blank space

Ontario Fire Code COMMENTARY ON CHANGES TO THE FIRE CODE (1997 edition)
 (revoked November 21, 2007)

Commentary on Changes to the Fire Code

This document has been prepared to identify significant changes adopted in the 1997 edition of the Fire Code, Ontario Regulation 388/97 .

This commentary contains explanations relating to the application and intent of these changes. For the full text of any requirements, reference should be made to the Official Volumes.

Additional Copies

Additional copies can be purchased from:

Publications Ontario Bookstore
880 Bay Street, Toronto M7A 1N8
(416) 326-5324

Publications Ontario Phone Orders
(416) 326-5300 or 1-800-668-9938

Access Ontario
Ottawa Court House
161 Elgin Street, Ottawa K2P 2K1
(613) 238-3630

Publications Ontario Website
www.publications.serviceontario.ca/
- accepts VISA or MasterCard


INTRODUCTION

Ontario Regulation 388/97, the Fire Code, was filed on October 30, 1997. This regulation represents the first extensive review of the Fire Code since 1987. Except as specifically noted otherwise, the regulation came into force on November 21, 1997. The package contains a number of technical amendments as well as numerous editorial amendments.

Some of the more significant technical amendments include:

(i) new qualifications and responsibilities for persons who carry out testing and servicing of fire alarm systems,

(ii) mandatory smoke alarm installation in previously unregulated residential units,

(iii) maintenance requirements for smoke alarms, and

(iv) the introduction of comprehensive technical requirements under Part 4, "Flammable and Combustible Liquids".

A separate commentary dealing specifically with Part 4 of the Fire Code is available.

The editorial amendments have been made to:

(i) clarify the intent of certain requirements,

(ii) reconcile differences with the Building Code,

(iii) update referenced standards, and

(iv) provide additional flexibility for compliance.

Many of these changes clarify the owner's responsibility for compliance and restore consistency, while improving the enforcement capability of the fire service.

As well, the consolidated printing includes Appendices A, B and C which provide relevant Building Code references for use with Part 9, "Retrofit".



PART 1 - APPLICATION AND DEFINITIONS

Article 1.1.1.3. Repair or Replacement of Defective Components

Many Articles in the Fire Code deal with the checking, inspecting or testing of components but the requirement that these components be repaired if they do not operate was not previously included in a consistent manner. Article 1.1.1.3. has been added to require that corrective action be carried out to repair or replace all defective components. To avoid duplication, corresponding deletions have been made in the body of the Code.

Subsection 1.1.5. Qualification and Responsibilities of Persons Performing Tests, Inspections and Maintenance of Fire Protection Equipment

This new Subsection requires that every person who carries out annual tests, annual inspections, repairs or alterations to a fire alarm system must have successfully completed a program or course acceptable to the Fire Marshal. These persons are also responsible for carrying out the work in compliance with the Code. Persons who are not qualified can work under the supervision of a qualified person.

This Subsection comes into force on November 21, 1999, to permit an adequate implementation period. These requirements were introduced to improve operability of fire alarm systems as a result of recommendations made by coroner's juries. Also, please refer to the corresponding requirements in Article 6.3.2.1.

Article 1.1.6.3. Other Exemptions

This Article identifies specific exemptions to the Fire Code to deal with situations where an owner has complied with previous editions of the Fire Code. It is not intended that additional changes be made in a building to satisfy the revised Fire Code in many cases. For example, where a theatre has been retrofitted to satisfy the previous version of Section 9.2, further upgrading is not necessary even though changes may have been made to this Section.

Article 1.1.7.2. Referenced Standards, Documents, Manuals or Handbooks

This Article has been amended to include a new Table 1.1.7.A. which identifies the edition of each standard, document, manual and handbook referenced in the Fire Code. The new table does not replace the actual references in the body of the Fire Code, but does eliminate the date of the particular edition from these references and captures them in the new table.

The referenced standards, documents, manuals and handbooks in Table 1.1.7.A. have been updated to correspond to the date of the editions listed in the 1990 Building Code (as amended to 1993), as much as practical.

Article 1.1.7.4. Chief Fire Official Discretion on Use of Reference Documents

This Article has been added to give authority to the Chief Fire Official to permit compliance with earlier editions of documents referenced in the Fire Code. This provides greater flexibility for compliance with the Code.

Article 1.1.7.5. Secondary References in Documents

This Article has been added to specify that where a document referenced in the Fire Code contains second level references to another document, only those portions of the second document that are specific to the subject matter are applicable. This is intended to clarify that application and enforcement of non-relevant material from the second document and additional tertiary documents is not required.

Article 1.1.8.3. Chief Fire Official

This new Article permits the Chief Fire Official to appoint persons who are assistants to the Fire Marshal to be Chief Fire Officials. The Chief Fire Official will have specific areas of responsibility or limitations as set out in the appointment.

Article 1.2.1.2. Definitions

All defined terms in the Fire Code are identified in bold print. Several types of amendments have occurred in the defined terms. A number of definitions have been amended to correspond with the definitions contained in the Building Code. This includes, but is not limited to, definitions for basement, building area, dwelling unit, exit, grade, means of egress, public corridor, etc.

As a result of amendments adopted elsewhere in the Fire Code, there are new definitions including contained use area, impeded egress zone and rapid transit station. Also, new definitions have been added to clarify the application and intent of various Articles in the Fire Code. These definitions include farm building, service room and service space. Other defined terms (e.g. "breeching" and "chimney liner") have been deleted from the definitions as they no longer appear in the Code.

