | [F01,F81-OS1.1,OP1.1] |
| 3.2.1.5. | [F02,F12-OS1.2,OP1.2] |
| 3.2.1.6. | Note1 |
| 3.2.1.7. | Note1 |
| Subsection 3.2.2. | Outdoor Storage of Lumber and Forest Products |
| 3.2.2.1. | Note1 |
|
3.2.2.2. (1) |
[F03,F12-OP1.2,OP3.1] [F04-OS1.3,OP1.2] |
| (2) | Note1 |
|
3.2.2.3. (1) |
[F03,F12-OP1.2,OP3.1] [F04-OS1.3,OP3.1] |
| (2) | Note1 |
| 3.2.2.4. (1) | [F03-OP1.2,OP3.1] |
| (2) | [F03-OP1.2,OP3.1] |
| (3) | [F12-OS1.2,OP1.2] |
| 3.2.2.5. (1) | [F03-OP3.1] |
| (2) | Note1 |
| 3.2.2.6. | [F03-OP1.2,OP3.1] |
| 3.2.2.7. | [F03-OP1.2,OP3.1] |
|
3.2.2.8. |
[F02-OP3.1,OS1.2] [F03-OP1.2] |
| 3.2.2.9. |
[F01-OS1.1] [F06-OS1.4,OP1.4] [F32-OS3.3] |
| 3.2.2.10. | [F02-OS1.2,OP1.2] |
| 3.2.2.11. | [F02,F12-OS1.2,OP1.2] |
| 3.2.2.12. (1) | [F12-OS1.2,OP3.1] |
| (2) | [F12-OS1.2,OP1.2,OP3.1] |
| 3.2.2.13. (1) | [F12-OS1.2,OP1.2,OP3.1] |
| (2) | [F12-OS1.2,OP1.2,OP3.1] |
|
3.2.2.14. |
[F02,F03-OP1.2] [F12-OS1.2,OP1.2,OP3.1] |
| 3.2.2.15. | [F12-OS1.2,OP1.2,OP3.1] |
| 3.2.2.16. | Note1 |
| 3.2.2.17. | [F01-OS1.1,OP1.1,OP3.1] |
|
3.2.2.18. |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP3.1] |
|
3.2.2.19. |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2,OP3.1] |
| 3.2.2.20. | [F03-OS1.2,OP1.2] |
| 3.2.2.21. | Note1 |
| 3.2.2.22. | [F01-OS1.1,OP1.1] |
| 3.2.2.23. | [F13-OS1.2,OP1.2,OP3.1] |
| 3.2.2.24. (1) | [F02,F12-OS1.2,OP1.2] |
| (2) | [F12,F81-OS1.4,OP1.4] |
| (3) | [F12-OS1.2,OP1.2] |
| (4) | [F02,F12-OS1.2,OP1.2] |
| 3.2.2.25 | Note1 |
| 3.2.2.26. | [F12-OS1.2,OS1.3,OP1.2,OP3.1] |
| 3.2.2.27. | [F12-OS1.2,OP1.2,OP3.1] |
| Subsection 3.2.3. | Outdoor Storage of Wood Chips |
| 3.2.3.1. | Note1 |
| 3.2.3.2. | [F12-OP1.2,OP3.1] |
| 3.2.3.3. | [F03-OP1.2,OP3.1] |
| 3.2.3.4. (1) | [F03-OP1.2,OP3.1] |
| (2) | Note1 |
| 3.2.3.5. | [F12-OS1.2,OP1.2,OP3.1] |
|
3.2.3.6. (1) |
[F03-OP1.2] [F12-OS1.2,OP1.2,OP3.1] |
| (2) |
[F03-OP1.2] [F12-OS1.2,OP1.2,OP3.1] |
| 3.2.3.7. | [F12-OS1.2,OP1.2,OP3.1] |
| 3.2.3.8. (1) | [F12-OS1.2,OP1.2,OP3.1] |
| (2) | Note1 |
| 3.2.3.9. | [F12-OS1.2,OP1.2,OP3.1] |
| 3.2.3.10. | Note1 |
| 3.2.3.11. | [F12-OS1.2,OP1.2] |
| 3.2.3.12. (1) | [F12-OS1.2,OP1.2,OP3.1] |
| (2) |
[F02-OS1.2,OP1.2] [F12-OP1.2,OP3.1] |
| (3) |
[F02,OS1.2] [F12-OP1.2,OP3.1] |
| 3.2.3.13. | Note1 |
| SECTION 3.3 | STORAGE |
| Subsection 3.3.1. | Indoor Tire Storage |
| 3.3.1.1. | Note1 |
| 3.3.1.2. | [F02,F12-OS1.2,OP1.2] |
| 3.3.1.3. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| 3.3.1.4. | [F02-OS1.2,OP1.2] |
| 3.3.1.5. | [F03,F12-OS1.2,OP1.2] |
| 3.3.1.6. | [F04-OS1.3,OP1.3] |
| 3.3.1.7. | Note1 |
| 3.3.1.8. (1) | [F02,F04-OS1.2,OP1.2] |
| (2) | [F02,F04-OS1.2,OP1.2] |
| 3.3.1.9. | [F12-OS1.2,OP1.2] |
| 3.3.1.10. (1) |
Note1 Applies to the following text in the Fire Code: “In addition to the requirements of Section 6.2”. [F02,F12-OS1.2,OP1.2] |
| Subsection 3.3.2. | Indoor General Storage |
| 3.3.2.1. (1) | Note1 |
| (2) | Note1 |
| 3.3.2.2. (1) | [F02,F12-OS1.2,OP1.2] |
| (2) | [F02,F12-OS1.2,OP1.2] |
| (3) | [F02,F12-OS1.2,OP1.2] |
| (4) | [F04-OS1.2,OP1.2,OS1.5] |
| 3.3.2.3. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02,F04-OS1.2,OS1.3,OP1.2,OP1.3] |
| 3.3.2.4. | [F12-OS1.2,OP1.2] |
| 3.3.2.5. | [F12-OS1.2,OP1.2] |
| 3.3.2.6. (1) | [F12-OS1.2,OP1.2] |
| (2) |
[F10-OS1.5] [F12-OS1.2,OP1.2] [F82-OS1.4] |
| (3) |
[F10-OS1.5] [F12-OS1.2,OP1.2] |
| (4) |
[F06-OS1.5] [F12-OS1.2,OP1.2] |
| (5) | Note1 |
| (6) | [F12-OS1.2,OP1.2] |
| 3.3.2.7. | [F04-OS1.3,OP1.3] |
| 3.3.2.8. | [F03-OS1.2,OP1.2] |
|
3.3.2.9. |
[F02-OS1.2,OP1.2] [F03-OP3.1] |
| 3.3.2.10. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | [F02-OS1.2,OP1.2] |
| 3.3.2.11. | [F01-OS1.1,OP1.1] |
| Subsection 3.3.3. | Indoor Storage of Ammonium Nitrate |
| 3.3.3.1. | Note1 |
| 3.3.3.2. (1) | Note1 |
| (2) | Note1 |
| (3) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] |
| (4) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| (5) | [F1,F81-OS1.1,OP1.1] |
| (6) | [F03-OP3.1] |
| (7) | Note1 |
| (8) | Note1 |
| (9) | Note1 |
| (10) | [F03-OS1.2,OP1.2] |
| 3.3.3.3. (1) | [F01,F81-OS1.1,OP1.1] |
| (2) | Note1 |
| (3) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] |
| (4) | [F01-OS1.1,OP1.1] |
| 3.3.3.4. | [F02,F12-OS1.2,OP1.2] |
|
3.3.3.5. (1) |
[F02-OS1.2,OP1.2] [F04-OS1.3] |
| (2) | [F02,F12-OS1.2,OP1.2] |
| (3) | Note1 |
| (4) |
[F12-OS1.2,OP1.2] [F81-OS1.1,OP1.1] |
| (5) | [F01-OS1.1,OP1.1] |
| (6) | [F81-OS1.1,OP1.1] |
| 3.3.3.6. (1) | [F02-OS1.2,OP1.2] |
| (2) | Note1 |
| 3.3.3.7. (1) | Note1 |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
| (4) | [F01-OS1.1,OP1.1] |
| (5) | [F01-OS1.1,OP1.1] |
| 3.3.3.8. | Note1 |
| 3.3.3.9. (1) | Note1 |
| (2) | [F81-OS1.1,OP1.1] |
| 3.3.3.10. | [F01-OS1.1,OP1.1] |
| SECTION 3.4 | INDUSTRIAL TRUCKS |
| Subsection 3.4.1. | General |
| 3.4.1.1. | [F01-OS1.1,OP1.1] |
| Subsection 3.4.2. | Industrial Trucks |
| 3.4.2.1. (1) | [F03-OS1.2,OP1.2] |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
| (4) | [F02,F12-OS1.2,OP1.2] |
| (5) | Note1 |
|
3.4.2.2. (1) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] |
| (2) | [F02,F12-OS1.2,OP1.2] |
| (3) | [F01,F81-OS1.1,OP1.1] |
| 3.4.2.3. (1) | [F01,F81-OS1.1,OP1.1] |
| SECTION 3.5 | SALVAGE SHOPS AND SALVAGE YARDS |
| Subsection 3.5.1. | General |
| 3.5.1.1. | [F03-OS1.2,OP1.2] |
| 3.5.1.2. | Note1 |
|
3.5.1.3. |
[F01-OS1.1,OP1.1] [F02-OS1.2] |
| 3.5.1.4. | [F12-OS1.2,OP1.2] |
| 3.5.1.5. | [F02,F12-OS1.2,OP1.2] |
| 3.5.1.6. | Note1 |
| 3.5.1.7. | [F12-OS1.2,OP1.2] |
| 3.5.1.8. | Note1 |
| 3.5.1.9. | [F01-OS1.1,OP1.1] |
| 3.5.1.10. | [F13-OP1.2,OS1.2] |
| Subsection 3.5.2. | Piling |
|
3.5.2.1. |
[F02,F12-OS1.2,OP1.2,OP3.1] [F03-OP3.1] |
|
3.5.2.2. |
[F03-OP1.2,OP3.1] [F12-OS1.2,OP1.2,OP3.1] |
|
3.5.2.3. |
[F03-OS1.2,OP1.2,OP3.1] [F12-OP1.2,OP3.1] |
| 3.5.2.4. (1) | [F02,F12,F81-OS1.2,OP1.2] |
| (2) | [F12-OS1.2,OP1.2] |
| (3) | [F12-OS1.2,OP1.2] |
| Subsection 3.5.3. | Outdoor Tire Storage Yards |
| 3.5.3.1. (1) | Note1 |
| (2) | Note1 |
| 3.5.3.2. (1) | Note1 |
| (2) | Note1 |
| (3) | [F01-OS1.1,OH5,OP1.1] |
| (4) |
[F01-OS1.1,OH5,OP1.1] [F06-OS1.2] [F12-OS1.2,OS3.3,OP1.2] |
| 3.5.3.3. (1) | Note1 |
| (2) | [F12-OS1.2,OH5,OP1.2] |
| (3) | [F12-OS1.2,OH5,OP1.2] |
| (4) | [F13-OS1.2,OH5,OP1.2] |
|
3.5.3.4. (1) |
[F02,F12-OS1.2,OH5,OP1.2] [F04-OS1.3] |
| (2) | [F03,F12-OS1.2,OH5,OP1.2] |
|
3.5.3.5. (1) |
[F01-OH5,OP1.1] [F03-OP3.1] |
|
(2) |
[F01-OH5] [F03-OP3.1] |
| (3) | [F03,F12-OH5,OP1.2,OP3.1] |
| 3.5.3.6. (1) | [F03-OH5,OP1.2,OP3.1] |
| 3.5.3.7. (1) | [F03-OH5,OP1.2,OP3.1] |
| (2) | [F02-OH5,OP1.2,OP3.1] |
| (3) | [F03-OH5,OP1.2,OP3.1] |
| 3.5.3.8. | Note1 |
| 3.5.3.9. (1) | [F12-OS1.2,OH5,OP1.2,OP3.1] |
| (2) | [F12-OS1.2,OH5,OP1.2,OP3.1] |
| (3) | Note1 |
| 3.5.3.10. (1) | [F34-OH5,OP1.1] |
| (2) | [F34-OH5,OP1.1] |
| (3) | [F12-OS1.2,OH5,OP1.2] |
| (4) | [F12-OS1.2,OH5,OP1.2] |
| (5) | [F12-OS1.2,OH5,OP1.2] |
| (6) | [F34-OH5,OP1.1] |
| 3.5.3.11. (1) | [F12-OS1.2,OH5,OP1.2] |
| (2) | [F02-OS1.2,OH5,OP1.2] |
| (3) | [F02-OS1.2,OH5,OP1.2] |
| (4) | [F12-OS1.2,OH5,OP1.2] |
| 3.5.3.12. | Note1 |
| 3.5.3.13. | [F02,F12-OS1.2,OH5,OP1.2] |
| SECTION 3.6 | DRY CLEANING AND DYEING PLANTS |
| Subsection 3.6.1. | Dry Cleaning and Dyeing Plants |
|
3.6.1.1. (1) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OS1.3,OP1.2,OP1.3] [F03-OS1.2,OP1.2] [F81-OS1.1,OS1.2,OS1.3,OP1.1,OP1.2,OP1.3] |
| (2) | Note1 |
|
(3) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| (4) | Note1 |
| (5) | Note1 |
| SECTION 3.7 | BOWLING ALLEYS |
| Subsection 3.7.1. | Resurfacing |
|
3.7.1.1. |
[F01-OS1.1,OP1.1] [F12-OS1.2,OP1.2] |
|
3.7.1.2. |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] |
| Subsection 3.7.2. | Pin Refinishing |
|
3.7.2.1. (1) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] |
| (2) | Note1 |
| (3) | [F01-OS1.1,OP1.1] |
| Subsection 3.7.3. | Flammable Liquids and Combustible Liquids |
| 3.7.3.1. | Note1 |
| 3.7.3.2. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F03-OS1.2,OP1.2] |
| Accceptable Solution | Objectives and Functional Statements |
|---|---|
| SECTION 4.1 | APPLICATION |
| Subsection 4.1.1. | Scope and Application |
| 4.1.1.1. (1) | Note1 |
| (2) | Note1 |
| 4.1.1.2. (1) | Note1 |
| (2) | Note1 |
| 4.1.1.3. | Note1 |
| 4.1.1.4. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| Subsection 4.1.2. | Classification |
| 4.1.2.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| 4.1.2.2. | Note1 |
| 4.1.2.3. (1) | Note1 |
| (2) | Note1 |
| Subsection 4.1.3. | Flash Point |
| 4.1.3.1. (1) | [F01-OS1.1] |
| (2) | [F01-OS1.1] |
| (3) | [F01-OS1.1] |
| (4) | [F01-OS1.1] |
| Subsection 4.1.4. | Electrical Installations |
| 4.1.4.1. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| Subsection 4.1.5. | Fire Prevention and Protection |
| 4.1.5.1. | Note1 |
| 4.1.5.2. | RESERVED |
| 4.1.5.3. | [F01-OS1.1,OP1.1] |
| 4.1.5.4. | [F01-OS1.1,OP1.1] |
| 4.1.5.5. (1) | [F01-OS1.1,OP1.1] |
| (2) | Note1 |
| 4.1.5.6. | Note1 |
| 4.1.5.7. | [F12-OS1.2,OP1.2,OP3.1] |
| 4.1.5.8. | Note1 |
| 4.1.5.9. (1) | [F01,F43-OS1.1,OP1.1] |
| (2) | [F01,F43-OS1.1] |
| (3) |
[F02-OS1.2,OP1.2] [F43-OS1.1,OP1.1] |
| (4)(a) | [F01-OS1.1,OP1.1] |
| (b) |
[F01-OS1.1,OP1.1] [F13-OS1.4,OP1.4] |
| (c) | [F03-OS1.2,OP1.2] |
| (d) |
[F01-OS1.1] [F12-OS1.2,OS1.5,OP1.2] |
| (e) | [F02-OS1.2,OP1.2] |
| (f) | [F02,F20-OS1.2,OS1.3,OP1.2,OP1.3] |
| (g) | [F13-OS1.1,OP1.1] |
| (5) | Note1 |
| 4.1.5.10. | [F82-OS1.1,OS1.2,OS1.4,OP1.1,OP1.2,OP1.4] |
| Subsection 4.1.6. | Spill Control and Drainage Systems |
| 4.1.6.1. (1) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2,OP3.1] |
| (2) | Note1 |
| (3) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| (4)(a) | [F44-OS1.2,OP3.1] |
| (b) | [F44-OH5,OP3.1] |
| (c) | [F44-OS1.5] |
| (d) | [F44-OS1.2,OP3.1] |
| (e) | [F44-OS1.4,OP1.4] |
| (f) | [F44-OS1.2,OP1.2] |
| (g) | [F44-OS1.2,OP1.2] |
| (h) | [F44-OS1.2,OP1.2] |
| (i) | [F44-OS1.2,OP1.2] |
| (j) | [F44-OS1.2,OP1.2] |
| 4.1.6.2. (1)(a) | [F44-OS1.1,OS1.2,OS1.4,OH5,OP1.1,OP1.2, OP1.4] |
| (b) | [F44-OS1.1,OS1.2,OS1.4,OP1.1,OP1.2,OP1.4, OP3.1] |
| (2) | [F03-OS1.2,OP1.2] |
| 4.1.6.3. (1) | [F44,F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| (2) | [F44-OS1.1,OS1.2,OP1.1,OP1.2] |
| (3)(a) |
[F03-OP3.1] [F44-OS1.1,OS1.2,OP1.1,OP1.2] |
| (b) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] [F44-OS1.1,OS1.2,OP1.1,OP1.2] |
| (4) | Note1 |
|
4.1.6.4. (1) |
[F02-OS1.2,OP1.2] [F44-OS1.2,OP1.2,OP3.1] |
| (2)(a) | [F43,F81-OS1.1,OP1.1] |
| (b) | [F01-OS1.1,OP1.1] |
| (c) | [F01-OS1.1,OP1.1] |
| (d) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] [F44-OS1.1,OS1.2,OP1.1,OP1.2] |
| (e) | [F12-OS1.2,OP1.2] |
| (f) | [F12-OS1.2,OP1.2] |
| (g) | [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| (h) | [F12-OS1.1,OS1.2,OP1.1,OP1.2] |
| (3) | [F12-OS1.1,OS1.2,OP1.1,OP1.2] |
| Subsection 4.1.7. | Ventilation |
| 4.1.7.1. | [F01-OS1.1,OP1.1] |
| 4.1.7.2. (1) | [F01-OS1.1,OP1.1] |
| (2) | Note1 |
| (3) | [F01-OS1.1,OP1.1] |
| (4) | [F01-OS1.1,OP1.1] |
| (5) | [F01,F11-OS1.1,OP1.1] |
| (6) | [F01-OS1.1,OP1.1] |
| 4.1.7.3. (1) | Note1 |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
| 4.1.7.4. (1)(a) | [F01-OS1.1,OP1.1] |
| (b) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2,OP3.1] |
| 4.1.7.5. (1) | [F03-OS1.2,OP1.2] |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F01,F44-OS1.1,OP1.1] |
| 4.1.7.6. (1) | [F01,F11-OS1.1,OP1.1] |
| 4.1.7.7. | Note1 |
| 4.1.7.8. | [F82-OS1.1,OP1.1] |
| Subsection 4.1.8. | Handling of Flammable and Combustible Liquids |
| 4.1.8.1. (1) | Note1 |
| (2) | [F43-OS1.1,OP1.1] |
| (3) | Note1 |
| 4.1.8.2. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | Note1 |
| (4) | [F22-OS1.1,OP1.1] |
| 4.1.8.3. (1) | [F43-OS1.1,OP1.1] |
| (2) | [F01,F20,F81-OS1.1,OP1.1] |
| 4.1.8.4. (1) | [F01,F43,F81-OS1.1] |
| (2) | [F43-OS1.1,OP1.1] |
| SECTION 4.2 | CONTAINER STORAGE AND HANDLING |
| Subsection 4.2.1. | Scope |
| 4.2.1.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| Subsection 4.2.2. | General |
| 4.2.2.1. (1) | Note1 |
| (2) | Note1 |
|
4.2.2.2. |
[F04-OS1.2,OS1.5,OH5,OP1.2] [F20 OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| 4.2.2.3. (1) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] [F43-OS3.4] |
| (2) | Note1 |
| Subsection 4.2.3. | Containers and Portable Tanks |
| 4.2.3.1. (1) | [F01,F04,F20,F43,F80,F81-OS1.1,OP1.1] |
|
4.2.3.2. (1) |
[F01,F81-OS1.1,OP1.1] [F12-OS1.1,OS1.2,OP1.1,OP1.2] |
| (2) |
[F01,F81-OS1.1,OP1.1] [F12-OS1.1,OS1.2,OP1.1,OP1.2] |
| 4.2.3.3. (1) | Note1 |
| Subsection 4.2.4. | Assembly and Residential Occupancies |
| 4.2.4.1. (1) | Note1 |
| 4.2.4.2. (1) | Note1 |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | [F02-OS1.2,OP1.2] |
| (4) | [F02,F03-OS1.2,OP1.2] |
|
4.2.4.3. |
[F01-OS1.1,OP1.1] [F12-OS1.2,OP1.2] |
| 4.2.4.4. | [F03-OS1.2,OP1.2] |
| 4.2.4.5. | [F02-OS1.2,OP1.2] |
| 4.2.4.6. | [F02-OS1.2,OP1.2] |
| Subsection 4.2.5. | Mercantile Occupancies |
| 4.2.5.1. (1) | Note1 |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | [F02-OS1.2,OP1.2] |
| (4) | Note1 |
| (5) | [F02,F03-OS1.2,OP1.2] |
| 4.2.5.2. (1) | [F01,F43-OS1.1,OP1.1] |
| (2) |
[F04-OS1.5,OP1.2] [F20-OS1.1,OS1.2,OP1.1] |
| (3) | Note1 |
|
4.2.5.3. |
[F01-OS1.1,OP1.1] [F02,F03,F44-OS1.2,OP1.2] |
|
Subsection 4.2.6. |
Business and Personal Services, Educational and Care or Detention Occupancies |
| 4.2.6.1. (1) | Note1 |
| 4.2.6.2. (1) |
[F01,F43-OS1.1,OP1.1] Applies to the following text in the opening line of Sentence (1) in the Fire Code: “Except as permitted in Article 4.2.6.3., flammable liquids and combustible liquids shall be kept in closed containers”.
