Fire Code Supplement FCS-1

Objectives and Functional Statements Attributed to the Acceptable Solutions

May 2007

 

 

COMMENCEMENT

Fire Code Supplement FCS-1 comes into force on November 21, 2007.

 

 

© Copyright


Reproduction of this document for commercial or advertising purposes is prohibited without the written permission from the Office of the Fire Marshal, Ministry of Community Safety and Correctional Services.
 

 

TABLE OF CONTENTS

SECTION TITLE
1. SCOPE
2. OBJECTIVES AND FUNCTIONAL STATEMENTS
3. ATTRIBUTION TO ACCEPTABLE SOLUTIONS
4. USING THE TABLES
Table 2 Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 2 of Division B
Table 3 Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 3 of Division B
Table 4 Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 4 of Division B
Table 5 Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 5 of Division B
Table 6 Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 of Division B
Table 7 Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 7 of Division B
Table 8 Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 8 of Division B
Table 9 Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 9 of Division B

 

 

Fire Code Supplement FCS-1

Objectives and Functional Statements Attributed to the Acceptable Solutions

 

1. SCOPE

This document prescribes, for the purposes of Subsection 1.2.2. in Division A of the Fire Code, the objectives and functional statements that have been attributed to acceptable solutions set out in Division B of the Fire Code.

Objectives, functional statements and acceptable solutions referred to in this document are those defined in Article 1.4.1.2. of the Fire Code.

2. OBJECTIVES AND FUNCTIONAL STATEMENTS

The objectives referred to in this document are those set out in Part 2 of Division A of the Fire Code.

The functional statements referred to in this document are those set out in Part 3 of Division A of the Fire Code.

3. ATTRIBUTION TO ACCEPTABLE SOLUTIONS

For the purposes of compliance with the Fire Code, as provided in Clause 1.2.2.1.(1)(b) of Division A, the objectives and functional statements attributed to the acceptable solutions in Division B shall be the objectives and functional statements set out in Tables 2 to 9.

Where objectives and functional statements have not been attributed to an acceptable solution in Tables 2 to 9, the provisions of Clause 1.2.2.1.(1)(b) of Division A of the Fire Code do not apply and compliance with the Fire Code must be achieved by complying with the acceptable solution specified in Division B of the Fire Code. Refer to Sentence 1.2.2.1.(3) of the Fire Code for additional details.

4. USING THE TABLES

For the purposes of Tables 2 to 9, a notation made by the following mark “ … ” identifies text contained in the Fire Code that is included for the purposes of the attribution but is omitted from the table for brevity. A notation made by the following mark “ __ ” identifies text contained in the Fire Code that is deliberately excluded for the purposes of the attribution.

 

Table 2
Objectives and Functional Statements Attributed to the
Acceptable Solutions in Part 2 of Division B

Acceptable Solution Objectives and Functional Statements
SECTION 2.1 GENERAL
Subsection 2.1.1. Scope and Application
2.1.1.1. Note1
2.1.1.2. Note1
2.1.1.3.        (1) Note1
                     (2) Note1
                     (3) Note1
Subsection 2.1.2.
 
Classification of Buildings or Parts of Buildings by Major Occupancy
2.1.2.1. Note1
2.1.2.2.

 
[F01-OS1.1,OS1.2,OS1.5,OP1.1,OP1.2]
[F03-OS1.2,OS1.5,OP1.2]
[F04-OS1.3,OP1.3]
2.1.2.3. [F02-OS1.2]
SECTION 2.2 FIRE SEPARATIONS
Subsection 2.2.1. Major Occupancies
2.2.1.1. [F03-OS1.2,OP1.2]
Subsection 2.2.2. Rooms and Spaces
2.2.2.1. [F03-OS1.2,OP1.2]
Subsection 2.2.3. Closures
2.2.3.1. [F82-OS1.2,OP1.2]
2.2.3.2.        (1) [F82-OS1.2,OP1.2]
2.2.3.3. Note1
2.2.3.4. [F82-OS1.4,OP1.4]
2.2.3.5.        (1) [F82-OS1.2,OP1.2]
                     (2) Note1
2.2.3.6. RESERVED
2.2.3.7. [F82-OS1.2,OP1.2]
2.2.3.8. [F81-OS1.2,OS1.4,OP1.2,OP1.4]
SECTION 2.3 INTERIOR FINISHING, FURNISHING AND DECORATIVE MATERIALS
Subsection 2.3.1. General
2.3.1.1.        (1) [F02-OS1.2,OP1.2]
                     (2) Note1
2.3.1.2. [F02-OS1.2,OP1.2]
Subsection 2.3.2. Textile Flammability
2.3.2.1.        (1) [F02-OS1.2,OS1.5,OP1.2]
                     (2) Note1
                     (3) Note1
2.3.2.2. [F82-OS1.2,OS1.5,OP1.2]
SECTION 2.4 FIRE HAZARDS
Subsection 2.4.1. Combustible Materials
2.4.1.1.        (1)
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2,OP3.1]
                     (2)
 