The term "existing" has been removed from the definitions and is now separately defined in each Section of Part 9, "Retrofit". A date is included with each of these defined terms corresponding to the date that Section came into force. This permits easier identification of existing systems or components within Part 9.

The term Building Code has been amended to generically reference any edition of the Building Code. This new definition is consistent with the original intent of the Fire Code and applies to Parts 1 to 8. A separate definition for "Building Code" appears in each Section of Part 9 to clearly identify the edition of the Building Code that is utilized in the direct references. Please refer to the complementary information contained in Appendices A, B and C.

Chief Fire Official has been amended to ensure that the individual has been designated as an assistant to the Fire Marshal.

The term combustible dust has been revised to include any dust and is now consistent with the original intent of the Fire Code.

PART 2 - BUILDING AND OCCUPANT FIRE SAFETY

Article 2.2.3.5. Checking Doors

This Article has been amended to exclude the need to check doors that are designed to close automatically in the event of fire or where the fire safety plan contains provisions for closing these doors in the event of a fire.

Examples of doors to which this exclusion would apply include:

(i) doors equipped with acceptable magnetic hold-open devices,

(ii) bedroom doors in health care facilities, which are normally open and would be closed under provisions in the fire safety plan, and

(iii) doors to classrooms in elementary and secondary schools, which are often open during classroom use and would also be closed under provisions in the fire safety plan.

Article 2.4.1.1. Accumulation of Combustible Materials

The term "waste" has been deleted from this Article to ensure that any combustible materials are properly stored. An exemption is provided for locations specifically designed for the storage of combustible materials.

Articles 2.4.1.2. to 2.4.1.10. Storage and Disposal of Combustible Materials

These Articles have been amended to better describe inappropriate combustible material storage locations. The phrase "except for building components" has been added to Article 2.4.1.2. to exclude combustible components such as wooden handrails, door trim, etc. Proper methods of handling flammable or combustible liquid spills are now addressed in Article 2.4.1.5.

Article 2.4.7.1. Vacant Buildings

This new Article requires that all vacant buildings be secured to help prevent acts of vandalism and arson. Previously, the only means to get a vacant building secured was by issuing a Fire Marshal's Order. Including this Article in the Fire Code makes enforcement more expedient.

What constitutes a vacant building can vary depending on the circumstances. According to the Insurance Bureau of Canada, the Canadian insurance industry uses two definitions for vacant. One requires that the premises be unoccupied for a period of four consecutive days and the other that they be unoccupied for a period of 30 consecutive days. Black's Law Dictionary does not use a specified number of days but states that vacant implies entire abandonment and nonoccupancy for any purpose.

The Fire Code has not adopted a specific definition. For the purpose of this Article, it is the concept of being abandoned or of having the appearance of having been abandoned which is important, rather than any specific time period.

Numerous methods are available to secure a building. The level of security which is required will vary depending on the specific circumstances.

It should be noted that when a building is being secured, it is still necessary to provide sufficient access for fire fighting and to comply with all applicable requirements in the Fire Code, including the provision of adequate means of egress.



Sentence 2.5.1.1.(1) Fire Department Access

Sentence 2.5.1.1.(1) has been amended to include fire access routes required by the Fire Code within the scope of Section 2.5. For example, fire access routes required by Part 9 must now be identified by signs and maintained under this Section.

Articles 2.6.1.2. to 2.6.1.8. Heating, Ventilating and Air-Conditioning

These Articles have been revised and renumbered to clarify the hazards associated with certain components of service equipment and the maintenance that is required. In particular, a requirement to repair or replace chimneys, flues or flue pipes due to damage or deterioration is stated.

Article 2.6.3.2. Incinerator Maintenance

This Article has been revised to identify the need to properly maintain both indoor and outdoor incinerators to NFPA 82, not just outdoor incinerators.

Subsection 2.6.4. Electrical Equipment Vaults

The application of the requirements is clarified by replacing the term "transformer vaults" with "electrical equipment vaults".

Article 2.7.1.4. Occupant Load in Assembly Occupancies

This Article has been amended to reflect the requirements in the Building Code for obtaining the occupant load of an assembly occupancy. It also establishes occupant load limits. Table 2.7.1.A. has been added to assist in determining the occupant load for an assembly area based upon the anticipated uses.

A new requirement places an upper limit on the occupant load, based on 0.60 m2 per person in "dining, alcoholic beverage and cafeteria space", and 0.40 m2 per person for all other uses. This ensures that occupants are not jammed into a space which has adequate means of egress but which cannot be accessed properly because of overcrowding.

This Article is also referenced in Article 9.2.3.1. for calculating occupant loads in floor areas of assembly occupancies for purposes of determining retrofit requirements.

Article 2.7.1.5. Posting Occupant Load

This Article now refers to Article 2.7.1.4., rather than the Building Code, for occupant load determination. When the occupant load exceeds 60 persons it must be posted in a conspicuous location.

In addition, this amended Article requires posting of the occupant load when it is based on a design other than Table 2.7.1.A. or on the number of fixed seats. This posting requirement is consistent with the Building Code. For instance, where the floor area of a room would allow an occupant load of more than 60 persons but only one egress door from the room exists, a design consideration could be to limit the occupant load to 60 persons. This occupant load would have to be posted.

Article 2.7.2.1. Exit and Access to Exit Door Release Hardware

This Article has been restructured to clarify where panic type or fire exit hardware is required on exit doors and has been expanded to also include access to exit doors. It now specifies which access to exit doors and exit doors must swing on a vertical axis in the direction of exit travel.

A new Sentence states that the door release hardware requirements do not apply in rapid transit stations which comply with the Building Code (Section 3.12 of the Building Code contains substantially different egress requirements from those stated elsewhere in the Building Code). The Fire Code requires existing rapid transit stations that do not comply with Section 3.12 of the Building Code to comply with this Article.