[F02,F03-OS1.2,OP1.2] |
| 4.2.6.3. (1) | Note1 |
| (2) | Note1 |
|
4.2.6.4. |
[F01,F04,F43-OS1.1,OP-1] [F02-OS1.2,OP1.2] |
| 4.2.6.5. | Note1 |
| Subsection 4.2.7. | Industrial Occupancies |
| 4.2.7.1. | Note1 |
| 4.2.7.2. (1) | [F02,F03-OS1.2,OP1.2] |
| 4.2.7.3. | [F03-OS1.2,OP1.2] |
|
4.2.7.4. (1) |
[F01-OS1.1] [F02,F03-OS1.2,OP1.2] |
| (2) |
[F01-OS1.1,OP1.1] [F02,OS1.2,OP1.2] |
|
4.2.7.5. (1)
|
[F01-OS1.1] [F02,F03-OS1.2,OP1.2] [F04-OS1.2,OS1.5,OH5,OP1.2] [F20-OS1.1,OS1.2] |
| (2) | [F03-OS1.2,OP1.2] |
| (3) | Note1 |
| (4) | Note1 |
| 4.2.7.6. | Note1 |
| 4.2.7.7. (1) | [F02-OS1.2,OP1.2] |
|
4.2.7.8. (1)
|
[F02,F81-OS1.2,OP1.2] Applies to the following text in the Fire Code: “The clearance between the top of storage and the __ sprinkler head deflectors or other overhead fire protection system components shall be not less than 450 mm”.
[F04-OS1.3,OP1.3] |
| (2) |
[F10-OS1.5] [F81,F82-OS1.1,OP1.1] |
| 4.2.7.9. | Note1 |
| 4.2.7.10. | Note1 |
| 4.2.7.11. | Note1 |
| 4.2.7.12. | Note1 |
| 4.2.7.13. | Note1 |
| Subsection 4.2.8. | Incidental Use |
| 4.2.8.1. | Note1 |
| 4.2.8.2. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | [F02-OS1.2,OP1.2] |
| 4.2.8.3. (1)(a) | [F01-OS1.1,OP1.1] |
| (b) | Note1 |
| (c) | Note1 |
| (d) | Note1 |
| (e) | Note1 |
| 4.2.8.4. (1) | [F02,F03-OS1.2,OP1.2] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | [F02-OS1.2,OP1.2] |
| (5) | Note1 |
| (6) | Note1 |
| Subsection 4.2.9. | Rooms for Container Storage and Dispensing |
| 4.2.9.1. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02,F03-OS1.2,OP1.2] |
| (3) | Note1 |
| 4.2.9.2. (1) | [F44-OS1.1,OS1.2,OP1.1,OP1.2] |
| (2) | Note1 |
| 4.2.9.3. | Note1 |
|
4.2.9.4. |
[F10-OS1.5] [F12-OS1.2,OP1.2] [F81,F82-OS1.1,OP1.1] |
| 4.2.9.5. | [F01,F43-OS1.1] |
| 4.2.9.6. (1) | [F02-OS1.3,OP1.3] |
| (2) | [F02-OS1.3,OP1.3] |
| 4.2.9.7. | Note1 |
| 4.2.9.8. (1) | Note1 |
| (2) |
[F03-OS1.2,OP1.2] [F10-OS1.5] |
| (3) | [F10-OS1.5] |
| (4) | [F05-OS1.5] |
| (5) | [F10-OS1.5] |
| Subsection 4.2.10. | Cabinets for Container Storage |
| 4.2.10.1. | [F01,F43-OS1.1,OP1.1] |
| 4.2.10.2. | [F02-OS1.2,OP1.2] |
| 4.2.10.3. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | [F02-OS1.2,OP1.2] |
| 4.2.10.4. | [F01-OS1.1,OP1.1] |
| 4.2.10.5. (1) |
[F01-OS1.1] [F03-OS1.2,OP1.2] [F44-OS1.1,OP1.1] |
|
4.2.10.6. (1) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] |
| Subsection 4.2.11. | Outdoor Container Storage |
| 4.2.11.1. (1) | [F02,F03-OS1.2,OP3.1] |
| (2) | [F02,F03-OS1.2,OP3.1] |
| 4.2.11.2. | Note1 |
| 4.2.11.3. | [F12-OP3.1] |
| 4.2.11.4. | Note1 |
| 4.2.11.5. (1) | [F34-OS1.1] |
| SECTION 4.3 | TANK STORAGE |
| Subsection 4.3.1. | Design, Construction and Use of Storage Tanks |
| 4.3.1.1. | Note1 |
| 4.3.1.2. (1) | [F01,F20,F43,F80,F81-OS1.1,OP1.1] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| (7) | Note1 |
| (8) |
[F20,F80,F81-OP1.1] [F43-OS1.1,OP1.1,OP3.1] |
| (9) | Note1 |
| 4.3.1.3. (1) | [F01,F20,F43,F80,F81-OS1.1,OP1.1] |
| (2) | [F01,F20,F43,F80,F81-OS1.1,OP1.1] |
| (3) | Note1 |
| 4.3.1.4. | Note1 |
| 4.3.1.5. | [F80-OS1.1,OP1.1] |
| 4.3.1.6. | [F04-OS1.2,OP1.2] |
|
4.3.1.7. |
[F12-OS1.2,OP1.2] [F81-OS1.1,OP1.1] |
| 4.3.1.8. (1) | [F43-OS1.1,OP1.1] |
| 4.3.1.9. | [F01,F20,F43,F80,F81-OS1.1,OP1.1] |
| 4.3.1.10. (1) | [F01,F20,F43-OS1.1,OP1.1] |
| (2) | [F01,F20,F43-OS1.1,OP1.1] |
| (3) | [F01,F20,F43-OS1.1,OP1.1] |
| (4) | Note1 |
| Subsection 4.3.2. | Installation of Outside Aboveground Storage Tanks |
| 4.3.2.1. (1) | Note1 |
| (2) | [F03-OS1.2,OP3.1] |
| (3) | [F03-OS1.2,OP3.1] |
| (4) | [F03-OS1.2,OP3.1] |
| (5) | [F03-OS1.2,OP3.1] |
| (6) | Note1 |
| (7) | Note1 |
| (8) | [F03-OS1.2,OP3.1] |
|
4.3.2.2. (1) |
Note1 Applies to the following text in the Fire Code: “Except as required in Sentences (2) and (3) and in Article 4.3.2.3.” [F03,F12-OP1.2] [F82-OS1.1,OP1.1] |
| (2) | [F82-OS1.1,OP1.1] |
| (3) | [F03-OP1.2] |
| 4.3.2.3. (1) | [F03-OS1.2,OP1.2] |
|
(2) |
Note1 Applies to the following text in the Fire Code: “Secondary containments for flammable liquid or combustible liquid storage tanks shall not contain any liquefied petroleum gas cylinder or tank”. [F02,F03,F12-OS1.2,OP1.2] |
| 4.3.2.4. (1) | [F12-OP1.2] |
| (2) | [F12-OP1.2] |
| (3) | [F02,F03,F12-OP1.2] |
| 4.3.2.5. (1) | Note1 |
| (2) | [F2,F3,F12-OS1.2,OP1.2] |
| 4.3.2.6. | Note1 |
|
Subsection 4.3.3. |
Supports, Foundations and Anchorage for Aboveground Storage Tanks |
|
4.3.3.1. (1) |
[F02-OS1.2,OP1.2] Applies to the following opening text in Sentence (1) of the Fire Code: “Storage tanks shall rest on the ground or on foundations, supports or piling made of concrete, masonry or steel”. [F20,F22,F81-OS1.1,OP1.1] |
| (2) | [F22,F80-OS1.1,OP1.1] |
| (3) | [F04-OS1.2,OP1.2] |
| (4) | [F20-OS1.1,OP1.1] |
| 4.3.3.2. (1) | [F22-OS1.1,OP1.1] |
| 4.3.3.3. | [F22-OS1.1,OP1.1] |
|
Subsection 4.3.4. |
Normal and Emergency Venting for Aboveground Storage Tanks |
|
4.3.4.1. (1) |
[F04-OS1.2,OP1.2] [F20-OS1.1,OS1.2,OP1.1,OP1.2] |
|
4.3.4.2. |
[F04-OS1.2,OP1.2] [F20-OS1.1,OS1.2,OP1.1,OP1.2] |
| Subsection 4.3.5. | Vent Piping for Aboveground Storage Tanks |
| 4.3.5.1. | Note1 |
| 4.3.5.2. (1) | [F01,F43-OS1.1,OP1.1] |
| (2) | [F01,F43-OS1.1,OP1.1] |
| (3) | [F44-OS1.2,OP1.2] |
| 4.3.5.3. (1) | [F20,F81-OS1.1,OP1.1] |
| (2) | [F01,F81-OS1.1,OP1.1] |
| Subsection 4.3.6. | Openings Other than Vents in Aboveground Storage Tanks |
| 4.3.6.1. (1) | [F43-OS1.1,OP1.1] |
| (2) | [F43-OS1.1,OP1.1] |
| 4.3.6.2. (1) |
[F04-OS1.2,OP1.2] [F20-OS1.1,OP1.1] |
| (2) | [F04,F20-OS1.1,OP1.1] |
| 4.3.6.3. | [F01,F43,F81-OS1.1,OP1.1] |
| 4.3.6.4. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F43-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
|
Subsection 4.3.7. |
Secondary Containment for Aboveground Storage Tanks |
| 4.3.7.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
|
4.3.7.2. (1)
|
Note1 Applies to the following text in the opening line of Sentence (1) in the Fire Code: “Except as provided in Sentence (2)”. [F04-OS1.2,OP1.2] [F04-OH5] [F04-OP3.1] |
| (2) | [F44-OS1.1,OP1.1] |
| (3) | Note1 |
| (4) | Note1 |
| 4.3.7.3. (1) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2,OP3.1] |
| (2) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2,OP3.1] |
| (3) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2,OP3.1] |
| 4.3.7.4. (1) |
[F01,F82-OS1.1,OP1.1] [F81-OS1.2,OP1.2,OP3.1] |
| (2) |
[F01,F82-OS1.1,OP1.1] [F81-OS1.2,OP1.2,OP3.1] |
|
4.3.7.5. (1)(a) |
[F12-OS1.2,OP1.2] [F82-OS1.1,OP1.1] |
| (b) | [F10-OS1.5] |
| (c) | [F12-OS1.2,OP1.2] |
| (2) | [F12-OS1.1,OP1.1] |
| 4.3.7.6. | [F04-OS1.2,OP1.2] |
| 4.3.7.7. | [F82-OS1.1,OP1.1] |
|
4.3.7.8. (1) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] Applies to the following text in the Fire Code: “Liquids, debris __ shall not be permitted to accumulate in the contained space created by the secondary containment”. [F12-OS1.2,OP1.2] |
| (2) | Note1 |
| (3)(a) | [F44-OS1.1,OP1.1,OS1.2,OP1.2,OP3.1] |
| (b) | [F12-OS1.2,OH5,OP1.2,OP3.1] |
| (c) | [F12-OS1.2,OH5,OP1.2,OP3.1] |
| 4.3.7.9. | Note1 |
| Subsection 4.3.8. | Installation of Underground Storage Tanks |
| 4.3.8.1. (1) | [F81-OS1.1,OP1.1] |
| (2)(a) | [F21-OS1.1,OP1.1] |
| (b) | [F01,F20,F21,F81-OS1.1,OP1.1] |
| (c) | [F20,F81-OS1.1,OP1.1] |
| 4.3.8.2. (1) | [F20,F81-OS1.1,OP1.1] |
| (2) | [F20,F81-OS1.1,OP1.1] |
| (3) | [F20,F81-OS1.1,OP1.1] |
|
(4) |
[F04-OS1.2,OP1.2] [F20,F81-OS1.1,OP1.1] |
| 4.3.8.3. (1) | [F82-OS1.1,OP1.1] |
| (2) | [F82-OS1.1,OP1.1] |
| 4.3.8.4. (1) | [F81-OS1.1,OP1.1] |
| (2) | Note1 |
| 4.3.8.5. (1) | [F81-OS1.1,OP1.1] |
| (2) | [F81-OS1.1,OP1.1] |
| (3) | [F20-OS1.1,OP1.1] |
| 4.3.8.6. (1) | Note1 |
| 4.3.8.7. (1) | [F43-OS1.1,OP1.1] |
| 4.3.8.8. | Note1 |
| 4.3.8.9. (1) | [F22-OS1.1,OP1.1] |
| (2) | [F80,F81-OS1.1,OP1.1] |
|
Subsection 4.3.9. |
Corrosion Protection of Underground Steel Storage Tanks |
| 4.3.9.1. (1) | [F80-OS1.1,OP1.1] |
| (2) | [F80-OS1.1,OP1.1] |
| Subsection 4.3.10. | Vents for Underground Storage Tanks |
| 4.3.10.1. | [F20,F81-OS1.1,OP1.1] |
| 4.3.10.2. | Note1 |
| 4.3.10.3. (1) | [F01,F43-OS1.1,OP1.1] |
| (2) | [F01,F43-OS1.1,OP1.1] |
| (3) | [F20,F81-OS1.1,OP1.1] |
| (4) | [F11,F20,F81-OS1.1,OP1.1] |
| (5) | [F20,F22,F81-OS1.1,OP1.1] |
| 4.3.10.4. (1) | [F20,F81-OS1.1,OP1.1] |
| (2) | [F20-OS1.1,OP1.1] |
| (3) | [F01,F81-OS1.1,OP1.1] |
|
Subsection 4.3.11. |
Openings Other than Vents in Underground Storage Tanks |
| 4.3.11.1. | [F01-OS1.1] [F43-OS1.1,OP1.1] |
| 4.3.11.2. | [F01,F43,F81-OS1.1,OP1.1] |