[F01-OS1.1,OP1.1]
[F02,F03-OS1.2,OP1.2]
                     (3) Note1
                     (4)
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
                     (5) [F02-OS1.2,OP1.2]
                     (6)
 
[F01-OS1.1]
[F02-OS1.2,OP3.1]
2.4.1.2. Note1
2.4.1.3.        (1) [F01-OS1.1,OP1.1]
                     (2)

 

 

 

Note1
Applies to the following text in the Fire Code: “combustible materials shall not be stored with ashes in the same receptacle”.

[F01-OS1.1]
Applies to the following text in the Fire Code: “Ashes shall be stored in receptacles that conform to Sentence (3)”.

                     (3) [F03-OS1.2,OP1.2]
2.4.1.4.        (1) [F03-OS1.2,OP1.2]
2.4.1.5. [F01-OS1.1,OP1.1]
2.4.1.6. [F43-OS1.2,OP1.2]
Subsection 2.4.2 RESERVED
Subsection 2.4.3. Smoking
2.4.3.1.        (1) [F01-OS1.1,OP1.1]
                     (2) [F02-OS1.2,OP1.2]
2.4.3.2. [F81-OS1.1,OP1.1]
Subsection 2.4.4 Open Flames
2.4.4.1.        (1) [F01-OS1.1,OP1.1]
                     (2) Note1
                     (3) [F01-OS1.1,OP1.1]
2.4.4.2.        (1) Note1
                     (2) [F01-OS1.1,OP1.1]
                     (3) [F01-OS1.1,OP1.1]
                     (4) [F02,F12-OS1.2,OP1.2]
2.4.4.3. [F01-OS1.1,OP1.1]
Subsection 2.4.5. Use of Hazardous Materials
2.4.5.1. [F01-OS1.1,OP1.1]
2.4.5.2. Note1
Subsection 2.4.6. Electrical Hazards
2.4.6.1. [F01-OS1.1,OP1.1]
Subsection 2.4.7. Vacant Buildings
2.4.7.1. [F34-OS1.1,OP1.1]
SECTION 2.5 FIRE DEPARTMENT ACCESS TO BUILDINGS
Subsection 2.5.1. General
2.5.1.1.        (1) Note1
2.5.1.2.        (1) [F12-OS1.2,OP1.2]
                     (2) [F12-OS1.2,OP1.2]
2.5.1.3. [F12-OS1.2,OP1.2]
2.5.1.4.   [F12-OS1.2,OP1.2]
SECTION    2.6 SERVICE EQUIPMENT
Subsection 2.6.1. Heating, Ventilating and Air-Conditioning
2.6.1.1. [F01-OS1.1,OP1.1]
2.6.1.2. [F01-OS1.1,OP1.1]
2.6.1.3.
 
[F01,F82-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
2.6.1.4.        (1)
 
[F01,F82-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
                     (2)

 

[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2]
[F04-OS1.3,OP1.3]
                     (3) [F82-OS1.1,OS1.2,OS1.3,OP1.1,OP1.2,OP1.3]
2.6.1.5. [F82-OS1.1,OP1.1,OS1.2,OP1.2]
2.6.1.6. RESERVED
2.6.1.7.     
 