Article 2.7.2.2. Exit and Access to Exit Door Operation

This Article has been revised to include doors in an access to exit to ensure that occupants can exit from any point in the building without having to rely on keys, special devices or special knowledge to open doors.

An exception to this requirement relates to contained use areas and impeded egress zones. Three conditions where locking devices may be provided in contained use areas and impeded egress zones are provided in this amended Article, consistent with the Building Code.

Electromagnetic locking devices are now allowed on all exit and access to exit doors, except in elementary and secondary schools and Group 'F' Division 1 occupancies. These electromagnetic locking devices must either be approved or installed in conformance with the Building Code.

A new exception in this Article allows doors in exits and access to exits in existing rapid transit stations to have the locking devices, provided these rapid transit stations have all the features required by Section 3.12 of the Building Code.

Article 2.7.3.2. Exit Signs

Wording change to this Article clarifies that both internally and externally illuminated exit signs must be illuminated when the building is occupied. The Building Code permits both types of signs.

Article 2.8.1.1. Emergency Planning - Application

Sentence (2) of this Article has been expanded to list additional occupancies that are identified elsewhere in the Fire Code and which require a fire safety plan (e.g. subject to provisions for outdoor tire storage, for flammable and combustible liquids, laboratories etc.).

Subsection 2.8.2. Fire Safety Plans

This Subsection has been reorganized for clarity and includes a new requirement for fire safety plans to be kept on site and available at all times.

Article 2.8.3.2. Fire Drills

This Article has been amended to require that fire drill records be kept for a period of one year after the drill. Without such a record, it is not possible to tell whether the fire drill frequency has been met.

Article 2.9.2.1. Flameproofing Treatments for Tents and Air-Supported Structures

This Article has been amended to identify that it is the owner's responsibility to have flameproofing treatments renewed as necessary.

Article 2.9.3.3. Fire Alarm or Firewatch in Tents and Air-Supported Structures

This Article has been amended to clarify the need for a fire alarm system or firewatch. Discretionary authority has been added, to allow the Chief Fire Official to approve a fire alarm system that does not meet the Building Code. Factors to be considered would be based on the system's ability to provide adequate early warning to the occupants.

Article 2.11.1.3. Insulation and Re-Insulation in Roof and Floor Assemblies

A wording change clarifies the intent to prevent insulation from being added to a roof or floor assembly where it would reduce the fire-resistance rating of the assembly.

Section 2.13 Installation of Smoke Alarms

This new Section has been developed to ensure that every dwelling unit is equipped with at least one smoke alarm. Specifically, this Section requires owners to install smoke alarms in homes that were not constructed under the Ontario Building Code, which was first introduced in December, 1975. Homes constructed to meet the Building Code should already have at least one smoke alarm.

For the purposes of this Section, smoke alarms conforming to CAN/ULC S531, "Smoke Alarms", must be installed between the sleeping area and the remainder of the dwelling unit, or in a hallway that serves sleeping areas.

Smoke alarms are required to be hard-wired, although battery operated units would also be acceptable.

This requirement takes effect when the Chief Judge (Provincial Division) establishes the fines for not having a smoke alarm, associated with ticketable offences under Part I of the Provincial Offences Act.

Complementary maintenance requirements for all smoke alarms are included in Subsection 6.3.3., which comes into force at the same time as this Section.

PART 3 - PROPERTY PROTECTION FOR INDUSTRIAL AND COMMERCIAL OCCUPANCIES

Articles 3.2.3.8. and 3.2.3.9. Fire Department Access to Wood Chip Piles

These revised Articles now require access walkways of a permanent nature, constructed of noncombustible materials. The Chief Fire Official has the authority to approve other means of ensuring adequate fire department access to wood chip piles. For instance, provision of portable turrets, deluge sets or monitor towers might allow complete hose stream coverage, minimizing the need for a walkway.



Article 3.3.2.6. Fire Access Aisles for Indoor General Storage

This Article has been revised to require a main access aisle extending the full length of the building with an increased minimum aisle width that is related to the storage height.

The revision also eliminates the requirement to have aisles "to the sides" of the building, although access aisles are still required to exits, fire department access panels and fire protection equipment.

Article 3.4.1.1. Industrial Trucks

This Article has been amended to require industrial trucks to conform with NFPA 505, "Powered Industrial Trucks Including Type Designations, Areas of Use, Maintenance, and Operation". This is a recognized standard that specifies proper designation, use, maintenance and operation of these vehicles.

Article 3.4.2.5. Propane Cylinders for Industrial Trucks

This Article has been amended to reference the Propane Storage Handling and Utilization Code made under the Energy Act, which is the proper legislation dealing with propane cylinder storage. This will ensure consistency with other pieces of legislation.

Article 3.5.3.10. Security Around Tire Storage Yards

This Article clarifies the security requirements around tire storage yards. It also specifies that overhead portions of gateways must be high enough to allow fire department vehicle entry.

Section 3.6 Cleaning and Dyeing Plants

In Article 3.6.1.1., the application of this Section has been amended to require dry cleaning plants to conform with specified portions of NFPA 32, "Drycleaning Plants". As well, specific reference is made to the Ontario Electrical Safety Code made under the Power Corporation Act in lieu of NFPA 70, which is referenced by NFPA 32.

An exception has been provided where existing dry cleaning and dyeing plants may be approved where the Chief Fire Official believes that an acceptable level of fire safety is provided.

The remainder of the Section continues to apply to dry cleaning and dyeing plants, and deals with the use of combustible liquids, ventilation and control of fire hazards.