| 4.3.11.3. (1) | [F43-OS1.1,OP1.1] |
| (2) | Note1 |
| (3) | [F01-OS1.1,OP1.1,OP3.1] |
| (4) | [F43-OS1.1,OP1.1,OP3.1] |
| (5) | [F01,F43-OS1.1,OP1.1] |
| Subsection 4.3.12. | Installation of Storage Tanks Inside Buildings |
| 4.3.12.1. | Note1 |
| 4.3.12.2. |
[F01-OS1.1,OP1.1] [F02,F03,F04-OS1.2,OP1.2] [F43,F81-OS1.1,OS1.2,OP1.1,OP1.2] |
| 4.3.12.3. | [F20-OS1.1,OP1.1] |
|
4.3.12.4. (1)(a) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
|
(b) |
[F01,F44-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] |
|
(2) |
[F01-OS1.1,OP1.1] [F02,F12-OS1.2,OP1.2] |
| (3) | Note1 |
| 4.3.12.5. | [F03-OS1.2,OP1.2] |
| 4.3.12.6. (1) | Note1 |
| 4.3.12.7. (1)(a) | [F44-OS1.1,OH5,OP1.1] |
| (b) | Note1 |
| (c) | Note1 |
| 4.3.12.8. (1) | Note1 |
| (2) | Note1 |
| 4.3.12.9. (1) | Note1 |
|
(2) |
[F04-OS1.3,OP1.3] [F20,F22,F80,F81-OS1.1,OP1.1] |
| 4.3.12.10. (1) | [F01-OS1.1,OP1.1] |
| Subsection 4.3.13. | Rooms for Storage Tanks |
| 4.3.13.1. (1)(a) | [F03-OS1.2,OP1.2] |
| (b) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| (c) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| (d) | Note1 |
| (e) | [F01-OS1.1,OP1.1] |
| 4.3.13.2. | [F82-OS1.1,OP1.1] |
| 4.3.13.3. |
[F02-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
| 4.3.13.4. (1) | [F12-OS1.2,OP1.2] |
| (2) | Note1 |
| 4.3.13.5. (1) | [F12-OS1.2,OP1.2] |
| (2) | [F12-OS1.2,OP1.2] |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | [F12-OS1.2,OP1.2] |
|
Subsection 4.3.14. |
Openings Other than Vents in Storage Tanks in Buildings |
|
4.3.14.1. (1) |
[F01-OS1.1] [F43-OS1.1,OP1.1] |
| (2) | [F44-OS1.1,OP1.1] |
| 4.3.14.2. (1) | [F01,F43,F81-OS1.1,OP1.1] |
| Subsection 4.3.15. | Leakage Testing of Storage Tanks |
| 4.3.15.1. (1) | [F82-OS1.1,OP1.1] |
| (2) | [F82-OS1.1,OP1.1] |
| (3) | [F01,F82-OS1.1,OP1.1] |
| (4) | [F01,F82-OS1.1,OP1.1] |
| 4.3.15.2. | Note1 |
| 4.3.15.3. (1) | [F43,F82-OS1.1,OP1.1] |
|
(2) |
[F12-OS1.2,OP1.2] [F43,F82-OS1.1,OP1.1] |
| 4.3.15.4. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | [F82-OS1.1,OP1.1] |
| (5) | [F20,F82-OS3.4] |
| (6) | [F20,F82-OS1.1,OP1.1] |
| (7) | [F01-OS1.1,OP1.1] |
| 4.3.15.5. (1) | Note1 |
| (2) | [F20,F82-OS1.1,OP1.1] |
| Subsection 4.3.16. | Leakage Detection of Storage Tanks |
| 4.3.16.1. (1) | [F82-OS1.1,OP1.1] |
| (2) | [F82-OS1.1,OP1.1] |
| (3) | [F82-OS1.1,OP1.1] |
| (4) | Note1 |
| 4.3.16.2. (1) | [F01,F82-OS1.1,OP1.1] |
| 4.3.16.3. (1) | [F43,F82-PS1.1,OP1.1] |
| Subsection 4.3.17. | Out of Service |
| 4.3.17.1. (1)(a) | [F82-OS1.1,OP1.1] |
| (b) | [F01,F34-OS1.1,OP1.1] |
| (c) | [F20,F81-OS1.1] |
| (2)(a) | [F01,F43-OS1.1,OP1.1] |
| (b) | [F01-OS1.1] |
| (c) | [F82-OS1.1,OP1.1] |
| (d) | [F01,F34-OS1.1,OP1.1] |
| (3)(a)(i) | [F82-OS1.1,OP1.1] |
| (ii) | [F82-OS1.1,OP1.1] |
| (iii) | [F01,F34-OS1.1] |
| (b) | [F82-OS1.1,OP1.1] |
| (4) | [F82-OS1.1,OP1.1] |
| 4.3.17.2. (1) | [F34-OS1.1,OP1.1] |
| (2) | [F82-OS1.1,OP1.1] |
| (3)(a) | [F01,F43-OS1.1,OP1.1] |
| (b) | [F81-OS1.1,OP1.1] |
| 4.3.17.3. | [F81-OS1.1,OP1.1] |
| 4.3.17.4. (1)(a) | [F01,F43-OS1.1,OP1.1] |
| (b) | [F01-OS1.1,OP1.1] |
| (c) | [F81-OS1.1,OP1.1] |
| (2) | [F44-OS1.1,OP1.1] |
| 4.3.17.5. (1) | [F81-OS1.1,OP1.1] |
| (2) | [F81-OS1.1,OP1.1] |
| 4.3.17.6. | [F80-OS1.1,OP1.1] |
| SECTION 4.4 | PIPING AND TRANSFER SYSTEMS |
| Subsection 4.4.1. | Scope |
| 4.4.1.1. (1) | Note1 |
| (2) | Note1 |
| Subsection 4.4.2. | Materials for Piping, Valves and Fittings |
|
4.4.2.1. (1) |
[F20-OS1.1,OP1.1] Applies to the following text in the Fire Code: “Materials for piping systems containing flammable liquids or combustible liquids shall be suitable for the maximum anticipated working pressures and operating temperatures”. [F80-OS1.1,OP1.1] |
| (2) | Note1 |
|
(3) |
[F04-OS1.2,OH5,OP1.2] [F20,F81-OS1.1,OP1.1] |
| (4) | [F20,F80,F81-OS1.1,OP1.1] |
| (5) | [F20,F80,F81-OS1.1,OP1.1] |
| (6) | Note1 |
| 4.4.2.2. | [F20,F80,F81-OS1.1,OP1.1] |
| Subsection 4.4.3. | Corrosion Protection of Piping Systems |
| 4.4.3.1. (1) | [F80-OS1.1,OP1.1] |
| (2) | [F80-OS1.1,OP1.1] |
| Subsection 4.4.4. | Identification of Piping Systems |
|
4.4.4.1. (1) |
[F12-OS1.2,OP1.2] [F81-OS1.1,OP1.1] |
|
(2) |
[F12-OS1.2,OP1.2] [F81-OS1.1,OP1.1] |
|
(3) |
[F12-OS1.1,OS1.2,OP1.1,OP1.2] [F81-OS1.1,OP1.1] |
| 4.4.4.2. (1) | [F12-OS1.2,OP1.2] |
| (2) | [F12-OS1.2,OP1.2] |
| Subsection 4.4.5. | Joints in Piping Systems |
| 4.4.5.1. | [F43,F81-OS1.1,OP1.1] |
|
4.4.5.2. (1) |
Note1 Applies to the following text in the Fire Code: “Welding of piping for flammable liquids or combustible liquids shall conform to Section 5.17”.
[F04-OS1.2,OH5,OP1.2] |
| (2) | [F01-OS1.1,OP1.1] |
| 4.4.5.3. (1) | [F20,F81-OS1.1,OP1.1] |
| (2) | Note1 |
| 4.4.5.4. | [F04-OS1.1,OH5,OP1.1] |
| 4.4.5.5. |
[F04-OS1.2,OH5,OP1.2] [F20-OS1.1,OP1.1] |
| 4.4.5.6. (1) | [F80,F82-OS1.1,OP1.1] |
| Subsection 4.4.6. | Leakage Testing of Piping Systems |
| 4.4.6.1. (1) | Note1 |
| (2) | [F82-OS1.1,OP1.1] |
| (3) | [F82-OS1.1,OP1.1] |
| 4.4.6.2. | Note1 |
| 4.4.6.3. | [F82-OS1.1,OP1.1] |
| 4.4.6.4. (1) | [F82-OS1.1,OP1.1] |
| (2) | [F82-OS1.1,OP1.1] |
| 4.4.6.5. (1) | [F20-OS1.1,OP1.1] |
| (2) | [F20,F81-OS1.1,OP1.1] |
| (3) | [F81-OS1.1,OS3.1,OS3.4,OP1.1] |
| 4.4.6.6. | [F43-OS1.1,OP1.1] |
| 4.4.6.7. | [F81,F82-OS1.1,OP1.1] |
| Subsection 4.4.7. | Location and Arrangement of Piping |
| 4.4.7.1. (1) | [F43-OS1.1,OP1.1] |
| (2) | [F43-OS1.1,OP1.1] |
| (3) | Note1 |
| (4) | [F81-OS1.1,OP1.1] |
| 4.4.7.2. (1) | [F20,F22-OS1.1,OP1.1] |
| (2) | [F81-OS1.1,OP1.1] |
| (3) | [F80,F82-OS1.1,OP1.1] |
| 4.4.7.3. (1)(a) | [F02,F04-OS1.2,OP1.2] |
|
(b) |
[F04-OS1.2,OP1.2] [F44-OS1.1,OP1.1] |
|
(2) |
[F02-OS1.2,OP1.2] [F44-OS1.1,OP1.1] |
| (3) | [F81-OS1.1,OP1.1] |
|
(4) |
[F04-OS1.2,OH5,OP1.2] [F21-OS1.1,OP1.1] |
| 4.4.7.4. (1) | [F21,F22-OS1.1,OP1.1] |
| (2) | [F20-OS1.1,OP1.1] |
| (3) | [F21,F22-OS1.1,OP1.1] |
| (4) | [F21,F22-OS1.1,OP1.1] |
| 4.4.7.5. (1)(a) | [F21,F22-OS1.1,OP1.1] |
| (b) | [F20,F21-OS1.1,OP1.1] |
| (2) | [F21,F22-OS1.1,OP1.1] |
| 4.4.7.6. | Note1 |
| 4.4.7.7. (1) | [F21,F82-OS1.1,OP1.1] |
| (2) | [F44-OS1.1,OP1.1] |
| (3) | [F21-OS1.1,OP1.1] |
| 4.4.7.8. (1) | [F81-OS1.1,OP1.1] |
|
(2) |
[F02-OS1.2,OP1.2] [F04-OS1.1,OP1.1] |
| 4.4.7.9. (1) | Note1 |
| (2) | [F01-OS1.1,OP1.1] |
| 4.4.7.10. (1) | [F81-OS1.1,OP1.1] |
| (2) | [F20-OS1.1,OP1.1] |
| (3) | [F20-OS1.1,OP1.1] |
| (4) | [F20-OS1.1,OP1.1] |
| 4.4.7.11. (1) | [F20-OS1.1,OP1.1] |
| (2) | [F20-OS1.1,OP1.1] |
| 4.4.7.12. (1) | [F81-OS1.1,OP1.1] |
| 4.4.7.13. (1) | [F21-OS1.1,OP1.1] |
| (2) | [F20,F21,F81-OS1.1,OP1.1] |
| Subsection 4.4.8. | Valves in Piping Systems |
| 4.4.8.1. (1) | [F20,F81-OS1.1,OP1.1] |
| (2) | [F20,F81-OS1.1,OP1.1] |
| (3) | [F20,F81-OS1.1,OP1.1] |
| (4) | Note1 |
| 4.4.8.2. (1) | [F44-OS1.1,OS1.2,OP1.1,OP1.2] |
| (2) | [F12,F44-OS1.1,OS1.2,OP1.1,OP1.2] |
|
(3)
|
[F04-OS1.2,OH5,OP1.2] [F20-OS1.1,OP1.1] Applies to the following text in the opening line of Sentence (3) of the Fire Code: “steel shut-off valves shall be provided”.
[F12,F44-OS1.1,OS1.2,OP1.1,OP1.2]
[F82-OS1.1,OP1.1] |
| (4) | Note1 |
| 4.4.8.3. | Note1 |
| 4.4.8.4. | [F20-OS1.1,OP1.1] |
| 4.4.8.5. | [F12-OS1.1,OS1.2,OP1.1,OP1.2] |
| 4.4.8.6. (1) | [F12,F81-OS1.1,OH5,OP1.1] |
| (2) | [F12,F81-OS1.1,OP1.1] |
| Subsection 4.4.9. | Heating of Piping Systems |
| 4.4.9.1. | [F01,F20,F81-OS1.1,OP1.1] |
| 4.4.9.2. (1) | [F20,F81-OS1.1,OP1.1] |
| (2) | [F20,F81-OS1.1,OP1.1] |
| (3) | [F01,F81-OS1.1,OP1.1] |
| 4.4.9.3. | Note1 |
| 4.4.9.4. (1) | Note1 |
| (2) |
[F82-OS1.1,OP1.1] Applies to the following text in the opening line of Sentence (2) of the Fire Code: “Systems permitted in Sentence (1) shall be installed and tested as complete units”. [F01-OS1.1,OP1.1] [F20,F81-OS1.1,OP1.1] [F01-OS1.1,OP1.1] |
| (3) | [F82-OS1.1,OP1.1] |
| 4.4.9.5. (1) | Note1 |
| (2) | [F01,F81-OS1.1,OP1.1] |
| Subsection 4.4.10. | Method of Transfer in Piping Systems |
| 4.4.10.1. (1) | [F01-OS1.1,OP1.1,OP3.1] |
| 4.4.10.2. (1) | Note1 |
|
(2) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| 4.4.10.3. (1) | [F20,F81-OS1.1,OP1.1] |
|
(2) |
[F02-OS1.2,OP1.2] [F82-OS1.1,OS1.2,OP1.1,OP1.2] Applies to the following text in the Fire Code: “Pits provided in conformance with Sentence (1) shall not be larger than necessary for inspection and maintenance”. [F81-OS1.1,OP1.1] |
|
4.4.10.4. |
[F12,F44-OS1.1,OS1.2,OP1.1,OP1.2] Applies to the following text in the Fire Code: “Pumps for piping systems shall be provided with duplicate control switches __ with one located in the operating area and the other at a remote location”.