[F01-OS1.1]
[F82-OS1.1,OS1.2,OP1.1,OP1.2]
2.6.1.8. [F82-OS1.2,OP1.2]
2.6.1.9.
 
[F01-OS1.1,OP1.1]
[F81-OS1.1,OS1.2,OP1.1,OP1.2]
2.6.1.10.      (1)
 
[F01-OS1.1,OP1.1]
[F02,F03-OS1.2,OP1.2]
2.6.1.11. [F43,F81-OS1.1,OP1.1]
2.6.1.12.      (1)

 

[F01-OS1.1]
[F02,F03,F12-OS1.2,OP1.2]
[F81-OS1.4,OP1.4]
                     (2) Note1
                     (3) Note1
2.6.1.13.


 

[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
[F81-OP1.4]
[F82-OS1.2,OS1.4,OP1.2]
2.6.1.14.      (1) [F12-OS1.2,OP1.2]
                     (2) Note1
Subsection 2.6.2. Solid-Fuel-Burning Appliances
2.6.2.1.
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2]
2.6.2.2.
 
[F01-OS1.1,OP1.1]
[F82-OS1.1,OS1.2,OP1.1,OP1.2]
Subsection 2.6.3. Incinerators
2.6.3.1.        (1) [F01-OS1.1,OP1.1,OP3.1]
[F81-OS1.1,OP1.1]
                     (2)
 

 

 

 

 

 

 

Note1
Applies to the following text in the Fire Code: “the flue venting an incinerator shall not serve as the chute conveying waste material to the incinerator”.

[F01-OS1.1,OP3.1]
[F03-OS1.2]
[F81-OS1.1,OS1.2]
[F82-OS1.1]
Applies to the following text in the Fire Code: “The design, construction, installation, alteration and maintenance of outdoor incinerators shall conform to NFPA 82, “Standard on Incinerators and Waste and Linen Handling Systems and Equipment””.

2.6.3.2.
 
[F01-OS1.1,OP1.1,OP3.1]
[F82-OS1.2,OP1.2]
2.6.3.3.        (1) [F82-OS1.1,OP1.1]
                     (2) [F01,F82-OS1.1,OP1.1]
2.6.3.4.        (1) [F01,F02,F03,F81-OS1.1,OS1.2,OP1.1,OP1.2,OP3.1]
                     (2) Note1
Subsection 2.6.4. Electrical Equipment Vaults
2.6.4.1. Note1
2.6.4.2. [F34-OS1.1,OP1.1]
SECTION 2.7 SAFETY TO LIFE
Subsection 2.7.1. Means of Egress
2.7.1.1. [F10-OS1.5]
2.7.1.2. [F10-OS1.5]
2.7.1.3. [F10-OS1.5]
2.7.1.4.        (1) [F10-OS1.5]
                     (2) [F10-OS1.5]
                     (3) [F10-OS1.5]
                     (4) Note1
                     (5) Note1
                     (6) Note1
                     (7) [F10-OS1.5]
2.7.1.5.        (1) [F10-OS1.5]
                     (2) [F10-OS1.5]
2.7.1.6.        (1) Note1
                     (2) [F10-OS1.5]
                     (3) [F10-OS1.5]
                     (4) Note1
                     (5) [F10-OS1.5]
                     (6) [F10-OS1.5]
                     (7) [F10-OS1.5]
                     (8) Note1
2.7.1.7.        (1)
  
[F10,F30-OS1.5]
[F12-OS1.2,OP1.2]
                     (2) [F82-OS1.5]
2.7.1.8.        (1)

  

[F10-OS1.5]
[F12-OS1.2,OP1.2]
[F82-OS1.2,OS1.5,OP1.2]
                     (2)

     