PART 4 - FLAMMABLE AND COMBUSTIBLE LIQUIDS

The new Part 4 of the Fire Code applies to the storage, handling, processing and use of flammable and combustible liquids in all occupancies. Compliance with Part 4 is phased in over a four year period beginning on August 21, 1998.

To assist owners in complying with these requirements, a separate "Commentary on Part 4 of the Ontario Fire Code" and audit guides have been developed. Please refer to those documents for complete details.

PART 5 - HAZARDOUS MATERIALS, PROCESSES AND OPERATIONS

Subsection 5.2.2. Fireworks and Pyrotechnics

The scope of this Subsection has been expanded to include pyrotechnics. This was always the intent but was not specifically stated. In addition, reference to the appropriate manuals has been updated.

Article 5.3.1.1. Matches

This Article has been amended to be consistent with current federal legislation which addresses all classification, packaging and labeling requirements for matches.

Sentences 5.6.1.1.(2) and (3) Compressed Gas Cylinders

These new Sentences have been added to narrow the scope to which Section 5.6 applies.

Sentence (2) exempts manufacturers of compressed gas, or facilities where cylinders are filled or distributed when storage and handling meets certain criteria. This exemption recognizes the unique nature of these operations and the impracticality of applying the storage conditions due to the large number of cylinders located in these facilities. It also recognizes that the employees will be trained about proper handling and hazards.

Sentence (3) has been added to exempt users of small quantities of compressed gases, such as doctors, dentists and jewellers, since the application of the stringent requirements is not warranted in the circumstances and creates unnecessary hardship.

Sentence 5.6.1.1.(4) Poisonous and Corrosive Compressed Gas Cylinders

This Sentence has been added to clarify that requirements of Articles 5.6.2.1. to 5.6.2.4. apply to the storage of any amount of poisonous or corrosive compressed gases, such as chlorine or anhydrous ammonia gas.

Article 5.6.1.2. Protection and Storage of Compressed Gas Cylinders

This Article has been amended to clarify the methods of storing cylinders to minimize the chance of accidental damage. Where the storage arrangements are not as specified, the other methods must be approved.

Article 5.6.1.4. Compressed Gas Cylinder Valve Protection

This Article has been amended to permit alternative ways to protect cylinder valves from damage besides the use of valve caps. For example, use of collars that are welded to the cylinder or placing cylinders in a box or metal cage would now meet the intent of this requirement.

Article 5.6.1.6. Ventilation for Compressed Gas Cylinder Storage

This Article now requires that ventilation satisfy the criteria in Sentence 5.6.2.4.(4). The continued intent is to ensure there is no buildup of the gases in an enclosed space.

Sentence 5.6.2.3.(1) Clearances of Compressed Gases from Building Openings

This Sentence has been amended to state that the volumes specified are for expanded gases at room temperature. The aggregate volume of a gas at standard temperature and pressure is a function of the container's liquid capacity, the liquid density and it's molecular weight.

Clauses 5.6.2.4.(1)(d) and (f) Indoor Storage of Flammable Compressed Gases

Clause (1)(d) has been amended to permit an interior door from a flammable gas storage room into a building if the door is appropriately rated and constructed to be gas tight. Previously such a storage room could only be accessed from the outside.

Clause (1)(f) has been amended to reference specific ventilation criteria. Natural or mechanical ventilation requirements for rooms storing flammable compressed gases are detailed in new Sentence 5.6.2.4.(4).

Sentence 5.6.2.4.(3) Storage of Heavier than Air Flammable Compressed Gases

This Sentence provides an exception to the storage room requirements in Sentence (1), and applies to heavier than air flammable compressed gases such as propane. Containment, quantity, location and ventilation requirements are specified. This Sentence does not apply to cylinders in use; rather it is intended for cylinder storage.

Sentence 5.6.2.4.(4) Ventilation in Storage Rooms for Flammable Compressed Gases

This Sentence has been added to provide further guidance on acceptable ventilation requirements for compressed gases storage rooms by providing both performance requirements and a specification on how to achieve similar ventilation rates through natural means. It is important to note that this requirement applies to compressed gas storage, as opposed to compressed gas that is in use.

Article 5.6.2.7. Storage Restrictions of Compressed Gases that May React With Each Other

This Article has been amended to fully describe ways and means of storing and separating compressed gases that have differing characteristics and may react with each other. Lighter than air gases have a tendency to rise and dilute on discharge. Gases which are heavier than air accumulate and migrate along the floor. This revision accommodates both these physical characteristics.

Sentence 5.12.2.1.(3) Spray Booth Floors

Reference to non-sparking material has been deleted from this Sentence. It was intended to guard against the possibility of static sparks being generated by the use of ferrous tools or equipment but continuation of the requirement is not warranted, nor required by other Codes.

Article 5.12.2.4. Spray Booth Fan Blades and Casings

This Article has been amended to allow ferrous material for exhaust fan blades and casings as long as there is no contact between ferrous parts. The intent is to ensure that the fan does not become a source of ignition by causing sparks from contact between the fan blade and casing which could ignite flammable vapours or residue in the exhaust duct and spray booth.

Article 5.12.3.1. Spray Booth Mechanical Ventilation

This Article has been amended to specify that mechanical ventilation must be provided so that concentration of flammable vapours or combustible dust does not exceed 25 per cent of the lower explosive limit (LEL).

Article 5.12.3.6. Maintenance of Air Velocity in Spray Booths

This Article has been amended to ensure that corrective action will be taken when the required gauges or alarms indicate low air velocities at the face of the spray booth. This is intended to prevent dangerous concentrations of flammable vapours or combustible dust from building up in the area immediately surrounding open-face spray booths.