[F44-OS1.1,OS1.2,OP1.1,OP1.2] |
| 4.4.10.5. (1) | Note1 |
| (2) | [F20,F81,F82-OS1.1,OP1.1] |
| (3) | [F20,F81-OS1.1,OP1.1] |
| (4) | [F20,F81-OS1.1,OP1.1] |
|
(5) |
[F43-OS1.1,OP1.1] [F44-OS1.2,OP1.2] |
| (6) | [F81-OS1.1,OP1.1] |
| 4.4.10.6. (1) | [F20,F81,F82-OS1.1,OP1.1] |
| (2) | [F20,F81-OS1.1,OP1.1] |
| (3) | [F20,F81-OS1.1,OP1.1] |
| (4) | [F04,F81-OS1.2,OH5,OP1.2] |
| 4.4.10.7. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| Subsection 4.4.11. | Method of Transfer in Piping Systems |
|
4.4.11.1. |
[F12-OS1.1,OS1.2,OP1.1,OP1.2] [81-OS1.1,OP1.1] |
| 4.4.11.2. (1)(a) | [F12-OS1.1,OP1.1] |
| (b) | [F12,F43-OS1.1,OP1.1] |
| (c) | [F12-OS1.2,OP1.2] |
|
(d) |
[F12-OS1.1,OS1.2,OP1.1,OP1.2] [F81-OS1.1,OP1.1] |
|
(2) |
[F12-OS1.1,OP1.1] Applies to the following text in the Fire Code: “Employees engaged in the operation of equipment for the transfer of flammable liquids or combustible liquids shall be trained in the location, function and operation of __ manual emergency shut-off valves”. [F12-OS1.2,OP1.2] |
| 4.4.11.3. | [F12-OS1.1,OS1.2,OP1.1,OP1.2] |
| 4.4.11.4. | [F02,F12-OS1.2,OP1.2] |
| 4.4.11.5. (1) | [F82-OS1.1,OP1.1] |
| (2) | [F82-OS1.1,OP1.1] |
| (3) | [F82-OS1.1,OP1.1] |
| (4) | Note1 |
| 4.4.11.6. | [F82-OS1.1,OP1.1] |
| 4.4.11.7. (1) | [F01,F43-OS1.1,OP1.1] |
| (2) | [F43-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
| (4) | [F81-OS1.1,OP1.1] |
| (5) | [F43-OS1.1,OP1.1] |
| (6) | [F01,F43-OS1.1,OP1.1] |
| SECTION 4.5 | FUEL DISPENSING STATIONS |
| Subsection 4.5.1. | Scope |
| 4.5.1.1. (1) | Note1 |
| (2) | [F01,F03,F81-OS1.1] |
| (3) | Note1 |
| Subsection 4.5.2. | Storage and Handling |
| 4.5.2.1. (1) | Note1 |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | [F34,F81-OS1.1,OP1.1] |
| 4.5.2.2. (1) | Note1 |
| 4.5.2.3. (1) | [F02-OS1.2,OP1.2] |
| (2)(a) | Note1 |
|
(b) |
[F01-OS1.1,OP1.1] [F12-OS1.2,OP1.2] |
| 4.5.2.4. | Note1 |
| 4.5.2.5. | Note1 |
| 4.5.2.6. | [F22,F81-OS1.1,OP1.1] |
| 4.5.2.7. | Note1 |
| Subsection 4.5.3. | Dispensing Systems |
| 4.5.3.1. | [F01,F43-OS1.1] |
| 4.5.3.2. | [F20,F43,F80,F81-OS1.1] |
|
4.5.3.3. (1) |
[F01,F43-OS1.1] Applies to the following text in the opening line of Sentence (1) in the Fire Code: “Fixed dispensers for Class I liquids shall be installed outside buildings”. [F01-OP3.1] [F01,F81-OS1.1] [F01,F81-OS1.1] [F01-OS1.1] [F02-OS1.2] [F01-OS1.1] |
| (2)(a) | [F43,F81-OS1.1,OP1.1] |
| (b) |
[F01-OS1.1,OP1.1] [F12,F44-OS1.2,OP1.2] |
| (c) | Note1 |
|
(d) |
Note1 Applies to the following text in the Fire Code: “ventilation is provided in conformance with Subsection 4.1.7.” [F01-OS1.1,OP1.1] |
| 4.5.3.4. (1) | [F81-OS1.1,OP1.1] |
| 4.5.3.5. | [F81-OS1.1] |
| Subsection 4.5.4. | Shut-Off Devices |
| 4.5.4.1. (1) |
[F06-OS1.2,OH5,OP1.2] Applies to the following text in the Fire Code: “A device to shut off power to all dispensers and pumps”. [F44-OS1.1,OH5,OP1.1] |
| (2) | [F12-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| 4.5.4.2. (1) | [F12,F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| (2) | [F12-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| 4.5.4.3. | [F12-OS1.1,OH5,OP1.1] |
| Subsection 4.5.5. | Delivery Hose and Nozzles |
| 4.5.5.1. (1) |
[F01-OS1.1] [F20,F43,F81-OS1.1,OP1.1] |
| (2) | [F43-OS1.1,OH5,OP1.1] |
| (3) | [F43-OS1.1,OH5,OP1.1] |
| (4) | Note1 |
| 4.5.5.2. (1) |
[F01-OS1.1] [F20,F43,F81-OS1.1,OP1.1] |
| (2) | [F43-OS1.1,OP1.1] |
| (3) | [F43-OS1.1,OP1.1] |
| (4) | [F81-OS1.1,OP1.1] |
| (5) | [F81-OS1.1,OP1.1] |
| Subsection 4.5.6. | Remote Pumping Systems |
| 4.5.6.1. | Note1 |
| 4.5.6.2. (1) | [F20,F81-OS1.1,OP1.1] |
| (2) | [F20,F22,F81-OS1.1,OP1.1] |
|
4.5.6.3. (1) |
[F04-OS1.1,OP1.1] [F43,F81-OS1.1,OH5,OP1.1] |
| (2) | [F82-OS1.1,OH5,OP1.1] |
| 4.5.6.4. (1) | [F01-OS1.1,OP3.1] |
| (2) | Note1 |
| 4.5.6.5. | Note1 |
| 4.5.6.6. (1) | [F12,F20,F22,F81-OS1.1,OP1.1] |
|
(2) |
[F02-OS1.2,OP1.2] [F44-OS1.1,OP1.1] |
| (3) | [F22-OS1.1,OP1.1] |
| (4) | Note1 |
| (5) | [F43,F81-OS1.1,OH5,OP1.1] |
|
(6) |
[F01-OS1.1,OP1.1] [F43-OS1.1,OP1.1] |
| Subsection 4.5.7. | Spill Control |
| 4.5.7.1. (1)(a) | Note1 |
| (b) | [F44-OS1.2,OP1.3] |
| Subsection 4.5.8. | Supervision and Dispensing Procedures |
|
4.5.8.1. (1) |
[F01-OS1.1,OP1.1] [F43,F44-OS1.1,OH5,OP1.1] |
|
(2) |
[F01-OS1.1,OP1.1] [F34,F43-OS1.1,OH5,OP1.1] |
|
(3) |
[F01-OS1.1,OP1.1] [F43-OS1.1,OH5,OP1.1] |
| (4) | [F81-OS1.1,OH5,OP1.1] |
| 4.5.8.2. (1) | [F81-OS1.1,OH5,OP1.1] |
| (2) | [F01,F12,F43,F44-OS1.1,OH5,OP1.1] |
| (3) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
|
(4) |
[F01-OS1.1,OP1.1] [F43,F44-OS1.1,OH5,OP1.1] |
|
(5) |
[F01-OS1.1,OP1.1] [F12,F43,F44-OS1.1,OH5,OP1.1] |
|
4.5.8.3. |
[F01-OS1.1,OP1.1] [F12,F44-OS1.1,OH5,OP1.1] |
| 4.5.8.4. (1) | Note1 |
| (2) | Note1 |
| (3) | [F34-OS1.1,OH5,OP1.1] |
| (4) | [F81-OS1.1,OH5,OP1.1] |
| (5) | [F13-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| (6)(a) | [F12-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| (b) | [F13-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| 4.5.8.5. (1)(a) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| (b) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
|
(c) |
[F01-OS1.1,OP1.1] [F43-OS1.1,OP1.1,OS1.2,OP1.2] |
| (d) | [F01-OS1.1] |
| (e) | [F01-OS1.1,OP1.1] |
| (f) | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| (2)(a) | [F01,F44-OS1.1] |
| (b)(i) | [F43-OS1.1] |
| (ii) | [F01,F44-OS1.1] |
| (3) | [F12,F81-OS1.1,OS1.2,OP1.1,OP1.2] |
| 4.5.8.6. (1) | [F01-OS1.1] |
| (2) | [F01-OS1.1] |
| (3) | Note1 |
| (4)(a) | [F43-OS1.1] |
| (b) | [F43-OS1.1] |
| (c) | [F44-OS1.1] |
| (d) | [F01-OS1.1] |
| (e) | [F43-OS1.1] |
| (f) | [F01-OS1.1.] |
| 4.5.8.7. | [F01-OS1.1] |
| 4.5.8.8. (1) |
[F01-OS1.1] Applies to the following text in the Fire Code: “At least one __ sign conforming to Sentences (2) to (4) shall be provided for each dispenser in a location visible to every driver approaching the dispenser”. [F80-OS1.1] |
| (2) | [F01-OS1.1] |
| (3) | [F01-OS1.1] |
| (4) | [F01-OS1.1] |
| Subsection 4.5.9. | Leakage Detection |
| 4.5.9.1. | Note1 |
| Subsection 4.5.10. | Fire Prevention and Protection |
| 4.5.10.1. | [F02,F12-OS1.2,OP1.2] |
| 4.5.10.2. | Note1 |
| SECTION 4.6 | BULK PLANTS |
| Subsection 4.6.1. | Scope |
| 4.6.1.1. | Note1 |
| Subsection 4.6.2. | Storage |
| 4.6.2.1. (1) | [F43-OS1.1,OP1.1] |
|
4.6.2.2. |
[F03-OS1.2,OH5,OP1.2] [F21,F22,F81-OS1.1,OP1.1] |
| 4.6.2.3. | [F20,F82-OS1.1,OP1.1] |
| 4.6.2.4. (1) | Note1 |
| (2) | Note1 |
| 4.6.2.5. | Note1 |
| 4.6.2.6. (1) | [F01,F34-OH5,OP3.1] |
| Subsection 4.6.3. | Dispensing |
| 4.6.3.1. | Note1 |
| 4.6.3.2. (1) | [F34-OS1.1,OP1.1] |
| (2) | [F43,F81-OS1.1,OP1.1] |
| 4.6.3.3. | Note1 |
| 4.6.3.4. | Note1 |
| Subsection 4.6.4. | Loading and Unloading Facilities |
|
4.6.4.1. (1) |
[F01-OS1.1,OP3.1] [F03-OS1.2,OP1.2,OP3.1] |
|
(2) |
[F03-OS1.2,OH5,OP1.2] [F21,F22,F81-OS1.1,OP1.1] |
| (3) | Note1 |
| 4.6.4.2. | [F01-OS1.1] |
| 4.6.4.3. (1) | [F01,F43-OS1.1,OP1.1] |
| (2) | [F43,F82-OS1.1,OP1.1] |
| 4.6.4.4. (1) | [F43-OS1.1,OP1.1] |
| (2) | [F43,F81-OS1.1,OP1.1] |
| 4.6.4.5. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
| (4) | [F01-OS1.1,OP1.1] |
| (5) | [F01-OS1.1,OP1.1] |
| 4.6.4.6. | Note1 |
| Subsection 4.6.5. | Fire Protection |
| 4.6.5.1. | [F02,F12-OS1.2,OP1.2] |
| Subsection 4.6.6. | Spill Control |
| 4.6.6.1. | Note1 |
| SECTION 4.7 | PIERS AND WHARVES |
| Subsection 4.7.1. | Scope |
| 4.7.1.1. | Note1 |
| Subsection 4.7.2. | General |
| 4.7.2.1. (1) | [F03-OS1.2,OP3.1] |
| (2) | [F03-OS1.2,OP3.1] |
|
4.7.2.2. |
[F04-OS1.2,OH5,OP1.2] [F20,F21,F80-OS1.1,OP1.1] |
| Subsection 4.7.3. | Storage Tanks |
|
4.7.3.1. (1) |
[F04-OS1.2,OH5,OP1.2] [F20-OS1.1,OP1.1] |
|
(2) |
[F04-OS1.2,OH5,OP1.2] [F20,F43-OS1.1,OP1.1] |
|
(3) |
[F04-OS1.2,OH5,OP1.2] [F20,F43-OS1.1,OP1.1] |
| Subsection 4.7.4. | Piping, Valves and Fittings |
| 4.7.4.1. | Note1 |
| 4.7.4.2. (1) | [F20,F22-OS1.1,OP1.1] |
| (2) | [F04-OS1.2,OH5,OP1.2] |
| (3) | [F04-OS1.2,OH5,OP1.2] |
| 4.7.4.3. | [F81-OS1.1,OP1.1] |
| 4.7.4.4. | [F21-OS1.1,OP1.1] |
| 4.7.4.5. | [F12,F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| 4.7.4.6. (1) | [F82-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| (2) | [F82-OS1.2,OH5,OP1.2] |
| 4.7.4.7. |
[F12-OS1.1,OS1.2,OH5,OP1.1,OP1.2] [F81-OS1.1,OP1.1] |
| 4.7.4.8. (1) | Note1 |
| (2) | [F82-OS1.1,OP1.1] |
| Subsection 4.7.5. | Bonding and Grounding |
| 4.7.5.1. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| Subsection 4.7.6. | Fire Protection |
| 4.7.6.1. (1) | [F02,F12-OS1.2,OP1.2] |
| (2) |
[F12-OS1.2,OP1.2] Applies to the following text in the Fire Code: “Portable extinguishers shall be kept in the pump house or other suitable location where they will be accessible in the event of an emergency”. [F34-OS1.2,OP1.2] |
| (3) | [F02,F12-OS1.2,OP1.2] |
| (4) | Note1 |
| 4.7.6.2. | [F12,F13-OS1.2,OP1.2] |
| Subsection 4.7.7. | Bulk Transfer Stations |
| 4.7.7.1. (1) | [F01,F81-OS1.1,OH5,OP1.1] |
| (2) | [F34-OS1.1,OP1.1] |
| 4.7.7.2. (1) | Note1 |
| (2) | [F43-OS1.1,OP1.1] |
|
4.7.7.3. (1) |
[F12-OS1.1,OS1.2,OP1.1,OP1.2] [F22,F43-OS1.1,OP1.1] [F44-OS1.2,OP1.2] |
| (2) | [F22,F43-OS1.1,OP1.1] |
| (3) | Note1 |
| Subsection 4.7.8. | Cargo Hose |
| 4.7.8.1. (1) | [F20,F22,F81-OS1.1,OP1.1] |
| 4.7.8.2. | [F20,F82-OS1.1,OP1.1] |
| 4.7.8.3. | [F20,F22-OS1.1,OP1.1] |
| Subsection 4.7.9. | Cargo Pumps |
| 4.7.9.1. | Note1 |
| 4.7.9.2. | [F20,F81-OS1.1,OP1.1] |
| 4.7.9.3. (1)(a) | [F02-OS1.2,OP1.2] |
|
(b) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2,OP3.1] |
|
(2)
|
[F01-OS1.1] [F02-OS1.2,OP3.1] [F03-OS1.2] [F44-OS1.1,OP3.1] |
| Subsection 4.7.10. | Pump Houses |
|
4.7.10.1. |
[F02-OS1.2,OP1.2] Applies to the following text in the Fire Code: “Pump houses shall be of noncombustible construction”. [F44-OS1.1,OP1.1] |
| 4.7.10.2. | Note1 |
| Subsection 4.7.11. | Transfer Operations |
| 4.7.11.1. (1) |
[F01,F12-OS1.1,OP1.1] [F02,F44-OS1.2,OP1.2] [F43-OS1.1,OH5,OP1.1] |
|
(2) |
[F12,F44-OS1.1,OP1.1] [F43-OS1.1,OH5,OP1.1] |
| (3)(a) | [F01-OS1.1,OP1.1] |
| (b) | [F43-OS1.1,OP1.1] |
| (c) |
[F43-OS1.1,OP1.1] Applies to the following text in the Fire Code: “inspect the hose and connections for leakage”. [F44-OS1.1,OP1.1] |
| 4.7.11.2. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| 4.7.11.3. (1) | [F21-OS1.1,OP1.1] |
| (2) | [F43-OS1.1,OP1.1] |
| (3) | [F43-OS1.1,OP1.1] |
| (4) | [F44-OS1.1,OP1.1] |
| 4.7.11.4. (1) | [F43-OS1.1,OP1.1] |
| (2) | [F43-OS1.1,OP1.1] |
| SECTION 4.8 | PROCESS PLANTS |
| Subsection 4.8.1. | Scope |
| 4.8.1.1. (1) | Note1 |
| (2) | Note1 |
| Subsection 4.8.2. | Outdoor Processing Equipment |
| 4.8.2.1. (1) | Note1 |
| (2) | [F03-OS1.2,OP3.1] |
| (3) | [F03-OS1.2,OP3.1] |
| (4) | [F03-OS1.2,OP3.1] |
| Subsection 4.8.3. | Processing Buildings |
| 4.8.3.1. | [F02-OS1.3,OP1.3] |
| 4.8.3.2. | [F03-OS1.2,OP1.2] |
| 4.8.3.3. (1) | Note1 |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
| 4.8.3.4. (1) | Note1 |
| (2) | [F01-OS1.1,OP1.1] |
| Subsection 4.8.4. | Fire Prevention and Protection |
| 4.8.4.1. (1)(a) | [F01,F43-OS1.1,OP1.1] |
| (b) | [F43-OS1.1,OP1.1] |
| (2) | Note1 |
| 4.8.4.2. (1)(a) | [F02,F20-OS1.2,OS1.3,OP1.2,OP1.3] |
| (b) | [F02,F20-OS1.2,OS1.3,OP1.2,OP1.3] |
| (c) | [F01-OS1.1,OP1.1] |
| 4.8.4.3. (1) |
[F01,F20-OS1.1,OP1.1,OP3.1] [F02,F03,F43-OS1.2,OP1.2,OP3.1] [F04-OS1.3,OP1.3,OP3.1] [F44-OS1.2,OH5,OP1.2,OP3.1] [F81-OS1.1,OS1.2,OP1.1,OP1.2,OP3.1] |
| (2) |
[F01,F20-OS1.1,OP1.1,OP3.1] [F02,F03,F43-OS1.2,OP1.2,OP3.1] [F04-OS1.3,OP1.3,OP3.1] [ F44-OS1.2,OH5,OP1.2,OP3.1] [F81-OS1.1,OS1.2,OP1.1,OP1.2,OP3.1] |
|
(3) |
[F81-OS1.1,OS1.2,OS1.3,OH5,OP1.1,OP1.2, OP1.3,OP3.1] |
| (4) | Note1 |
| (5) | Note1 |
| SECTION 4.9 | DISTILLERIES |
| Subsection 4.9.1. | Scope |
| 4.9.1.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| Subsection 4.9.2. | General |
| 4.9.2.1. (1) | Note1 |
| (2) | Note1 |
| Subsection 4.9.3. | Storage Tanks and Containers |
| 4.9.3.1. | [F20,F43,F80-OS1.1,OP1.1] |
| 4.9.3.2. (1) | [F02,F04-OS1.2,OP1.2] |
| (2) | [F04-OS1.2,OP1.2] |
| (3) | [F02-OS1.2,OP1.2] |
|
4.9.3.3. |
[F01-OS1.1,OP1.1] [F20,F81-OS1.1,OH5,OP1.1] |
| Subsection 4.9.4. | Storage |
|
4.9.4.1. (1) |
[F02-OS1.2,OP1.2] [F11-OS1.5] |
| (2) | [F02-OS1.2,OP1.2] |
| 4.9.4.2. | Note1 |
| Subsection 4.9.5. | Piping and Pumping Systems |
| 4.9.5.1. | [F20,F80-OS1.1,OP1.1] |
| Subsection 4.9.6. | Ventilation |
| 4.9.6.1. (1) | [F01-OS1.1] |
| (2) | Note1 |
| Subsection 4.9.7. | Spill Control |
| 4.9.7.1. | Note1 |
| Subsection 4.9.8. | Fire Protection |