[F10-OS1.5]
[F12-OS1.2,OP1.2]
[F82-OS1.2,OS1.5,OP1.2]
2.7.1.9.        (1) [F10-OS1.5]
                     (2) Note1
                     (3) [F10-OS1.5]
                     (4) Note1
                     (5) [F10-OS1.5]
                     (6) [F10-OS1.5]
Subsection 2.7.2. Door Hardware
2.7.2.1.        (1) [F10-OS1.5]
                     (2) [F10-OS1.5]
                     (3) [F10-OS1.5]
                     (4) Note1
                     (5) Note1
2.7.2.2.        (1) [F10-OS1.5]
                     (2) Note1
                     (3) Note1
                     (4) Note1
Subsection 2.7.3. Exit Lighting and Emergency Lighting
2.7.3.1. [F10,F82-OS1.5]
2.7.3.2. [F10-OS1.5]
2.7.3.3.        (1) [F10,F82-OS1.5]
                     (2) [F10,F82-OS1.5]
                     (3) [F10,F82-OS1.5]
                     (4) [F10,F82-OS1.5]
                     (5) [F10,F82-OS1.5]
                     (6) [F10,F82-OS1.5]
Subsection 2.7.4. Indoor Public Amusement Areas
2.7.4.1.        (1)

 

[F01-OS1.1]
[F02-OS1.2]
[F10-OS1.5]
                     (2)
 
[F01-OS1.1]
[F02-OS1.2]
2.7.4.2.        (1) [F10,F36-OS1.5]
SECTION 2.8 EMERGENCY PLANNING
Subsection 2.8.1. General
2.8.1.1.        (1) Note1
                     (2) Note1
                     (3) Note1
                     (4) Note1
2.8.1.2.        (1) [F12-OS1.2,OS1.4,OS1.5,OP1.2,OP1.4]
                     (2) [F12-OS1.2,OS1.4,OS1.5]
                     (3) Note1
2.8.1.3. [F12-OS1.2,OS1.4,OS1.5,OP1.2,OP1.4]
Subsection 2.8.2. Fire Safety Plan
2.8.2.1.        (1)(a)(i)
 
[F11-OS1.5]
[F13-OS1.2,OS1.5,OP1.2]
                              (ii) [F13-OS1.2,OS1.5,OP1.2]
                              (iii) [F11-OS1.5]
                              (iv) [F10-OS1.5]
                              (v) [F12,F36-OS1.5]
                              (vi) [F02-OS1.2,OP1.2]
                          (b) [F12-OS1.2,OS1.5,OP1.2]
                          (c) [F12-OS1.2,OS1.5,OP1.2]
                          (d) [F12-OS1.2,OS1.5,OP1.2]
                          (e) [F10,F12-OS1.5]
                          (f) [F01-OS1.1,OP1.1]
                          (g) [F82-OS1.1,OS1.2,OP1.1,OP1.2]
                          (h)
  

  

 

[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
[F10,F11,F36-OS1.5]
[F12-OS1.2,OS1.5]
[F13-OS1.2,OS1.5,OP1.2]
[F82-OS1.1,OS1.2,OP1.1,OP1.2]
                     (2) Note1
                     (3) [F12-OS1.2,OS1.5,OP1.2]
                     (4) Note1
                     (5) Note1
2.8.2.2.        (1)

 

[F01-OS1.1]
[F02-OS1.2]
[F12-OS1.2,OS1.4,OS1.5]
                     (2)

 

[F01-OS1.1]
[F02-OS1.2]
[F12-OS1.2,OS1.4,OS1.5]
2.8.2.3.        (1)
 
[F2,F3,F12,F13-OS1.2,OS1.5,OP1.2]
[F11-OS1.5]
2.8.2.4.

 

 

[F01-OS1.1]
[F02-OS1.2,OP1.2]
[F10,F11-OS1.5]
[F12,F13-OS1.2,OS1.4,OS1.5,OP1.2,OP1.4]
[F82-OS1.1,OS1.2,OS1.4,OS1.5,OP1.1,OP1.2,OP1.4]
2.8.2.5.        (1) [F10-OS1.5]
                     (2)(a) [F10-OS1.5]
                          (b) [F12-OS1.2,OS1.5,OP1.2]
                     (3) [F13-OS1.2,OP1.2]
Subsection 2.8.3. Fire Drills
2.8.3.1.        (1) [F10-OS1.5]
[F12-OS1.2,OS1.5,OP1.2]
                     (2) Note1
2.8.3.2.        (1) [F10-OS1.5]
[F12-OS1.2,OS1.5,OP1.2]
                     (2) [F10-OS1.5]
[F12-OS1.2,OS1.5,OP1.2]
                     (3) Note1
SECTION 2.9 TENTS AND AIR-SUPPORTED STRUCTURES
Subsection 2.9.1. General
2.9.1.1. Note1
2.9.1.2. Note1
Subsection 2.9.2. Materials
2.9.2.1. [F82-OS1.2,OS1.5,OP1.2]
Subsection 2.9.3. Fire Hazards and Control
2.9.3.1. [F02-OS1.2]
2.9.3.2. [F01-OS1.1,OP1.1]
2.9.3.3.        (1) Note1
2.9.3.4.        (1)
 