Article 5.12.7.2. Spray Booth Cleaning and Residue Disposal

This Article has been amended to address the fire risk from the accumulation of combustible residue in spray booths. The owner must keep the inner surfaces of the spray booth from accumulations of combustible residue that may present a fire hazard. Proper disposal of the residue on the same day as the cleaning operation is now required.

The amendment also refers to specific Articles that provide criteria for acceptable containers used for disposal of the combustible residue and removes the onus on the Chief Fire Official to approve them.

Article 5.12.9.2. Drying Operations

This Article has been revised to restrict the use of any drying or curing equipment in or near a spraying area where the equipment is capable of causing ignition of flammable vapours, such as by a spark, open flame or hot surface. Previously, this Article only restricted equipment that utilized open flames or produced sparks.

Article 5.12.9.3. Drying Operations Adjacent to Spraying Areas

This Article has been amended to include specific ventilation criteria to limit flammable vapour or combustible dust concentrations at no more than 25 per cent of the lower explosive limit (LEL) for drying areas that are set up adjacent to spraying areas.

Article 5.12.9.4. Automobile Spray Booths Used for Drying

This Article has been amended to reference Section 5.18 for proper design of an automobile spray booth where drying also takes place. It also restricts portable heating devices to infrared types, if used in these spray booths.

Specific criteria has been included in the amendments for ventilation to limit flammable vapour or combustible dust concentrations to a maximum 25 per cent of the lower explosive limit (LEL).

Article 5.13.1.1. Dip Tanks for Flammable or Combustible Liquids

This Article has been amended to clarify that a properly designed and separated room is required when the dip tank volume exceeds 45 litres or the dip tank liquid surface area is greater 0.40 m2. Other requirements in this Subsection continue to apply to all dip tanks.

Article 5.14.2.5. Flow-Coating Operations

This Article has been amended to limit the scope of the requirements to flammable and combustible liquids only.

Shut down of a pumping supply system has also been amended to allow alternative listed devices for automatically shutting down the liquid pumping operation in the event of a fire. In addition to heat-actuated devices which were previously permitted, other methods might include products-of-combustion, infrared or UV detectors.

PART 6 - FIRE PROTECTION EQUIPMENT

Article 6.2.1.1. Portable Extinguishers

This Article now accepts the use of any "listed" extinguisher, not just ULC labeled extinguishers.

Sentences 6.2.4.1.(1) and 6.2.6.1.(1) Portable Extinguisher Location

These Sentences have been amended so that location and use of portable extinguishers relate to occupancies located both inside and outside buildings. This has always been the intent, but was not specifically stated previously.

Table 6.2.6.A. Extinguishers for Class A Fires

This table no longer contains references to 1A rated extinguishers because they are considered inadequate for all occupancies within the scope of Section 6.2.

Article 6.2.6.9. Extinguishers for Flammable and Combustible Liquids in Open Containers

This Article now identifies that minimum extinguisher requirements shall not be less than that required in Table 6.2.6.B. As well, a maximum travel distance of 15 m to a portable extinguisher is now specified for this application.

Article 6.2.6.12. Extinguishers for Commercial Cooking Equipment

This Article has been amended to permit wet chemical extinguishers for the protection of commercial cooking equipment in addition to alkali based dry chemical extinguishers.

Wet chemical extinguishers are commonly potassium acetate-based, potassium carbonate-based or potassium citrate-based.

Article 6.2.6.16. Portable Extinguisher Distribution for Combustible Metal Fires

This Article has been added to include the portable extinguisher requirements for Class D fires. This requirement was not previously provided in the Fire Code.

Article 6.2.7.1. Inspection, Testing and Maintenance of Extinguishers

Amendments to this Article effectively ban the use of extinguishers of copper/brass solder shell construction, through reference to NFPA 10, "Portable Fire Extinguishers". Given the potential hazard for these extinguishers to rupture due to normal internal operating pressures, such a ban is appropriate.

Article 6.2.7.4. Record of Inspection of Extinguishers

Sentence (2) has been added to this Article to allow other means of keeping records of extinguisher maintenance and recharge dates if approved by the Chief Fire Official. Computerized check sheets constitute one means of record keeping that could be approved.

Article 6.3.1.6. Security of Fire Alarm Power Supply

This new Article requires that disconnect switches for the power supply for fire alarms and interconnected smoke alarms must be maintained in a secure area or be otherwise approved by the Chief Fire Official.

Unrestricted access to the power supply resulted in the alarm system impairment that was a contributing factor in the fatal fire at the Rupert Hotel in Toronto.

Article 6.3.1.7. Relocating Manual Pull Stations

This Article has been added to address the high incidence of false alarms due to malicious acts. It allows relocation of manual pull stations to locations less susceptible to abuse. Before considering relocation, there is merit in investigating the nature of the false alarms, and considering possible deterrents such as increased security, permanent inks, pull station covers etc. Relocation of manual pull stations may simply involve shifting devices to locations that are more visible, or by setting the devices further back from doors.

The Chief Fire Official must be satisfied that alternate life safety measures are provided before granting approval.

Changes to the activation of the fire alarm system are also required be identified in the fire safety plan.

Article 6.3.1.8. Repairs to Fire Alarm Systems

This new Article specifies that any repair or alteration work on fire alarm systems must be carried out in conformance with CAN/ULC-S524, "Installation of Fire Alarm Systems". Previously, there was no specific standard for remedial work and this led to concerns over the reliability of systems or components that had been serviced.