| 4.9.8.1. (1) | Note1 |
| (2) | [F02,F12-OS1.2,OP1.2] |
| (3) | [F02,F12-OS1.2,OP1.2] |
| (4) | [F02,F12-OS1.2,OP1.2] |
|
4.9.8.2. (1) |
[F01-OS1.1,OP1.1] [F02,F12-OS1.2,OP1.2] |
| (2) | Note1 |
| SECTION 4.10 | RESERVED |
| SECTION 4.11 | TANK VEHICLES |
| Subsection 4.11.1. | Scope |
| 4.11.1.1. | Note1 |
| Subsection 4.11.2. | General |
| 4.11.2.1. (1) | [F02,F12-OS1.2,OP1.2] |
| (2) | [F12-OS1.2,OP1.2] |
| 4.11.2.2. | Note1 |
| 4.11.2.3. (1)(a) |
[F01,F43,F44-OS1.1,OH5,OP1.1] [F02,F03-OS1.2,OP1.2] |
| (b) | [F21-OS1.1,OP1.1] |
| (c) | Note1 |
|
4.11.2.4. (1) |
[F02-OS1.2,OP3.1] [F34,F81-OS1.1] |
|
(2) |
[F03-OS1.2,OP3.1] [F81-OS1.1,OP3.1] |
|
Subsection 4.11.3. |
Loading, Unloading and Dispensing from Tank Vehicles |
| 4.11.3.1. | Note1 |
| 4.11.3.2. | [F01-OS1.1,OP1.1] |
| 4.11.3.3. | [F01-OS1.1,OP1.1] |
| 4.11.3.4. | [F44-OS1.1,OS1.2,OP1.1,OP1.2] |
| 4.11.3.5. | [F01-OS1.1,OP1.1] |
| 4.11.3.6. | [F01-OS1.1,OP1.1] |
| 4.11.3.7. (1) | [F43-OS1.1,OP1.1] |
| (2) | [F20,F43,F81-OS1.1,OP1.1] |
| (3) | Note1 |
| 4.11.3.8. (1) | [F01,F43-OS1.1,OP1.1] |
|
(2)(a) |
[F01-OS1.1,OP3.1] [F03-OS1.2,OP3.1] |
| (b) | [F02,F12-OP1.2] |
| (c) | Note1 |
| (d) | [F43,F44-OS1.1] |
| (e) | [F44-OS1.1] |
| SECTION 4.12 | LABORATORIES |
| Subsection 4.12.1. | Scope |
| 4.12.1.1. | Note1 |
| Subsection 4.12.2. | Separation |
| 4.12.2.1. (1) | [F03-OS1.2,OP1.2] |
| (2) | Note1 |
| Subsection 4.12.3. | Maximum Quantities |
|
4.12.3.1. (1) |
[F02-OS1.2,OP1.2] [F43-OS1.1,OP1.1] |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | [F03-OS1.2,OP1.2] |
| (4) | [F01,F43-OS1.1,OP1.1] |
| Subsection 4.12.4. | Emergency Planning |
| 4.12.4.1. (1) | Note1 |
| (2) | [F12-OS1.5] |
| (3) | [F01,F12-OS1.1,OP1.1] |
| (4) | [F34-OS1.1,OP1.1] |
| Subsection 4.12.5. | Spill Control |
| 4.12.5.1. | Note1 |
| Subsection 4.12.6. | Electrical Equipment |
| 4.12.6.1. | Note1 |
| Subsection 4.12.7. | Inspection and Maintenance |
| 4.12.7.1. (1) | [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| (2) | [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| Subsection 4.12.8. | Ventilation |
| 4.12.8.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| 4.12.8.2. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01,F81-OS1.1,OP1.1] |
| 4.12.8.3. (1) | [F01-OS1.1,OP1.1] |
| 4.12.8.4. (1) | [F01-OS1.1,OP1.1] |
| (2)(a) | [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| (b) | [F02-OS1.2,OP1.2] |
|
4.12.8.5. (1)(a) |
[F01,F80-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| (b) | [F82-OS1.1,OP1.1] |
| (c) | [F81-OS1.1,OP1.1] |
| (d) | Note1 |
| (2)(a) | [F80-OS1.1,OP1.1] |
| (b) | [F02-OS1.2,OP1.2] |
| (3) | Note1 |
| Subsection 4.12.9. | Refrigerated Storage |
| 4.12.9.1. (1) | [F81-OS1.1,OP1.1] |
| (2) | [F01,F43-OS1.1,OP1.1] |
| Accceptable Solution | Objectives and Functional Statements |
|---|---|
| SECTION 5.1 | GENERAL |
| Subsection 5.1.1. | Application |
| 5.1.1.1. | Note1 |
| Subsection 5.1.2. | Means of Egress |
| 5.1.2.1. | [F10-OS1.5] |
| Subsection 5.1.3. | Electrical Installations |
| 5.1.3.1. | [F01-OS1.1] |
| Subsection 5.1.4. | Ventilation |
| 5.1.4.1. | [F01-OS1.1] |
| SECTION 5.2 | EXPLOSIVES, FIREWORKS AND PYROTECHNICS |
| Subsection 5.2.1. | Explosives |
|
5.2.1.1. |
[F01-OS1.1] [F02,F03-OS1.2] |
| 5.2.1.2 (1)(a) | [F12-OS1.2,OP1.2] |
| (b) | [F12-OS1.2,OP1.2] |
| (c) | [F12-OS1.2,OP1.2] |
| Subsection 5.2.2. | Fireworks and Pyrotechnics |
|
5.2.2.1. |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| 5.2.2.2. |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] [F03-OP3.1] |
| SECTION 5.3 | MATCHES |
| Subsection 5.3.1. | Storage |
|
5.3.1.1. |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| 5.3.1.2. | [F03-OS1.2,OP1.2] |
| 5.3.1.3. | [F02,F03-OS1.2,OP1.2] |
| 5.3.1.4. | [F03-OS1.2,OP1.2] |
| 5.3.1.5. | [F03-OS1.2,OP1.2] |
| SECTION 5.4 | CELLULOSE NITRATE PLASTICS |
| Subsection 5.4.1. | Displays |
| 5.4.1.1. | [F02,F03-OS1.2,OP1.2] |
| 5.4.1.2. | [F01-OS1.1,OP1.1] |
| Subsection 5.4.2. | Manufacture |
|
5.4.2.1. |
[F01-OS1.1,OP1.1] [F02,F12-OS1.2,OP1.2] |
| 5.4.2.2. | [F02-OS1.2,OP1.2] |
|
5.4.2.3. |
[F01-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] |
|
5.4.2.4. |
[F01-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] |
| 5.4.2.5. | [F81-OS1.1,OP1.1] |
| 5.4.2.6. | [F02-OS1.2,OP1.2] |
| 5.4.2.7. | [F02-OS1.2,OP1.2] |
| 5.4.2.8. | [F81-OS1.1,OP1.1] |
| Subsection 5.4.3. | Storage of Finished Products |
| 5.4.3.1. | [F01-OS1.1,OP1.1] |
| 5.4.3.2. (1) | [F01-OS1.1,OP1.1] |
| 5.4.3.3. (1) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| 5.4.3.4. (1) |
[F01-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
| 5.4.3.5. (1) |
[F01-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
| Subsection 5.4.4. | Cellulose Nitrate Motion Picture Film |
| 5.4.4.1. | Note1 |
| 5.4.4.2. | [F02,F03-OS1.2,OP1.2] |
|
5.4.4.3. |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| Subsection 5.4.5. | Fire Protection |
| 5.4.5.1. | [F02-OS1.2,OP1.2] |
| SECTION 5.5 | RESERVED |
| SECTION 5.6 | COMPRESSED GAS CYLINDERS |
| Subsection 5.6.1. | General |
| 5.6.1.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| 5.6.1.2. (1) | [F01,F43-OS1.1,OP1.1] |
| (2) | [F01,F43-OS1.1,OP1.1] |
| 5.6.1.3. | [F01,F43-OS1.1,OP1.1] |
| 5.6.1.4. | [F01,F43,F81-OS1.1,OP1.1] |
| 5.6.1.5. | [F20-OS1.1,OP1.1] |
| 5.6.1.6. (1)(a) | [F80-OS1.1,OP1.1] |
| (b) | [F01-OS1.1,OP1.1] |
| 5.6.1.7. | [F01-OS1.1,OP1.1] |
| Subsection 5.6.2. | Storage |
|
5.6.2.1. (1) |
[F01,F34,F80,F81-OS1.1] [F02-OS1.2] |
| (2) | [F02-OS1.2] |
| 5.6.2.2. (1) |
[F12-OS1.2] [F34-OS1.1] |
| (2) |
[F01-OS1.1] [F03-OS1.2] |
| 5.6.2.3. (1) | [F44-OS1.1,OP1.1] |
| (2) | Note1 |
| 5.6.2.4. (1)(a) | [F03-OS1.2,OP1.2] |
| (b) |
[F03,F12-OS1.2,OP1.2] [F44-OS1.1,OS1.2,OP1.1,OP1.2] |
| (c) |
[F03,F12-OS1.2,OP1.2] [F44-OS1.1,OS1.2,OP1.1,OP1.2] |
| (d) |
[F02-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
| (e) | [F01-OS1.1,OP1.1] |
| (f) | [F01-OS1.1,OP1.1] |
| (g) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | Note1 |
| (4) | [F01-OS1.1,OP1.1] |
|
(5) |
[F01,F81-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] |
| 5.6.2.5. | RESERVED |
| 5.6.2.6. | Note1 |
|
5.6.2.7. (1) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 5.6.2.8. | [F12-OS1.2,OP1.2] |
| SECTION 5.7 | RESERVED |
| SECTION 5.8 | RESERVED |
| SECTION 5.9 | RESERVED |
| SECTION 5.10 | COMBUSTIBLE DUST PRODUCING PROCESSES |
| Subsection 5.10.1. | Dust Collection |
| 5.10.1.1. (1) | Note1 |
|
(2) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
|
5.10.1.2. (1) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
| 5.10.1.3. | [F01-OS1.1,OP1.1] |
| 5.10.1.4. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F01-OS1.1,OP1.1] |
| 5.10.1.5. (1) | [F02-OS1.2,OP1.2] |
|
(2) |
[F02,F03-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
|
(3) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] |
| (4) | Note1 |
| (5) | Note1 |
| 5.10.1.6. | [F01-OS1.1,OP1.1] |
|
5.10.1.7. (1) |
[F02-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
|
(2) |
[F02-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
|
5.10.1.8. (1) |
[F02-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
|
(2) |
[F02-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
| 5.10.1.9. | [F01-OS1.1,OP1.1] |
| 5.10.1.10. | [F02-OS1.2,OP1.2] |
| 5.10.1.11. (1)(a) | [F01,F20-OS1.1,OP1.1] |
| (b) | [F01,F20-OS1.1,OP1.1] |
| (c) | [F20-OS1.1,OP1.1] |
| (d) | [F20-OS1.1,OP1.1] |
| 5.10.1.12. | [F01-OS1.1,OP1.1] |
| 5.10.1.13. | [F01-OS1.1,OP1.1] |
| 5.10.1.14. | [F01-OS1.1,OP1.1] |
| SECTION 5.11 | COMBUSTIBLE FIBRES |
| Subsection 5.11.1. | Storage |
| 5.11.1.1. | [F02-OS1.2,OP1.2] |
| 5.11.1.2. (1) | [F02,F03-OS1.2,OP1.2] |
| (2) | [F02,F03-OS1.2,OP1.2] |
| (3) | [F02,F03-OS1.2,OP1.2] |
| (4) | [F02,F03-OS1.2,OP1.2] |
| (5) | [F02,F03-OS1.2,OP1.2] |
| 5.11.1.3. (1)(a) | [F02-OS1.2,OP1.2] |
| (b) | [F04-OS1.2,OS1.3,OP1.2,OP1.3] |
| (c) | [F03,F12-OS1.2,OP1.2] |
| (d) | [F04-OS1.3,OP1.3] |
| 5.11.1.4. | [F04-OS1.2,OS1.3,OS1.5,OP1.2,OP1.3] |
| 5.11.1.5. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02,F04-OS1.2,OS1.3,OP1.2,OP1.3] |
| 5.11.1.6. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F81-OS1.1,OP1.1] |
| Subsection 5.11.2. | Fire Protection |
| 5.11.2.1. | [F12-OS1.2,OP1.2] |
| 5.11.2.2. | Note1 |
|
5.11.2.3. |
[F04-OS1.3,OP1.3] [F12-OS1.2,OP1.2] |
|
SECTION 5.12 |
SPRAY APPLICATIONS USING FLAMMABLE AND COMBUSTIBLE MATERIALS |
| Subsection 5.12.1. | Location |
| 5.12.1.1. | [F03-OS1.2,OP1.2] |
| Subsection 5.12.2. | Construction |
| 5.12.2.1. (1) | [F02,F03-OS1.2,OP1.2] |
| (2) | [F02,F82-OS1.2,OP1.2] |
| (3) | [F02-OS1.2,OP1.2] |
| 5.12.2.2. (1) |
[F02-OS1.2,OP1.2] [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| (2) | Note1 |
| 5.12.2.3. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | [F82-OS1.2,OP1.2] |
| (4) | [F01-OS1.1,OP1.1] |
| (5) | [F82-OS1.1,OP1.1] |
| (6) | [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| (7) | [F01-OS1.1,OP1.1] |
| 5.12.2.4. | [F01-OS1.1,OP1.1] |
| Subsection 5.12.3. | Ventilation |
|
5.12.3.1. (1) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
|
5.12.3.2. |
[F02-OS1.2,OP1.2] [F44-OS1.1,OP1.1] |
|
5.12.3.3. |
[F02-OS1.2,OP1.2] [F44-OS1.1,OP1.1] |
| 5.12.3.4. | [F03-OS1.2,OP1.2] |
| 5.12.3.5. | [F44-OS1.1,OP1.1] |
| 5.12.3.6. (1) | [F81-OS1.1,OP1.1] |
| (2) | [F81,F82-OS1.1,OP1.1] |
| Subsection 5.12.4. | Exhaust Ducts |
| 5.12.4.1. | [F02,F03,F04-OS1.2,OP1.2] |
| 5.12.4.2. | [F03-OS1.2,OP1.2] |
| 5.12.4.3. (1) | [F03-OS1.2,OP1.2] |
| (2) | [F03-OS1.2,OP1.2] |
|
5.12.4.4. |
[F02-OS1.2,OP1.2] [F82-OS1.1,OP1.1] |
| 5.12.4.5. (1) | [F03-OS1.2,OP1.2,OP3.1] |
| Subsection 5.12.5. | Electrical Equipment |
| 5.12.5.1. | [F01-OS1.1,OP1.1] |
| 5.12.5.2. | [F01-OS1.1,OP1.1] |
| 5.12.5.3. | [F01-OS1.1,OP1.1] |
| Subsection 5.12.6. | Flammable Liquids and Combustible Liquids |
|
5.12.6.1. |
Note1 Applies to the following text in the Fire Code: “Flammable liquids and combustible liquids for use in spraying areas shall be stored and handled in conformance with Part 4”. [F02-OS1.2,OP1.2] |
| 5.12.6.2. | [F01,F43-OS1.1,OP1.1] |
| 5.12.6.3. | [F01,F43-OS1.1,OP1.1] |
| 5.12.6.4. | [F81-OS1.1,OP1.1] |
| Subsection 5.12.7. | Control of Fire Hazards |
| 5.12.7.1. |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] Applies to the following text in the Fire Code: “The spraying equipment for a spray booth shall be interlocked to shut down in the event of failure of the ventilation system”. [F01,F81-OS1.1,OP1.1] |
| 5.12.7.2. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
|
5.12.7.3. |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| 5.12.7.4. | [F01-OS1.1,OP1.1] |
| 5.12.7.5. | [F01-OS1.1,OP1.1] |
| 5.12.7.6. | [F01-OS1.1,OP1.1] |
| Subsection 5.12.8. | Fire Protection Equipment |
| 5.12.8.1. | Note1 |
| 5.12.8.2. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | Note1 |
| 5.12.8.3. (1) | [F81-OS1.2,OP1.2] |
| (2) | [F82-OS1.2,OP1.2] |
| Subsection 5.12.9. | Drying Operations |
| 5.12.9.1. | [F01-OS1.1,OP1.1] |
| 5.12.9.2. | [F01-OS1.1,OP1.1] |
| 5.12.9.3. (1) | Note1 |
|
5.12.9.4. (1) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| SECTION 5.13 | DIP TANKS |
| Subsection 5.13.1. | Location |
| 5.13.1.1. | [F02,F03-OS1.2,OP1.2] |
|
5.13.1.2. |
[F01-OS1.1,OP1.1] [F12-OS1.2,OP1.2] |
| Subsection 5.13.2. | Construction |
| 5.13.2.1. | [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2] |
| 5.13.2.2. (1) | [F04-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| 5.13.2.3. | [F43-OS1.1,OH5,OP1.1] |
| 5.13.2.4. | [F04-OS1.2,OP1.2] |
| 5.13.2.5. | [F03,F44-OS1.2,OP1.2] |
| 5.13.2.6. | [F03,F44-OS1.2,OP1.2] |
| Subsection 5.13.3. | Overflow and Drain Pipes |
| 5.13.3.1. | [F43-OS1.1,OP1.1] |
| 5.13.3.2. |
[F03-OS1.2,OP1.2] [F43-OS1.1,OP1.1] |
| 5.13.3.3. |
[F03-OS1.2,OP1.2] [F43-OS1.1,OP1.1] |
| 5.13.3.4. |
[F03-OS1.2,OP1.2] [F43-OS1.1,OP1.1] |
| 5.13.3.5. | [F81-OS1.1,OP1.1] |
|
5.13.3.6. |
[F82-OS1.1,OP1.1] Applies to the following text in the Fire Code: “Piping connections for __ overflow lines shall be designed so as to allow for easy access to their interiors for cleaning purposes”. [F82-OS1.2,OP1.2] |
| 5.13.3.7. | [F02,F43-OS1.2,OP1.2] |
| 5.13.3.8. | [F02,F03-OS1.2,OP1.2] |
| 5.13.3.9. | [F02-OS1.2,OP1.2] |
| 5.13.3.10. | [F06,F12-OS1.2,OP1.2] |
| 5.13.3.11. | [F02-OS1.2,OP1.2] |
| 5.13.3.12. | [F81-OS1.2,OP1.2] |
| Subsection 5.13.4. | Salvage Tanks |
| 5.13.4.1. | [F81-OS1.2,OP1.2] |
| 5.13.4.2. | [F43-OS1.2,OP1.2] |