Article 6.3.2.1. Tests and Repairs for Fire Alarm Systems

This Article has been added to clarify the building owner's responsibility for ensuring that only qualified persons carry out the annual inspections and tests or work on fire alarm systems.

The owner need not comply with this requirement until November 21, 1999, which corresponds with the requirement in Subsection 1.1.5. for the qualification of persons performing work on fire alarm systems.

Articles 6.3.2.4. and 6.3.2.5. Voice Communication Systems

These Articles have been amended to specify different test requirements for voice communication systems, depending on whether or not they are integrated with the fire alarm system. For integrated voice systems, testing must be in compliance with CAN/ULC-S536, "Inspection and Testing of Fire Alarm Systems".

Voice systems that are not integrated with the fire alarm system must be tested in compliance with Article 6.3.2.5.

Subsection 6.3.3. Smoke Alarms - Testing and Maintenance

This new Subsection requires smoke alarms to be maintained in operating condition by the owner.

The Subsection also requires that where smoke alarms are being replaced, the level of detection required by the Building Code or municipal by-law at the time of construction be maintained. For example, battery operated smoke alarms cannot be used to replace hard-wired smoke alarms required by the Building Code at the time of construction.

In rental dwelling units, the landlord is considered as the owner and is responsible for maintaining the smoke alarms in operable condition. The landlord must also provide a copy of the maintenance requirements (manufacturer's instructions or approved alternative) to the tenant.

A new Article also prohibits anyone from intentionally tampering with a smoke alarm so as to render it inoperable.

As with Section 2.13, these requirements come into effect when the Chief Judge (Provincial Division) establishes the fines for not maintaining a smoke alarm, associated with ticketable offences under the Provincial Offences Act.

Article 6.4.1.3. Standpipe and Hose System Fire Department Connections

This Article has been amended to ensure that where fire department connections are damaged, corrective action is taken. In addition, if it is found that the caps or plugs are missing, back flushing of the line may be necessary prior to replacing the caps of plugs.

A similar change for sprinkler fire department connections has been made in Article 6.5.4.4.

Sentence 6.4.2.7.(1) Fire Hose Cabinets

This new Sentence permits fire hose stations to be located in approved lockable hose cabinets to reduce the incidence of theft and vandalism. Sentence 6.2.1.3.(2) also permits lockable hose cabinets that contain portable extinguishers.

Sentence 6.4.2.7.(2) Fire Hose Cabinets in Group 'B' Division 1 Occupancies

This new Sentence allows security measures to be taken for hose cabinets in facilities where persons are under restraint for correctional purposes.

Sentence 6.5.1.6.(5) Sprinkler Testing

This Sentence now clarifies that the objective of the main drain flow test is to ensure that there are no obstructions to the sprinkler water supply. It is the flowing water pressure that is observed to determine if there are obstructions.

Table 6.5.1.A. Flushing of Underground Mains for Sprinkler Systems

This table has been amended to bring the flow rates for flushing underground feed mains for sprinkler systems in line with the recognized standard, NFPA 24, "Installation of Private Service Mains and Their Appurtenances". The required flushing flow rates are generally significantly increased. The flow rate has been changed from L/s to L/min, which is a more widely accepted unit of measurement, and 100 mm pipe size has been added because it is common in small sprinkler systems.


Article 6.5.3.3. Pressure Maintenance in Sprinkler Systems

This Article has been amended to include weekly checking of water and/or air pressures on both the upstream side and downstream side of alarm-check valves or dry-valves of both wet and dry sprinkler systems. This weekly check is intended to monitor leaks in these sprinkler systems and helps confirm that the systems are operational.

Article 6.5.4.3. Dry-Pipe Sprinkler Valve Priming Water Level

This Article has been amended to increase the inspection frequency for confirming proper priming water levels in dry-pipe sprinkler systems to every 3 months. This period is consistent with NFPA 25, "Inspection, Testing and Maintenance of Water-Based Fire Protection Systems". If the priming water is not maintained at the proper level, false tripping of the alarm valve or total system failure can result.

Article 6.5.4.4. Sprinkler System Fire Department Connections

This Article has been amended to ensure that where fire department connections are damaged, corrective action is taken. In addition, if it is found that the caps or plugs are missing, back flushing of the line may be necessary prior to replacing the caps of plugs.

A similar change for standpipe fire department connections has been made in Article 6.4.1.3.

Article 6.5.5.2. Sprinkler Alarm Testing

This Article has been amended to clarify that testing of sprinkler alarms is to be carried out by flowing water through the test connection at the sprinkler control valve. The amendments also relax the alarm testing frequency of electrically supervised sprinkler systems where the system operates in conformance with Article 6.5.5.7.

This Article now has an additional requirement to clear the alarm line so as to prevent freezing after the test.

Article 6.5.5.4. Trip Testing of Dry-Pipe Valves

This Article has been amended to include details on the proper method and frequency for trip testing dry-pipe valves on dry sprinkler systems. This includes a minimum annual frequency with the main control valve partially open and a minimum 3 year frequency with the control valve fully open.

The dry-pipe valve trip time (the time that it takes for the valve to open and permit water to enter into the sprinkler system) is also required to be maintained within 10 per cent of its original design. This allowance recognizes that long term deterioration of the sprinkler system may result in a variance in the trip time, and is acceptable within certain limitations.

If the trip time exceeds this allowance, the system must be checked to determine the cause and corrective action taken.

Sentence 6.5.5.7.(1) Electrical Supervision Signal Testing

This Sentence has been amended to clarify that the signal device on the sprinkler system must be operated to ensure that it functions reliably. For example, where a sprinkler control valve has a supervisory switch, the control valve should be operated to ensure that the switch will transmit a signal to the control panel.