| 5.13.4.3. | [F03-OS1.2,OP1.2] |
| Subsection 5.13.5. | Control of Fire Hazards |
| 5.13.5.1. | [F01-OS1.1,OP1.1] |
|
5.13.5.2. |
[F01-OS1.1,OP1.1] [F11-OS1.1,OS1.5,OP1.1] |
| 5.13.5.3. | [F01-OS1.1,OP1.1] |
| 5.13.5.4. | [F02,F03-OS1.2,OP1.2] |
| 5.13.5.5. | [F01-OS1.1,OP1.1] |
| 5.13.5.6. | [F01-OS1.1,OP1.1] |
| 5.13.5.7. (1) | Note1 |
| (2) | [F02-OS1.2,OP1.2] |
| 5.13.5.8. | [F01-OS1.1,OP1.1] |
| 5.13.5.9. | [F81-OS1.1,OP1.1] |
| Subsection 5.13.6. | Fire Protection |
|
5.13.6.1. |
[F02-OS1.2,OP1.2] [F04-OS1.3,OP1.3] |
| 5.13.6.2. (1) | [F02,F03-OS1.2,OP1.2] |
| 5.13.6.3. | Note1 |
| 5.13.6.4. | Note1 |
|
SECTION 5.14 |
SPECIAL PROCESSES INVOLVING FLAMMABLE AND COMBUSTIBLE LIQUIDS |
| Subsection 5.14.1. | Quench Tanks |
| 5.14.1.1. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| 5.14.1.2. | [F01-OS1.1] |
| 5.14.1.3. | Note1 |
|
5.14.1.4. (1) |
[F01,F11-OS1.1,OP1.1] [F81-OS1.2,OP1.2] |
| (2) | [F01,F81-OS1.1,OP1.1] |
| 5.14.1.5. | [F01-OS1.1,OP1.1] |
| 5.14.1.6. | Note1 |
| 5.14.1.7. | [F01-OS1.1,OP1.1] |
| Subsection 5.14.2. | Flow-Coating Operations |
| 5.14.2.1. (1) | Note1 |
| (2) | Note1 |
| 5.14.2.2. | [F01-OS1.1,OP1.1] |
| 5.14.2.3. | [F01-OS1.1,OP1.1] |
| 5.14.2.4. | [F01-OS1.1,OP1.1] |
|
5.14.2.5. (1) |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| Subsection 5.14.3. | Roll-Coating Processes |
| 5.14.3.1. | Note1 |
| 5.14.3.2. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| 5.14.3.3. | [F02,F03-OS1.2,OP1.2] |
| Subsection 5.14.4. | Electrostatic Spraying and Detearing Equipment |
| 5.14.4.1. (1) | [F01-OS1.1,OP1.1] |
| (2) | Note1 |
|
5.14.4.2. (1) |
[F01,F81-OS1.1,OP1.1] [F11-OS1.1,OS1.5,OP1.1] |
| 5.14.4.3. | [F01,F82-OS1.1,OP1.1] |
| 5.14.4.4. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F81-OS1.1,OP1.1] |
| 5.14.4.5. | [F02-OS1.2,OP1.2] |
| 5.14.4.6. | [F01,F81-OS1.1,OP1.1] |
| 5.14.4.7. | [F01-OS1.1,OP1.1] |
| 5.14.4.8. | [F01-OS1.1,OP1.1] |
| 5.14.4.9. | [F01-OS1.1,OP1.1] |
| 5.14.4.10. | [F01-OS1.1,OP1.1] |
| 5.14.4.11. | [F01-OS1.1,OP1.1] |
| 5.14.4.12. | [F01,F43-OS1.1,OP1.1] |
| 5.14.4.13. | [F01-OS1.1,OP1.1] |
| 5.14.4.14. | [F01,F81-OS1.1,OP1.1] |
| 5.14.4.15. | [F01,F82-OS1.1,OP1.1] |
| 5.14.4.16. | [F81-OS1.1,OP1.1] |
| 5.14.4.17. | [F02-OS1.2,OP1.2] |
| Subsection 5.14.5. | Automobile Undercoating |
| 5.14.5.1. | Note1 |
| 5.14.5.2. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| 5.14.5.3. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F81-OS1.1,OP1.1] |
| 5.14.5.4. | Note1 |
| 5.14.5.5. | Note1 |
| 5.14.5.6. | [F02,F12-OS1.2,OP1.2] |
|
5.14.5.7. |
[F01,F82-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] |
| Subsection 5.14.6. | Dry Powder Finishing |
| 5.14.6.1. (1) | Note1 |
|
(2) |
[F01-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] |
| (3) | Note1 |
| (4) | Note1 |
| 5.14.6.2. | [F01-OS1.1,OP1.1] |
| 5.14.6.3. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| 5.14.6.4. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F81-OS1.1,OP1.1] |
| 5.14.6.5. | [F01-OS1.1,OP1.1] |
| 5.14.6.6. | [F01-OS1.1,OP1.1] |
|
5.14.6.7. |
Note1 Applies to the following text in the Fire Code: “shall not be released to the outside atmosphere”. [F01-OS1.1,OP1.1] |
| 5.14.6.8. | [F01-OS1.1,OP1.1] |
| 5.14.6.9. | [F01-OS1.1,OP1.1] |
| 5.14.6.10. | [F01,F82-OS1.1,OP1.1] |
| 5.14.6.11. (1) | Note1 |
| (2) | [F81-OS1.1,OP1.1] |
| Subsection 5.14.7. | Organic Peroxides and Dual Component Coatings |
| 5.14.7.1. | [F02,F03-OS1.2,OP1.2] |
| 5.14.7.2. | [F01-OS1.1,OP1.1] |
| 5.14.7.3. | [F01-OS1.1,OP1.1] |
| 5.14.7.4. | [F01-OS1.1,OP1.1] |
| 5.14.7.5. | [F01-OS1.1,OP1.1] |
| 5.14.7.6. | [F81-OS1.1,OP1.1] |
| New 5.14.8. | Floor Finishing (New subsection) |
| 5.14.8.1. | Note1 |
| 5.14.8.2. | Note1 |
| 5.14.8.3. | Note1 |
| 5.14.8.4. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
|
5.14.8.5. |
Note1 Applies to the following text in the Fire Code: “smoking and the use of open flames shall be prohibited during the application of flammable liquids and for at least 1 h after such application”. [F01-OS1.1,OP1.1] |
|
5.14.8.6. |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2] |
| SECTION 5.15 | RADIOACTIVE MATERIALS |
| Subsection 5.15.1. | Application |
| 5.15.1.1. | Note1 |
| Subsection 5.15.2. | Storage |
|
5.15.2.1. |
[F12-OS1.2,OP1.2] [F43-OS3.4,OH5] |
|
5.15.2.2. |
[F12-OS1.2,OP1.2] [F43-OS3.4,OH5] |
| 5.15.2.3. | Note1 |
| Subsection 5.15.3. | Emergency Procedures |
| 5.15.3.1. (1) | [F12-OS3.4] |
|
SECTION 5.16 |
FUMIGATION AND THERMAL INSECTICIDAL FOGGING |
| Subsection 5.16.1. | Application |
| 5.16.1.1. (1) | Note1 |
| (2) | Note1 |
| Subsection 5.16.2. | Safety Precautions |
|
5.16.2.1. (1) |
[F01-OS1.1,OP1.1] [F12-OS1.2,OP1.2] |
| 5.16.2.2. | [F11-OS1.5,OP3.1] |
| 5.16.2.3. | [F01-OS1.1,OP1.1] |
| 5.16.2.4. | [F01-OS1.1,OP1.1] |
| 5.16.2.5. | [F81-OS1.4,OP1.4] |
| 5.16.2.6. | [F12-OS1.2,OP1.2] |
| 5.16.2.7. (1) | [F34-OS1.1,OP1.1] |
| (2) | [F34,F81-OS1.1,OP1.1] |
| (3) | [F34-OS1.1,OP1.1] |
| SECTION 5.17 | WELDING AND CUTTING |
| Subsection 5.17.1. | General |
| 5.17.1.1. | [F01-OS1.1,OP1.1] |
| Subsection 5.17.2. | Use and Maintenance of Equipment |
| 5.17.2.1. | [F01,F81-OS1.1,OP1.1] |
| 5.17.2.2. | Note1 |
| 5.17.2.3. | Note1 |
| 5.17.2.4. | [F81-OS1.1,OP1.1] |
| 5.17.2.5. | Note1 |
| 5.17.2.6. (1) | [F82-OS1.1,OP1.1] |
| (2) | [F82-OS1.1,OP1.1] |
| (3) | [F81,F82-OS1.1,OP1.1] |
| 5.17.2.7. | [F01,F43-OS1.1,OP1.1] |
| 5.17.2.8. | [F01-OS1.1,OP1.1] |
| Subsection 5.17.3. | Prevention of Fires |
| 5.17.3.1. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
| 5.17.3.2. | [F81-OS1.1,OP1.1] |
| 5.17.3.3. (1) | [F01-OS1.1,OP1.1] |
| (2) | Note1 |
| (3) | [F12-OS1.2,OP1.2] |
|
SECTION 5.18 |
INDUSTRIAL OVENS FOR BAKING AND DRYING PROCESSES |
| Subsection 5.18.1. | Application |
| 5.18.1.1. | Note1 |
| Subsection 5.18.2. | Location |
|
5.18.2.1. |
[F01-OS1.1,OP1.1] [F12-OS1.2,OP1.2] |
| Subsection 5.18.3. | Construction |
| 5.18.3.1. |
[F02-OS1.2,OP1.2] Applies to the following text in the Fire Code: “with smooth interior surfaces to permit cleaning”. [F03-OS1.2,OP1.2] |
| 5.18.3.2. | [F01-OS1.1,OP1.1] |
| 5.18.3.3. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | Note1 |
| (4) | Note1 |
| 5.18.3.4. (1)(a) | [F03-OS1.2,OP1.2] |
| (b) | [F03-OS1.2,OP3.1] |
|
(c)(i) |
[F01-OS1.1,OP1.1] [F03-OS1.2,OP1.2] |
| (ii) | [F03-OS1.2,OP1.2] |
| Subsection 5.18.4. | Ventilation |
| 5.18.4.1. | [F01-OS1.1,OP1.1] |
| 5.18.4.2. (1) | [F01-OS1.1,OP1.1] |
|
5.18.4.3. (1) |
[F01-OS1.1,OP1.1] [F02,F03-OS1.2,OP1.2] |
| Subsection 5.18.5. | Maintenance |
| 5.18.5.1. (1) | [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| (2) | [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| (3) | [F82-OS1.1,OS1.2,OP1.1,OP1.2] |
| Subsection 5.18.6. | Fire Protection |
| 5.18.6.1. | Note1 |
| 5.18.6.2. | [F02-OS1.2,OP1.2] |
| 5.18.6.3. | [F02-OS1.2,OP1.2] |
| 5.18.6.4. | [F02-OS1.2,OP1.2] |
| Accceptable Solution | Objectives and Functional Statements |
|---|---|
| SECTION 6.1 | GENERAL |
| Subsection 6.1.1. | Scope |
| 6.1.1.1. | Note1 |
| SECTION 6.2 | PORTABLE EXTINGUISHERS |
| Subsection 6.2.1. | General |
| 6.2.1.1. | [F02,F12-OS1.2,OP1.2] |
| 6.2.1.2. | [F82-OS1.4,OP1.4] |
| 6.2.1.3. (1) | [F12-OS1.2,OP1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 6.2.1.4. | [F12-OS1.2,OS1.5,OP1.2] |
| 6.2.1.5. | [F12-OS1.2,OP1.2] |
| 6.2.1.6. | [F06,F12-OS1.2,OP1.2] |
| 6.2.1.7. | [F80-OS1.4,OP1.4] |
| 6.2.1.8. (1) | [F81-OS1.4,OP1.4] |
| 6.2.1.9. | [F20,F81-OS1.4,OP1.4] |
| Subsection 6.2.2. | Classification |
| 6.2.2.1. | [F02,F12-OS1.2,OP1.2] |
| Subsection 6.2.3. | Selection Requirements |
| 6.2.3.1. | [F02,F12-OS1.2,OP1.2] |
| Subsection 6.2.4. | Installation Requirements |
| 6.2.4.1. (1) | [F02,F12-OS1.2,OP1.2] |
| (2) | Note1 |
| (3) | Note1 |
|
6.2.4.2. |
[F12-OS1.2,OP1.2] [F30-OS3.1] |
|
6.2.4.3. |
[F12-OS1.2,OP1.2] [F30-OS3.1] |
| 6.2.4.4. | [F12-OS1.2,OP1.2] |
| Subsection 6.2.5. | Grading of Hazards |
| 6.2.5.1. | Note1 |
| 6.2.5.2. | Note1 |
| 6.2.5.3. | Note1 |
| Subsection 6.2.6. | Distribution |
| 6.2.6.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| 6.2.6.2. | [F02,F12-OS1.2,OP1.2] |
| 6.2.6.3. | [F02,F12-OS1.2,OP1.2] |
| 6.2.6.4. | [F02,F12-OS1.2,OP1.2] |
| 6.2.6.5. | [F02,F12-OS1.2,OP1.2] |
| 6.2.6.6. | Note1 |
| 6.2.6.7. | [F02,F12-OS1.2,OP1.2] |
| 6.2.6.8. (1) | Note1 |
| (2) | Note1 |
| 6.2.6.9. (1) | [F12-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| (3) | [F12-OS1.2,OP1.2] |
| 6.2.6.10. (1) | Note1 |
| (2) | Note1 |
| 6.2.6.11. | Note1 |
| 6.2.6.12. | [F02,F12-OS1.2,OP1.2] |
|
6.2.6.13. |
[F02,F12-OS1.2-OP1.2] [F32-OS3.3] |
| 6.2.6.14. | Note1 |
| 6.2.6.15. | Note1 |
| 6.2.6.16. (1) | [F02,F12-OS1.2,OP1.2] |
| (2) | [F12-OS1.2,OP1.2] |
| Subsection 6.2.7. | Inspection, Testing and Maintenance |
| 6.2.7.1. (1) | [F82-OS1.4,OP1.4] |
| (2) | Note1 |
| 6.2.7.2. | [F82-OS1.4,OP1.4] |
| 6.2.7.3. | [F82-OS1.4,OP1.4] |
| 6.2.7.4. (1) | [F82-OS1.4,OP1.4] |
| (2) | Note1 |
| 6.2.7.5. | [F82-OS1.4,OP1.4] |
| 6.2.7.6. | [F82-OS1.4,OP1.4] |
| 6.2.7.7. | [F82-OS1.4,OP1.4] |
| 6.2.7.8. | [F82-OS1.4,OP1.4] |
| 6.2.7.9. (1) | [F82-OS1.4,OP1.4] |
| (2) | Note1 |
|
SECTION 6.3 |
FIRE ALARM AND VOICE COMMUNICATION SYSTEMS FOR LIFE SAFETY |
| Subsection 6.3.1. | General |
| 6.3.1.1. | [F82-OS1.4] |
| 6.3.1.2. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | [F82-OS1.4] |
| (5) | [F82-OS1.4] |
| 6.3.1.3. | Note1 |
| 6.3.1.4. | [F82-OS1.4] |
| 6.3.1.5. (1) | [F11,F81-OS1.5] |
| (2) | Note1 |
| 6.3.1.6. | [F81-OS1.4,OP1.4] |
| 6.3.1.7. (1) | Note1 |
| (2) | Note1 |
| 6.3.1.8. |
[F11-OS1.5] [F13-OS1.2,OP1.2] [F82-OS1.4,OP1.4] |
| Subsection 6.3.2. | Check, Inspect and Test |
| 6.3.2.1. (1) | Note1 |
| 6.3.2.2. (1) | [F82-OS1.4] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| 6.3.2.3. | [F82-OS1.4,OP1.4] |
| 6.3.2.4. | [F82-OS1.4,OP1.4] |
| 6.3.2.5. (1) | Note1 |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | [F82-OS1.4,OP1.4] |
| (4) | Note1 |
| 6.3.2.6. (1) | Note1 |
| (2) | [F82-OS1.4] |
| (3) | [F82-OS1.4] |
| (4) | [F82-OS1.4] |
| (5) | [F82-OS1.4] |
| (6) | Note1 |
| (7) | Note1 |
| Subsection 6.3.3. | Smoke Alarms – Testing and Maintenance |
| 6.3.3.1. (1) | Note1 |
| (2) | Note1 |
| 6.3.3.2. (1) | [F82-OS1.4] |
| (2) | Note1 |
| (3) | Note1 |
| 6.3.3.3. (1) | [F82-OS1.4] |
| (2) | Note1 |
| 6.3.3.4. | [F81-OS1.4] |
| 6.3.3.5. (1) | [F11-OS1.5] |
| SECTION 6.4 | STANDPIPE AND HOSE SYSTEMS |
| Subsection 6.4.1. | General |
| 6.4.1.1. | [F02,F12-OS1.2,OP1.2] |
| 6.4.1.2. | [F82-OS1.4,OP1.4] |
| 6.4.1.3. (1) | [F81-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | [F81,F82-OS1.4,OP1.4] |
| 6.4.1.4. | Note1 |
| 6.4.1.5. | Note1 |
| 6.4.1.6. | Note1 |
|
Subsection 6.4.2. |
Maintenance and Inspection of Hose Stations and Equipment |
| 6.4.2.1. | [F82-OS1.4,OP1.4] |
| 6.4.2.2. | [F81-OS1.4,OP1.4] |
| 6.4.2.3. |
[F12-OS1.2,OP1.2] [F81-OS1.4,OP1.4] |
| 6.4.2.4. | [F82-OS1.4,OP1.4] |
| 6.4.2.5. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| 6.4.2.6. (1) | [F12,F81-OS1.4,OP1.4] |
| (2) | [F12,F81-OS1.4,OP1.4] |
| 6.4.2.7. (1) | Note1 |
| (2) | Note1 |
| Subsection 6.4.3. | Testing |
| 6.4.3.1. (1) | Note1 |
| (2) | Note1 |
| 6.4.3.2. | [F82-OS1.4,OP1.4] |
| 6.4.3.3. | [F82-OS1.4,OP1.4] |
| 6.4.3.4. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| 6.4.3.5. | [F82-OS1.4,OP1.4] |
| 6.4.3.6. | [F82-OS1.4,OP1.4] |
| 6.4.3.7. | [F82-OS1.4,OP1.4] |
| SECTION 6.5 | SPRINKLER SYSTEMS |
| Subsection 6.5.1. | General |
| 6.5.1.1. (1) | [F02-OS1.2,OP1.2] |
| (2) | Note1 |
| 6.5.1.2. | [F82-OS1.4,OP1.4] |
| 6.5.1.3. (1) | [F81-OS1.4,OP1.4] |
| 6.5.1.4. | [F81-OS1.4,OP1.4] |
| 6.5.1.5. (1) | [F02-OS1.2,OP1.2] |
| (2) | [F02-OS1.2,OP1.2] |
| 6.5.1.6. (1) | Note1 |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | [F81-OS1.4,OP1.4] |
| (4) | Note1 |
| (5) | [F82-OS1.4,OP1.4] |
| (6) | [F82-OS1.4,OP1.4] |
| (7) | [F82-OS1.4,OP1.4] |
| (8) | [F82-OS1.4,OP1.4] |
| 6.5.1.7. (1) | [F82-OS1.4,OP1.4] |
| (2) | Note1 |
| 6.5.1.8. (1) | Note1 |
| (2) | Note1 |
| Subsection 6.5.2. | Sprinkler System Shutdowns |
| 6.5.2.1. | Note1 |
| 6.5.2.2. (1) | Note1 |
| (2) | Note1 |
| 6.5.2.3. | [F81-OS1.4,OP1.4] |
| 6.5.2.4. | Note1 |
| 6.5.2.5. | [F12,F81-OS1.4,OP1.4] |
| 6.5.2.6. | [F12,F81-OS1.4,OP1.4] |
| Subsection 6.5.3. | Checking |
| 6.5.3.1. (1) |
[F81-OS1.4,OP1.4] Applies to the following text in the Fire Code: “valves controlling sprinkler water supplies or alarms shall be sealed in the open position”.