Article 6.5.6.6. Protection for Combustible Sprinkler Piping

This Article has been added to clarify that protection for combustible sprinkler piping which is installed to meet the Building Code must also be maintained. For instance, the required thermal barrier which separates the plastic piping from the floor area protected by the sprinklers must be maintained in good condition.

Article 6.6.5.2. Inspection of Hydrants

This Article has been amended to clarify actions that are required to ensure that a hydrant is operable. This includes checking that hydrant caps are in place and the need for an examination of the hydrant barrel for obstructions if the hydrant caps are missing. The word "threads" has been replaced by "connections" to accommodate quick connect couplings.

Article 6.6.5.5. Hydrant Leakage

This Article has been amended to permit alternative methods to keep hydrants from freezing if they do not drain properly. This is subject to approval by the Chief Fire Official and is intended for hydrants that are impractical to repair.

For example, a hydrant located in an area with a high water table may impede the ability of the hydrant barrel to drain properly, but the problem could be addressed by injecting antifreeze into the barrel of the hydrant for the winter months.

Article 6.7.1.4. Fuel Supply for Emergency Power Systems

This Article has been amended to reduce the fuel supply that is required for emergency electrical power systems from 8 hours to 2 hours. This is consistent with the current Ontario Building Code and National Fire Code.

PART 7 - INSPECTION, TESTING AND MAINTENANCE OF FIRE EMERGENCY SYSTEMS IN HIGH BUILDINGS

Article 7.2.1.2. Maintenance of Firefighters' Elevators

This Article has been expanded to include firefighters' elevators required in buildings under Part 9 of the Fire Code.

Sentence 7.2.2.1.(1) Elevator Door-Opening Devices

This Sentence has been amended to increase the door open time limit for photo-electric operated elevators to a maximum of 20 seconds from 10 seconds. This is now consistent with the Building Code.

Sentence 7.2.3.1.(4) Maintenance of Smoke Venting Systems

This Sentence has been amended to identify the proper Building Code reference.

PART 8 - DEMOLITION

Sentences 8.1.2.2.(4) and (5) Fire Safety Planning for Demolition

These Sentences have been added to provide a greater degree of fire safety at demolition sites by requiring the establishment of practices and procedures to control fire hazards and maintain fire protection equipment. As well, demolition site personnel must be instructed on fire emergency procedures to be taken in the event of a fire. This is consistent with the National Fire Code.

Sentence 8.1.2.3.(2) Combustible Salvage

This Sentence has been added to specify design and installation criteria for temporary refuse chutes at demolition sites. This is intended to enhance the fire safety at demolition sites by ensuring that temporary refuse chutes do not facilitate fire spread.

Sentence 8.1.2.6.(5) Maintenance of Standpipe Systems in High-Rise Buildings Under Demolition

This Sentence has been amended to clarify that in buildings under demolition, existing standpipes must be connected to an operational fire pump and water supply. This is to ensure that there will be a reliable water supply for fire department use.

This requirement only applies to buildings that exceed 84 metres in building height.

PART 9 - RETROFIT

Although not stated explicitly in Part 9, work carried out to comply with Part 9 does not relieve the owner of the building from obtaining a building permit where required under the Building Code Act.

Definitions for the terms "Building Code" and "existing" are identified at the beginning of each Section of Retrofit in order to eliminate confusion over which edition of the Building Code is referenced in the requirements. The definition for "existing" stated in each Section allows certain features in a building to receive credit as a compliance alternative.

Section 9.2 Assembly Buildings

Sentence 9.2.1.1.(2) Definitions

This Sentence provides specific definitions for the terms "1986 Building Code" as meaning O. Reg. 419/86, and "existing" as it refers to building components being in place in the building on February 11, 1987. The definitions of these terms are for purposes of this Section only.

For ease of use, the appropriate Building Code references are contained in Appendix A.

Article 9.2.3.1. Occupant Load Determination in Assembly Occupancies

This Article now refers to revised Article 2.7.1.4. for occupant load calculations, rather than a Building Code table. This updates and clarifies occupant load calculations and eliminates confusion that existed due to differing calculation methods.

Articles 9.2.3.7. to 9.2.3.9. Widths of Exits in Assembly Occupancies

The term "units of exit width" as a means of specifying required exit widths from assembly areas has been deleted from the Articles. Instead, the current practice of calculating exit widths based on the full net width of the egress path is identified. This is consistent with the Building Code. Minimum stair and corridor widths are still specified in paths of egress travel.

Section 9.3 Boarding, Lodging and Rooming Houses

Sentence 9.3.1.1.(3) Definitions

This Sentence provides specific definitions for the terms "1986 Building Code" as meaning O. Reg. 419/86, and "existing" as it refers to building components being in place in the building on February 11, 1987. The definitions of these terms are for purposes of this Section only.

For ease of use, the appropriate Building Code references are contained in Appendix A.

Articles 9.3.2.1. to 9.3.2.4. Required Fire Separations

These Articles have been amended to clarify the intent and to be consistent with fire separation requirements as described in other Sections of Retrofit. Fire separation requirements for floor assemblies and guest rooms are now clearly stated.

Also, Subsection 9.10.3. of the Building Code is now specifically referenced for construction of fire separations.

Sentence 9.3.2.5.(2) Fire Separations for Furnace Rooms

This Sentence has been added to permit existing walls consisting of lath and plaster or gypsum board to be acceptable in lieu of a 45-min fire separation. This is consistent with other Retrofit Sections of the Fire Code.

Article 9.3.3.13. Emergency Lighting

This Article has been amended to reference Article 9.9.11.5. of the Building Code (in addition to Article 9.9.11.4.). These references relate to emergency lighting.

Articles 9.3.4.1. and 9.3.4.2. Alarm and Detection Requirements

These Articles have been amended to more clearly identify the application of the fire alarm requirements for buildings covered under this Section. The requirements are dependent upon the type and rating of fire separations and the occupant load.

Generally, a fire alarm system is not required where the occupant load is 10 persons or less, each sleeping room is served by a properly separated and rated corridor and the floors are also properly separated and rated. In most other cases, a fire alarm system would be required.

Section 9.4 Health Care Facilities

Sentence 9.4.1.1.(2) Definitions

This Sentence provides specific definitions for the terms "1986 Building Code" as meaning O. Reg. 419/86, and "existing" as it refers to building components being in place in the building on February 11, 1987. The definitions of these terms are for purposes of this Section only.

For ease of use, the appropriate Building Code references are contained in Appendix A.

Article 9.4.2.13. Vertical Service Spaces in Health Care Facilities

This Article has been reworded to be consistent with other Sections in the Fire Code.

Section 9.5 Buildings Up to and Including Six Storeys in Building Height with Residential Occupancies

Sentence 9.5.1.1.(4) Definitions

This Sentence provides specific definitions for the terms "1990 Building Code" as meaning O. Reg. 413/90, and "existing" as it refers to building components being in place in the building on October 9, 1992. The definitions of these terms are for purposes of this Section only.

For ease of use, the appropriate Building Code references are contained in Appendix B.

Sentence 9.5.2.8.(6) Closures in Fire Separations

This editorial amendment clarifies that the waiver of a self-closing device only pertains to suite doors that do not open into a dead end corridor or exit.

Sentence 9.5.3.1.(3) Access to Exits

This new Sentence provides another option for egress and containment for boarding and lodging facilities with up to 10 residents where not more than 2 residents require assistance to evacuate in a fire emergency. This option will serve to maintain the family living environment of these types of facilities, while still providing an appropriate level of fire safety.

Sentence 9.5.3.7.(2) Fire Escapes

This Sentence has been revised to apply only where a fire escape serves any storey above the second floor. This change is consistent with the Building Code.

Sentence 9.5.4.1.(3) Fire Alarm Requirements

This Sentence now clarifies the conditions under which a fire alarm is not required in the building, dependent upon either the number of dwelling units that have access to an exit or, in a boarding and lodging facility, the number of persons that have access to an exit.

Section 9.6 Buildings Higher Than Six Storeys in Building Height with Residential Occupancies

Sentence 9.6.1.1.(4) Definitions

This Sentence provides specific definitions for the terms "1990 Building Code" as meaning O. Reg. 413/90, and "existing" as it refers to building components being in place in the building on October 9, 1992. The definitions of these terms are for purposes of this Section only.

For ease of use, the appropriate Building Code references are contained in Appendix B.

Sentence 9.6.5.2.(3) Standpipe Systems

This Sentence continues to permit existing standpipe systems with specified water flows, but the amendment clarifies that proper floor coverage for the standpipe outlets must still be provided.

Sentence 9.6.5.2.(4) Emergency Power for Standpipe Systems

This Sentence has been clarified as to the conditions under which emergency power is required for standpipe systems. It applies to standpipe systems that require more than one pump in series to provide a multi-staged boost of the water supply to feed the hose stations in the upper portions of high buildings.

These standpipe systems require an emergency power supply in the event of an electrical power failure, as the fire department would not likely have the equipment to boost water to the upper portions of the building using the fire department pumper connection.



Sentence 9.6.5.4.(3) Hydrants

This Sentence has been added to permit existing hydrant locations that have sufficient fire suppression capability and are approved by the Chief Fire Official. Aspects that could influence the acceptability of the arrangement include, but are not limited to, the presence of a booster pump equipped with emergency power, enhanced fire suppression within the building (e.g. being fully sprinklered), and availability of manpower and apparatus to respond.

Section 9.8 Two Unit Residential Occupancies

Sentence 9.8.1.1.(2) Definitions

This Sentence provides specific definitions for the terms "1994 Building Code" as meaning R.R.O. 1990, Regulation 61, as amended, and "existing" as it refers to building components being in place in the building on July 14, 1994. The definitions of these terms are for purposes of this Section only.

For ease of use, the appropriate Building Code references are contained in Appendix C.

Article 9.8.4.3. Maintenance of Smoke Alarms

This Article has been amended so that it will be revoked when the general maintenance requirements for all smoke alarms in Subsection 6.3.3. come into force. This will eliminate duplication and specify more precise requirements for maintenance of smoke alarms.

APPENDICES

Three new Appendices have been printed with the consolidated Fire Code as follows:

Appendix A, 1986 Building Code References, which contains extracts from O. Reg. 419/86, as referenced in Sections 9.2, 9.3 and 9.4 of the Fire Code;

Appendix B, 1990 Building Code References, which contains extracts from O. Reg. 413/90, as referenced in Sections 9.5 and 9.6 of the Fire Code; and

Appendix C, 1994 Building Code References, which contains extracts from R.R.O. 1990, Regulation 61, as amended by O. Reg. 400/91, 158/93, 160/93 and 383/94. These provisions are referenced in Section 9.8 of the Fire Code.

The intent of the new Appendices is to provide the user of the Fire Code with convenient access to Building Code references made in Part 9 of the Fire Code. Wherever possible, the Appendices provide exact wording from the original documents. In some cases this is not possible due to the extent of the reference. In those instances, an explanatory note has been provided in place of the original text of the regulation.

The appendix material is provided for convenience only. For accurate reference, code users are cautioned to use the Official Ontario Regulations.