[F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | [F82-OS1.4,OP1.4] |
| 6.5.3.2. | [F82-OS1.4,OP1.4] |
| 6.5.3.3. | [F82-OS1.4,OP1.4] |
| 6.5.3.4. | [F82-OS1.4,OP1.4] |
| 6.5.3.5. | [F82-OS1.4,OP1.4] |
| Subsection 6.5.4. | Inspection |
| 6.5.4.1. | [F82-OS1.4,OP1.4] |
| 6.5.4.2. | [F82-OS1.4,OP1.4] |
| 6.5.4.3. | [F82-OS1.4,OP1.4] |
| 6.5.4.4. (1) | [F81-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | [F81,F82-OS1.4,OP1.4] |
| Subsection 6.5.4. | Testing |
| 6.5.5.1. | [F11,F12-OS1.5] |
| 6.5.5.2. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F81,F82-OS1.4,OP1.4] |
| 6.5.5.3. | [F82-OS1.4,OP1.4] |
| 6.5.5.4. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | Note1 |
| (4) | [F82-OS1.4,OP1.4] |
| (5) | [F82-OS1.4,OP1.4] |
| 6.5.5.5. | [F82-OS1.4,OP1.4] |
| 6.5.5.6. | [F82-OS1.4,OP1.4] |
| 6.5.5.7. (1) | Note1 |
| (2) | Note1 |
| (3) | [F82-OS1.4,OP1.4] |
| Subsection 6.5.6. | Maintenance |
| 6.5.6.1. | [F81-OS1.4,OP1.4] |
| 6.5.6.2. |
[F12-OS1.2,OP1.2] [F82-OS1.4,OP1.4] |
| 6.5.6.3. |
[F12-OS1.2,OP1.2] [F51,F82-OS1.4,OP1.4] |
| 6.5.6.4. (1) | [F81-OS1.4,OP1.4] |
| (2) | Note1 |
| 6.5.6.5. (1) | Note1 |
| (2) | [F81,F82-OS1.4,OP1.4] |
| (3) | [F82-OS1.4,OP1.4] |
| (4) | [F81-OS1.4,OP1.4] |
| (5) | [F82-OS1.4,OP1.4] |
| 6.5.6.6. | [F82-OS1.4,OP1.4] |
| SECTION 6.6 | WATER SUPPLIES FOR FIRE PROTECTION |
| Subsection 6.6.1. | General |
| 6.6.1.1. | [F82-OS1.4,OP1.4] |
| 6.6.1.2. (1) |
[F81-OS1.4,OP1.4] Applies to the following text in the Fire Code: “valves controlling water supplies used exclusively for fire protection systems shall be sealed in the open position”. [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | [F82-OS1.4,OP1.4] |
| 6.6.1.3. | [F81-OS1.4,OP1.4] |
| 6.6.1.4. | [F81-OS1.4,OP1.4] |
| 6.6.1.5. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| Subsection 6.6.2. | Tanks |
| 6.6.2.1. | [F82-OS1.4,OP1.4] |
| 6.6.2.2. | [F82-OS1.4,OP1.4] |
| 6.6.2.3. | [F81,F82-OS1.4,OP1.4] |
| 6.6.2.4. | [F81,F82-OS1.4,OP1.4] |
| 6.6.2.5. | [F82-OS1.4,OP1.4] |
| 6.6.2.6. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| 6.6.2.7. | [F82-OS1.4,OP1.4] |
| 6.6.2.8. | [F82-OS1.4,OP1.4] |
| 6.6.2.9. | [F82-OS1.4,OP1.4] |
| 6.6.2.10. | [F04,F20,F81,F82-OS1.4,OP1.4] |
| 6.6.2.11. | [F82-OS1.4,OP1.4] |
| 6.6.2.12. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| 6.6.2.13. | [F82-OS1.4,OP1.4] |
| Subsection 6.6.3. | [F82-OS1.4,OP1.4] |
| 6.6.3.1. | [F82-OS1.4,OP1.4] |
| 6.6.3.2. | [F82-OS1.4,OP1.4] |
| 6.6.3.3. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| 6.6.3.4. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| 6.6.3.5. | [F82-OS1.4,OP1.4] |
| 6.6.3.6. | Note1 |
| Subsection 6.6.4. | Hydrants |
| 6.6.4.1. | [F82-OS1.4,OP1.4] |
| 6.6.4.2. | [F82-OS1.4,OP1.4] |
| 6.6.4.3. | [F82-OS1.4,OP1.4] |
| Subsection 6.6.5. | Inspection of Hydrants |
| 6.6.5.1. | [F82-OS1.4,OP1.4] |
| 6.6.5.2. (1) | [F81-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | [F81,F82-OS1.4,OP1.4] |
| 6.6.5.3. | [F81,F82-OS1.4,OP1.4] |
| 6.6.5.4. | [F82-OS1.4,OP1.4] |
| 6.6.5.5. | Note1 |
| 6.6.5.6. | [F82-OS1.4,OP1.4] |
| 6.6.5.7. | [F82-OS1.4,OP1.4] |
| 6.6.5.8. | Note1 |
| Subsection 6.6.6. | Uniform Marking of Hydrants |
| 6.6.6.1. | [F12-OS1.2,OP1.2] |
| SECTION 6.7 | EMERGENCY POWER SYSTEMS |
| Subsection 6.7.1. | General |
| 6.7.1.1. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | Note1 |
| 6.7.1.2. | [F12,F81-OS1.4,OP1.4] |
| 6.7.1.3. | Note1 |
| 6.7.1.4. | [F82-OS1.4,OP1.4] |
| 6.7.1.5. (1) | [F82-OS1.4,OP1.4] |
| (2) | Note1 |
| SECTION 6.8 | SPECIAL FIRE SUPPRESSION SYSTEMS |
| Subsection 6.8.1. | Installation |
| 6.8.1.1. (1) | Note1 |
| (2) | Note1 |
| (3) | [F02,F81-OS1.2,OP1.2] |
| (4) | [F02,F81-OS1.2,OP1.2] |
| (5) | [F02,F81-OS1.2,OP1.2] |
| (6) | [F02,F81-OS1.2,OP1.2] |
| (7) | [F12,F82-OS1.4,OP1.4] |
| (8) | [F12-OS1.4,OP1.4] |
| Subsection 6.8.2. | Inspection and Maintenance |
| 6.8.2.1. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | Note1 |
| 6.8.2.2. | Note1 |
| 6.8.2.3. | [F82-OS1.4,OP1.4] |
| 6.8.2.4. | [F82-OS1.4,OP1.4] |
| 6.8.2.5. | [F20,F82-OS1.4,OP1.4] |
| 6.8.2.6. | [F81-OS1.4,OP1.4] |
| Accceptable Solution | Objectives and Functional Statements |
|---|---|
| SECTION 7.1 | GENERAL |
| Subsection 7.1.1. | General |
| 7.1.1.1. | Note1 |
| 7.1.1.2. | Note1 |
| 7.1.1.3. (1) | Note1 |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | [F82-OS1.4,OP1.4] |
| (4) | [F82-OS1.4,OP1.4] |
| (5) | [F82-OS1.4,OP1.4] |
| (6) | [F82-OS1.4,OP1.4] |
| SECTION 7.2 | INSPECTION, TESTING AND MAINTENANCE |
| Subsection 7.2.1. | Intervals Between Tests |
| 7.2.1.1. | [F82-OS1.4,OP1.4] |
| 7.2.1.2. | [F82-OS1.4,OP1.4] |
| Subsection 7.2.2. | Elevators |
| 7.2.2.1. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | [F82-OS1.4,OP1.4] |
| Subsection 7.2.3. | Venting to Aid Fire Fighting |
| 7.2.3.1. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | [F82-OS1.4,OP1.4] |
| (4) | [F82-OS1.4,OP1.4] |
|
Subsection 7.2.4. |
Central Alarm and Control Facilities and Voice Communication Systems for Life Safety |
| 7.2.4.1. | Note1 |
|
SECTION 7.3 |
INSPECTION AND TESTS FOR SMOKE CONTROL EQUIPMENT |
| Subsection 7.3.1. | General |
| 7.3.1.1. | [F82-OS1.4,OP1.4] |
| 7.3.1.2. | [F82-OS1.4,OP1.4] |
| 7.3.1.3. (1) | [F82-OS1.4,OP1.4] |
| (2) | [F82-OS1.4,OP1.4] |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| Accceptable Solution | Objectives and Functional Statements |
|---|---|
| SECTION 8.1 | GENERAL |
| Subsection 8.1.1. | Application |
| 8.1.1.1. | Note1 |
| Subsection 8.1.2. | Requirements |
| 8.1.2.1. |
[F01-OS1.1,OP1.1] [F02-OS1.2,OP1.2,OP3.1] |
| 8.1.2.2. (1) |
[F11-OS1.5] [F13-OS1.2,OP1.2] Applies to the following text in the Fire Code: “During periods when demolition operations will create a fire hazard to __ partially occupied spaces, a firewatch shall be provided.” [F13-OP3.1] Applies to the following text in the Fire Code: “During periods when demolition operations will create a fire hazard to neighbouring properties __ a firewatch shall be provided.” |
|
(2) |
[F11-OS1.5] [F13-OS1.2,OP1.2,OP3.1] |
| (3) | [F12-OS1.2,OS1.5,OP1.2,OP3.1] |
|
(4) |
[F11-OS1.5] [F13-OS1.2,OP1.2,OP3.1] |
| (5) |
[F01-OS1.1,OP1.1,OP3.1] [F11-OS1.5] [F12-OS1.5,OP1.2] [F13-OS1.2,OS1.5,OP1.2,OP3.1] [F82-OS1.4,OP1.4,OP3.1] |
| 8.1.2.3. (1) | [F01-OS1.1,OP1.1,OP3.1] |
|
(2) |
[F02-OS1.2,OS1.5,OP3.1] [F03-OP1.2] |
| 8.1.2.4. | [F01-OP3.1] |
| 8.1.2.5. | Note1 |
| 8.1.2.6. (1) | [F12-OS1.2,OP1.2,OP3.1] |
| (2) | [F12-OS1.2,OP1.2,OP3.1] |
| (3) | [F12-OS1.2,OP1.2,OP3.1] |
| (4) | [F12-OS1.2,OP1.2,OP3.1] |
|
(5) |
[F12-OS1.2,OP1.2,OP3.1] [F82-OS1.4,OP1.4,OP3.1] |
| 8.1.2.7. (1) | Note1 |
| (2) | [F12-OS1.2,OP1.2] |
| (3) | [F12-OS1.2,OS1.5,OP1.2] |
| (4) | [F12-OS1.2,OP1.2] |
| 8.1.2.8. (1) | Note1 |
| (2) | [F12-OS1.2,OP1.2] |
| (3) | [F02-OS1.2,OP1.2] |
| (4) | Note1 |
| 8.1.2.9. | Note1 |
| 8.1.2.10. (1) | [F01-OS1.1,OP1.1] |
| (2) | [F01-OS1.1,OP1.1] |
| (3) | [F01-OS1.1,OP1.1] |
| 8.1.2.11. | [F01-OS1.1,OP1.1] |
| 8.1.2.12. | [F10-OS1.5] |
| 8.1.2.13. (1) | [F11-OS1.5] |
| (2) | [F11-OS1.5] |
| Accceptable Solution | Objectives and Functional Statements |
|---|---|
| SECTION 9.1 | GENERAL |
| Subsection 9.1.1. | General |
| 9.1.1.1. | Note1 |
| 9.1.1.2. (1) | Note1 |
| 9.1.1.3. | Note1 |
| Subsection 9.1.2. | Application |
| 9.1.2.1. (1) | Note1 |
| (2) | Note1 |
| 9.1.2.2. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| Subsection 9.1.3. | Schedule of Compliance |
| 9.1.3.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| 9.1.3.2. | Note1 |
| Subsection 9.1.4. | Life Safety Study |
| 9.1.4.1. (1) | Note1 |
| 9.1.4.2. (1) | Note1 |
| 9.1.4.3. | Note1 |
| 9.1.4.4. | Note1 |
| 9.1.4.5. | Note1 |
| 9.1.4.6. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| (7) | Note1 |
| (8) | Note1 |
| 9.1.4.7. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| (7) | Note1 |
| 9.1.4.8. | Note1 |
| SECTION 9.2 | ASSEMBLY OCCUPANCIES |
| Subsection 9.2.1. | Application |
| 9.2.1.1. (1) | Note1 |
| (2) | Note1 |
| 9.2.1.2. | Note1 |
| 9.2.1.3. | Note1 |
| Subsection 9.3.1. | Containment |
| 9.2.2.1. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.2.2.2. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 9.2.2.3. (1) | [F03-OS1.2] |
| (2) | [F03-OS1.2] |
| (3) | Note1 |
| (4) | [F03-OS1.2] |
| (5) | Note1 |
| 9.2.2.4. (1) | [F02-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| Subsection 9.2.3. | Means of Egress |
| 9.2.3.1. | Note1 |
| 9.2.3.2. (1) | [F10-OS1.5] |
| (2) | Note1 |
| 9.2.3.3. (1) | [F10-OS1.5] |
| (2) | Note1 |
| 9.2.3.4. (1) | [F10-OS1.5] |
| (2) | Note1 |
| 9.2.3.5. | [F10-OS1.5] |
| 9.2.3.6. (1) | [F10-OS1.5] |
| 9.2.3.7. (1) | [F10-OS1.5] |
| 9.2.3.8. | [F10-OS1.5] |
| 9.2.3.9. | Note1 |
| 9.2.3.10. | [F10-OS1.5] |
|
9.2.3.11. (1) |
[F03-OS1.2] [F05,F10,F20,F30-OS1.5] |
| (2) | Note1 |
| 9.2.3.12. | [F10,F30-OS1.5] |
| 9.2.3.13. (1) | [F10-OS1.5] |
| (2) | Note1 |
| 9.2.3.14. | [F10-OS1.5] |
| 9.2.3.15. (1) |
[F03-OS1.2] [F05-OS1.5] |
|
(2) |
[F03-OS1.2] [F05-OS1.5] |
| (3) | Note1 |
| (4) | Note1 |
|
9.2.3.16. (1) |
[F03-OS1.2] [F05,F10-OS1.5] |
| (2) | Note1 |
|
9.2.3.17. (1) |
[F02,F03-OS1.2] [F05-OS1.5] |
|
(2) |
[F03-OS1.2] [F05-OS1.5] |
| (3) | Note1 |
| 9.2.3.18. (1) | [F05-OS1.5] |
| (2) | [F05-OS1.5] |
| (3) | Note1 |
| Subsection 9.2.4. | Fire Alarm and Detection |
| 9.2.4.1. (1) | [F11-OS1.5] |
| (2) | Note1 |
| Subsection 9.2.5. | Suppression |
| 9.2.5.1. (1) | [F12-OS1.2,OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| 9.2.5.2. (1) | [F02-OS1.2] |
| (2) | Note1 |
| (3) | [F02-OS1.2] |
| (4) | [F02-OS1.2] |
| (5) | Note1 |
| (6) | [F02-OS1.2] |
| SECTION 9.3 | BOARDING, LODGING AND ROOMING HOUSES |
| Subsection 9.3.1. | Application |
| 9.3.1.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| 9.3.1.2. | Note1 |
| 9.3.1.3. | Note1 |
| Subsection 9.3.2. | Containment |
| 9.3.2.1. | [F03-OS1.2] |
| 9.3.2.2. (1)(a) | [F03-OS1.2] |
| (b) | [F03-OS1.5] |
| (2) | Note1 |
| 9.3.2.3. | Note1 |
| 9.3.2.4. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.3.2.5. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | [F03-OS1.2] |
| (4) | [F03-OS1.2] |
| (5) | Note1 |
| (6) | [F03-OS1.2] |
| (7) | Note1 |
| 9.3.2.6. | [F81-OH1.1] |
| Subsection 9.3.3. | Means of Egress |
| 9.3.3.1. (1) | [F10-OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| 9.3.3.2. (1) | [F10-OS1.5] |
| (2) | [F05-OS1.5] |
| (3) | [F05-OS1.5] |
| (4) | [F05-OS1.5] |
| (5) | Note1 |
| 9.3.3.3. | Note1 |
|
9.3.3.4. (1) |
[F03-OS1.2] [F10,F20,F30-OS1.5] |
| (2) | Note1 |
| (3) | [F10-OS1.5] |
|
9.3.3.5. (1) |
[F03-OS1.2] [F05-OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| 9.3.3.6. (1) | [F03-OS1.2] |
| (2) | [F03-OS1.2] |
| 9.3.3.7. | Note1 |
| 9.3.3.8. (1) | [F03-OS1.2] |
| (2) | [F03-OS1.2] |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| 9.3.3.9. | Note1 |
| 9.3.3.10. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
|
9.3.3.11. |
[F02-OS1.2] [F10-OS1.5] |
| 9.3.3.12. | [F10,F30-OS1.5] |
| 9.3.3.13. | [F10-OS1.5] |
| Subsection 9.3.4. | Fire Alarm and Detection |
| 9.3.4.1. (1) | [F11-OS1.5] |
| (2) | [F11-OS1.5] |
| 9.3.4.2. (1) | [F11-OS1.5] |
| 9.3.4.3. | Note1 |
| 9.3.4.4. | Note1 |
| Subsection 9.3.5. | Suppression |
| 9.3.5.1. (1) | [F02-OS1.2] |
| (2) | [F02-OS1.2] |
| SECTION 9.4 | HEALTH CARE FACILITIES |
| Subsection 9.4.1. | Application |
| 9.4.1.1. (1) | Note1 |
| (2) | Note1 |
| Subsection 9.4.2. | Containment |
| 9.4.2.1. (1) | Note1 |
| (2) | [F03-OS1.2] |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | [F03-OS1.2] |
| 9.4.2.2. (1) | Note1 |
|
(2) |
[F03-OS1.2] [F04-OS1.3] |
| (3) | Note1 |
| 9.4.2.3. (1) | Note1 |
|
(2) |
[F03-OS1.2] [F04-OS1.3] |
| (3) | [F10-OS1.5] |
| (4) | Note1 |
|
9.4.2.4. (1)(a) |
[F03-OS1.2] [F04-OS1.3] |
| (b) | [F02-OS1.2] |
| (2) | Note1 |
| 9.4.2.5. (1) | [F03-OS1.2] |
| (2) | [F02,F03,F11-OS1.2] |
| (3) | Note1 |
| 9.4.2.6. (1) | [F03-OS1.2] |
| (2) | [F05-OS1.5] |
| (3) | Note1 |
| (4) | Note1 |
|
9.4.2.7. (1) |
[F03-OS1.2,OS1.5] [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | Note1 |
| 9.4.2.8. (1) | [F03-OS1.2] |
| (2) | [F03-OS1.2] |
| (3) | Note1 |
| (4) | Note1 |
| (5) | [F03-OS1.2] |
| (6) | Note1 |
| 9.4.2.9. | [F03-OS1.2] |
| 9.4.2.10. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | [F03-OS1.2] |
| 9.4.2.11. | [F81-OH1.1] |
| 9.4.2.12. | [F03-OS1.2] |
| 9.4.2.13. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.4.2.14. (1) | [F02,F03-OS1.2] |
| (2) | Note1 |
| (3) | [F03-OS1.2] |
| 9.4.2.15. | [F03-OS1.2] |
| Subsection 9.4.3. | Means of Egress |
| 9.4.3.1. (1) | [F10-OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| 9.4.3.2. | [F10,F12-OS1.5] |
|
9.4.3.3. (1) |
[F03-OS1.2] [F05-OS1.5] |
| (2) | Note1 |
| 9.4.3.4. (1) | [F10-OS1.5] |
| (2) | Note1 |
| 9.4.3.5. (1) | [F10-OS1.5] |
| (2) | Note1 |
| 9.4.3.6. (1) | [F10-OS1.5] |
|
(2) |
[F03-OS1.2] [F05,F10,F20,F30-OS1.5] |
| (3) | Note1 |
| 9.4.3.7. | [F10-OS1.5] |
| Subsection 9.4.4. | Fire Alarm and Detection |
| 9.4.4.1. | [F11-OS1.5] |
| 9.4.4.2. (1) | [F11,F13-OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| 9.4.4.3. (1) | [F13-OS1.5,OS1.2] |
| (2) | Note1 |
|
9.4.4.4. (1) |
[F03-OS1.2] [F10-OS1.5] |
|
(2) |
[F03-OS1.2] [F10-OS1.5] |
| Subsection 9.4.5. | Fire Suppression |
| 9.4.5.1. (1) | [F12-OS1.2,OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| 9.4.5.2. (1) | [F02,F03-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
|
9.4.5.3. (1) |
[F10-OS1.5] [F12-OS1.2] |
| (2) | Note1 |
| 9.4.5.4. (1) | [F11-OS1.5] |
| (2) | Note1 |
| SECTION 9.5 | BUILDINGS UP TO AND INCLUDING 6 STOREYS IN BUILDING HEIGHT WITH RESIDENTIAL OCCUPANCIES |
| Subsection 9.5.1. | Application |
| 9.5.1.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| 9.5.1.2. | Note1 |
| 9.5.1.3. | Note1 |
| Subsection 9.5.2. | Containment |
| 9.5.2.1. (1) | Note1 |
| (2) | [F03-OS1.2] |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | [F03-OS1.2] |
| (7) | Note1 |
| 9.5.2.2. (1) | Note1 |
|
(2) |
[F03-OS1.2] [F04-OS1.3] |
| (3) | Note1 |
| (4) | Note1 |
| 9.5.2.3. (1) | Note1 |
| 9.5.2.4. (1) | Note1 |
|
(2) |
[F03-OS1.2] [F04-OS1.3] |
| (3) | [F11-OS1.5] |
| (4) | Note1 |
|
9.5.2.5. (1)(a) |
[F03-OS1.2] [F04-OS1.3] |
| (b) | [F02-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 9.5.2.6. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 9.5.2.7. (1) | [F03-OS1.2] |
|
(2) |
[F03-OS1.2] [F05-OS1.5] |
| (3) | Note1 |
| 9.5.2.8. (4) | [F03-OS1.2] |
| (2) | [F03-OS1.2] |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| (7) | [F03-OS1.2] |
| (8) | Note1 |
| 9.5.2.9. (1)(a) | [F03-OS1.2] |
| (b)(i) | [F02-OS1.2] |
|
(ii) |
[F03-OS1.2] [F11-OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| 9.5.2.10. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 9.5.2.11. | [F81-OH1.1] |
| 9.5.2.12. (1) | [F03-OS1.2] |
| (2) | [F02-OS1.2] |
| 9.5.2.13. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.5.2.14. (1) | [F03-OS1.2] |
| (2) | [F02,F03-OS1.2] |
| (3) | Note1 |
| (4) | Note1 |
| 9.5.2.15. | [F03-OS1.2] |
| Subsection 9.5.3. | Means of Egress |
| 9.5.3.1. (1) | [F10-OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| 9.5.3.2. (1) | [F10-OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
|
9.5.3.3. (1) |
[F03-OS1.2] [F05-OS1.5] |
| (2) | Note1 |
|
(3) |
[F03-OS1.2] [F05-OS1.5] |
| 9.5.3.4. | [F10-OS1.5] |
| 9.5.3.5. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | [F10-OS1.5] |
|
9.5.3.6. (1) |
[F02-OS1.2] [F10-OS1.5] |
| (2) | Note1 |
|
9.5.3.7. (1) |
[F03-OS1.2] [F10,F20,F30-OS1.5] |
| (2) | [F05-OS1.5] |
| (3) | [F05-OS1.5] |
| (4) | [F05-OS1.5] |
| (5) | Note1 |
| 9.5.3.8. | [F10-OS1.5] |
| 9.5.3.9. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | [F10-OS1.5] |
| Subsection 9.5.4. | Fire Alarm and Detection |
| 9.5.4.1. (1) | [F11-OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| 9.5.4.2. (1) | Note1 |
| 9.5.4.3. (1) | [F11-OS1.5] |
| (2) | [F11-OS1.5] |
| (3) | Note1 |
| 9.5.4.4. (1) | [F11-OS1.5] |
| 9.5.4.5. (1) | [F11-OS1.5] |
| (2) | Note1 |
| (3) | [F81-OS1.4] |
| (4) | Note1 |
| 9.5.4.6. | Note1 |
| Subsection 9.5.5. | Suppression |
| 9.5.5.1. (1) | [F12-OS1.2,OS1.5] |
| (2) | Note1 |
| 9.5.5.2. (1) | [F02,F12-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 9.5.5.3. (1) | [F02-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
|
SECTION 9.6 |
BUILDINGS HIGHER THAN 6 STOREYS IN BUILDING HEIGHT WITH RESIDENTIAL OCCUPANCIES |
| Subsection 9.6.1. | Application |
| 9.6.1.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| 9.6.1.2. | Note1 |
| 9.6.1.3. | Note1 |
| Subsection 9.6.2. | Containment |
| 9.6.2.1. (1) | Note1 |
| (2) | [F03-OS1.2] |
| (3) | Note1 |
| (4) | Note1 |
| 9.6.2.2. (1) | [F03-OS1.2] |
| (2) |
[F03-OS1.2] [F04-OS1.3] |
| (3) | Note1 |
| 9.6.2.3. (1) | [F02-OS1.2] |
| (2) | Note1 |
| 9.6.2.4. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.6.2.5. (1) | [F03-OS1.2] |
|
(2) |
[F03-OS1.2] [F05-OS1.5] |
| (3) | Note1 |
| (4) | Note1 |
| 9.6.2.6. (1) | [F03-OS1.2] |
| (2) | [F03-OS1.2] |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| (7) | Note1 |
| (8) | [F03-OS1.2] |
| (9) | Note1 |
| 9.6.2.7. (1)(a) | [F03-OS1.2] |
| (b) | [F02-OS1.2] |
| (2) | Note1 |
| 9.6.2.8. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.6.2.8. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.6.2.9. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.6.2.10. | [F81-OH1.1] |
| 9.6.2.11. (1) | [F02,F03-OS1.2] |
| 9.6.2.12. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.6.2.13. (1) | [F03-OS1.2] |
| (2) | [F02-OS1.2] |
| (3) | Note1 |
|
9.6.2.14. |
[F03-OS1.2] [F11-OS1.5] |
| 9.6.2.15. (1) | [F03-OS1.2] |
| (2) | [F02-OS1.2] |
| (3) | Note1 |
| 9.6.2.16. (1) | [F03-OS1.2,OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| Subsection 9.6.3. | Means of Egress |
| 9.6.3.1. (1) | [F10-OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| 9.6.3.2. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| 9.6.3.3. (1) | [F10-OS1.5] |
|
9.6.3.4. (1) |
[F03-OS1.2] [F05-OS1.5] |
| (2) | Note1 |
| 9.6.3.5. | [F10-OS1.5] |
| 9.6.3.6. (1) | [F10-OS1.5] |
| (2) | [F10,F12-OS1.5] |
|
9.6.3.7. (1) |
[F02-OS1.2] [F10-OS1.5] |
| (2) | Note1 |
| 9.6.3.8. | [F10-OS1.5] |
| 9.6.3.9. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | [F10-OS1.5] |
| Subsection 9.6.4. | Fire Alarm and Detection |
| 9.6.4.1. (1) | [F11,F13-OS1.5] |
| (2) | Note1 |
| 9.6.4.2. (1) | [F11-OS1.5] |
| (2) | [F11-OS1.5] |
| (3) | Note1 |
| 9.6.4.3. | [F11-OS1.5] |
| 9.6.4.4. (1) | [F81-OS1.4] |
| (2) | Note1 |
| 9.6.4.5. (1) | [F12-OS1.5] |
| (2) | Note1 |
| 9.6.4.6. | [F13-OS1.5] |
| 9.6.4.7. (1) | [F11,F12-OS1.5] |
| (2) | [F11,F12-OS1.5] |
| (3) | Note1 |
| 9.6.4.8. | [F11,F13-OS1.5] |
| 9.6.4.9. | [F03-OS1.2] |
| 9.6.4.10. (1) | [F11-OS1.5] |
| (2) | Note1 |
| (3) | [F81-OS1.4] |
| (4) | Note1 |
| Subsection 9.6.5. | Suppression |
| 9.6.5.1. (1) | [F12-OS1.5] |
| (2) | Note1 |
| 9.6.5.2. (1) | [F02,F12-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | [F02,F12-OS1.2] |
| 9.6.5.3. (1) | [F12-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 9.6.5.4. (1) | [F12-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 9.6.5.5. (1) | [F02-OS1.2,OS1.4] |
| (2) | Note1 |
| 9.6.5.6. (1) | [F12-OS1.2,OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| 9.6.5.7. (1) | [F81-OS1.4] |
| (2) | Note1 |
| SECTION 9.7 | RESERVED |
| SECTION 9.8 | TWO UNIT RESIDENTIAL OCCUPANCIES |
| Subsection 9.8.1. | Application |
| 9.8.1.1. (1) | Note1 |
| (2) | Note1 |
| Subsection 9.8.2. | Containment |
| 9.8.2.1. (1) | [F03-OS1.2] |
| (2) | [F03-OS1.2] |
| (3) | Note1 |
| (4) | Note1 |
| 9.8.2.2. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 9.8.2.3. | Note1 |
| 9.8.2.4. | [F81-OH1.1] |
| 9.8.2.5. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| Subsection 9.8.3. | Means of Egress |
| 9.8.3.1. | Note1 |
| 9.8.3.2. (1) | [F10-OS1.5] |
| 9.8.3.3. (1) | [F10-OS1.5] |
| (2) | [F11-OS1.5] |
| 9.8.3.4. (1)(a) | [F10-OS1.5] |
| (b) | [F10,F11-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | [F10-OS1.5] |
| 9.8.3.5. | Note1 |
| Subsection 9.8.4. | Fire Alarm and Detection |
| 9.8.4.1. (1) | [F11-OS1.5] |
|
(2) |
[F11-OS1.5] [F81-OS1.4] |
|
9.8.4.2. (1) |
[F11-OS1.5] [F81-OS1.4] |
| (2) | Note1 |
| (3) | [F81-OS1.4] |
| (4) | Note1 |
| (5) | Note1 |
| Subsection 9.8.5. | Suppression |
|
9.8.5.1. |
[F02-OS1.2] [F81-OS1.4] |
| Subsection 9.8.6. | Electrical |
| 9.8.6.1. (1) | [F01-OS1.1] |
| (2) | [F82-OS1.1] |
| (3) | Note1 |
| SECTION 9.9 | HOTELS |
| Subsection 9.9.1. | Application |
| 9.9.1.1. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| (7) | Note1 |
| 9.9.1.2. (1) | Note1 |
| (2) | Note1 |
| Subsection 9.9.2. | Containment |
| 9.9.2.1. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | [F03-OS1.2] |
| (7) | Note1 |
| (8) | Note1 |
| 9.9.2.2. (1) | Note1 |
|
(2) |
[F03-OS1.2] [F04-OS1.3] |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| 9.9.2.3. (1) | Note1 |
|
(2) |
[F03-OS1.2] [F04-OS1.3] |
| (3) | [F11-OS1.5] |
| (4) | Note1 |
|
9.9.2.4. (1) |
[F02,F03-OS1.2] [F04-OS1.3] |
| (2) | Note1 |
| (3) | Note1 |
|
9.9.2.5. (1) |
[F02,F03-OS1.2] [F04-OS1.3] |
| (2) | Note1 |
| 9.9.2.6. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| 9.9.2.7. (1) | Note1 |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| 9.9.2.8. (1) | [F03-OS1.2] |
|
(2) |
[F03-OS1.2] [F05-OS1.5] |
| (3) | Note1 |
| 9.9.2.9. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.9.2.10. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| (7) | [F03-OS1.2] |
| (8) | Note1 |
| 9.9.2.11. | [F03-OS1.2] |
| 9.9.2.12. (1) | [F03-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | [F81-OH1.1] |
| (6) | Note1 |
| (7) | Note1 |
| 9.9.2.13. (1) | [F03-OS1.2] |
| (2) | Note1 |
| 9.9.2.14. (1) | [F03-OS1.2] |
| (2) | [F03-OS1.2] |
| (3) | [F02,F03-OS1.2] |
| (4) | Note1 |
| 9.9.2.15. (1) | Note1 |
| (2) | [F03-OS1.2,OS1.5] |
| (3) | [F03-OS1.2,OS1.5] |
| (4) | Note1 |
| (5) | Note1 |
| 9.9.2.16. (1) | [F02-OS1.2] |
| (2) | [F02-OS1.2] |
| (3) | [F02-OS1.2] |
| 9.9.2.17. (1) | [F05-OS1.5] |
| (2) | Note1 |
| 9.9.2.18. | [F05-OS1.5] |
| 9.9.2.19. (1) | Note1 |
|
(2) |
[F01-OS1.1] [F02,F03-OS1.2] [F82-OS1.1,OS1.2] |
| (3) | [F02-OS1.2] |
| (4) | [F02-OS1.2] |
| (5) | [F03-OS1.2] |
| (6) | Note1 |
| Subsection 9.9.3. | Containment |
| 9.9.3.1. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| 9.9.3.2. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | [F10-OS1.5] |
| (4) | Note1 |
| (5) | [F10-OS1.5] |
| (6) | [F10-OS1.5] |
| (7) | Note1 |
| (8) | Note1 |
| (9) | [F10-OS1.5] |
| (10) | [F10-OS1.5] |
| (11) | [F10-OS1.5] |
| 9.9.3.3. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | [F10-OS1.5] |
| (4) | Note1 |
| (5) | [F10-OS1.5] |
| (6) | Note1 |
| 9.9.3.4. | Note1 |
| 9.9.3.5. (1) | [F10-OS1.5] |
|
9.9.3.6. (1) |
[F03-OS1.2] [F05-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| 9.9.3.7. (1) | Note1 |
|
(2) |
[F03-OS1.2] [F10,F20,F30-OS1.5] |
| (3) | [F05-OS1.5] |
| (4) | [F10-OS1.5] |
| (5) | [F10-OS1.5] |
| (6) | Note1 |
| 9.9.3.8. | [F10-OS1.5] |
| 9.9.3.9. | [F10-OS1.5] |
| 9.9.3.10. (1) | [F10-OS1.5] |
|
(2) |
[F10-OS1.5] [F12-OS1.2,OS1.5] |
| (3) | Note1 |
|
9.9.3.11. (1) |
[F02-OS1.2] [F05-OS1.5] |
| (2) | Note1 |
| 9.9.3.12. | [F02-OS1.2] |
| 9.9.3.13. | [F10-OS1.5] |
| 9.9.3.14. (1) | [F10-OS1.5] |
| (2) | [F10-OS1.5] |
| (3) | [F10-OS1.5] |
| Subsection 9.9.4. | Fire Alarm and Detection |
|
9.9.4.1. (1) |
[F11-OS1.5] [F13-OS1.2,OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
|
9.9.4.2. (1) |
[F11-OS1.5] [F13-OS1.2,OS1.5] |
|
(2) |
[F11-OS1.5] [F13-OS1.2,OS1.5] |
| (3) | Note1 |
| (4) | Note1 |
|
9.9.4.3. (1) |
[F11-OS1.5] [F13-OS1.2,OS1.5] |
| (2) | Note1 |
|
(3) |
[F11-OS1.5] [F13-OS1.2,OS1.5] |
| 9.9.4.4. (1) | [F11,F13-OS1.5] |
| 9.9.4.5. (1) | [F12-OS1.2,OS1.5] |
| (2) | Note1 |
| 9.9.4.6. | [F03-OS1.2] |
| 9.9.4.7. (1) | [F81-OS1.4] |
|
9.9.4.8. |
[F11-OS1.5] [F13-OS1.2,OS1.5] |
|
9.9.4.9. |
[F11-OS1.5] [F13-OS1.2,OS1.5] |
| 9.9.4.10. | [F81-OS1.4] |
| 9.9.4.11. (1) | [F11,F13-OS1.5] |
| (2) | Note1 |
| (3) | [F81-OS1.4] |
| (4) | [F81-OS1.4] |
| 9.9.4.12. (1) | [F81-OS1.4] |
| (2) | [F81-OS1.4] |
| (3) | Note1 |
| 9.9.4.13. (1) | [F11-OS1.5] |
|
(2) |
[F11-OS1.5] [F81-OS1.4] |
| (3) | Note1 |
|
(4) |
[F11-OS1.5] [F81-OS1.4] |
| (5) |
Note1 Applies to the following text in the Fire Code: “Smoke alarms __ shall have no disconnect switches between the overcurrent device and the smoke alarm”.
[F81-OS1.4] |
| (6) | Note1 |
| (7) | [F11-OS1.5] |
| 9.9.4.14. (1) | [F11,F12-OS1.5] |
| (2) | [F11,F12-OS1.5] |
| (3) | Note1 |
| Subsection 9.9.5. | Suppression |
| 9.9.5.1. (1) | [F12-OS1.2,OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| 9.9.5.2. (1) | [F02,F12-OS1.2] |
| (2) | Note1 |
| (3) | Note1 |
| (4) | Note1 |
| (5) | Note1 |
| (6) | Note1 |
| 9.9.5.3. (1) | [F12-OS1.2,OS1.5] |
| (2) | Note1 |
| (3) | Note1 |
|
9.9.5.4. |
[F02-OS1.2] [F81-OS1.4] |
| 9.9.5.5. (1) | [F81-OS1.4] |
| (2) | [F81-OS1.4] |