[F10-OS1.5]
[F12-OS1.2,OS1.5]
2.9.3.5.
 
[F11-OS1.5]
[F13-OS1.2,OP1.2]
SECTION 2.10 DAY CARE CENTRES
Subsection 2.10.1. Application
2.10.1.1.      (1) Note1
                     (2) Note1
Subsection 2.10.2. Combustible Materials
2.10.2.1. [F02-OS1.2,OP1.2]
2.10.2.2. [F02,F03-OS1.2,OP1.2]
2.10.2.3.

 

 

 

 

Note1
Applies to the following text in the Fire Code: “Flammable liquids and combustible liquids shall be stored in conformance with Part 4”.

[F01,F34-OS1.1]
Applies to the following text in the Fire Code: “Flammable liquids and combustible liquids shall be stored __ in areas inaccessible to children”.

Subsection 2.10.3. Staffing
2.10.3.1. [F12-OS1.5]
SECTION 2.11 INSULATION AND RE-INSULATION
Subsection 2.11.1. General
2.11.1.1. Note1
2.11.1.2. [F02-OS1.2,OP1.2]
2.11.1.3. [F03-OS1.2,OP1.2]
SECTION 2.12 COVERED MALLS
Subsection 2.12.1. General
2.12.1.1.       (1)

 

[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
[F10-OS1.5]
                      (2) Note1
2.12.1.2. [F02-OS1.2,OP1.2]
2.12.1.3.      (1) [F03-OS1.2,OP3.1]
                     (2) Note1
2.12.1.4. Note1
2.12.1.5.

 

[F11-OS1.5]
[F12-OS1.2,OS1.5,OP1.2]
[F13-OS1.2,OP1.2]
2.12.1.6. Note1
2.12.1.7. [F01,F81-OS1.1,OP1.1]
SECTION 2.13 INSTALLATION OF SMOKE ALARMS
Subsection 2.13.1. Scope
2.13.1.1.       (1) Note1
                      (2) Note1
                      (3) Note1
Subsection 2.13.2. Installation
2.13.2.1.      (1) [F11,F81-OS1.4,OS1.5]
                     (2) [F11-OS1.5]
                     (3) [F11-OS1.5]
                     (4)

 

 

 

 

Note1
Applies to the following text in the Fire Code: “Smoke alarms __ shall have no disconnect switch between the overcurrent device and the smoke alarm”.

[F11-OS1.5]
Applies to the following text in the Fire Code: “Smoke alarms shall be installed by permanent connections to an electrical circuit”.

                     (5) Note1
                     (6) Note1
                     (7) Note1
SECTION 2.14 OUTDOOR PUBLIC AMUSEMENT AREAS
Subsection 2.14.1. General
2.14.1.1. Note1
2.14.1.2.       (1)

 

[F01-OS1.1]
[F02-OS1.2]
[F10-OS1.5]
                      (2)
 
[F01-OS1.1]
[F02-OS1.2]
2.14.1.3. [F01-OS1.1]
2.14.1.4.       (1) [F10,F36-OS1.5]
2.14.1.5.       (1)(a)
 
[F11-OS1.2,OS1.5]
[F13-OS1.2,OS1.5,OP1.2]
                           (b) [F10-OS1.5]
                           (c) [F12-OS1.2,OS1.5,OP1.2]
                           (d)
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
                       (2) Note1
SECTION 2.15 PORTABLE OXYGEN SYSTEMS
Subsection 2.15.1. General
2.15.1.1. Note1
2.15.1.2.
 
[F01-OS1.1]
[F02,F03-OS1.2,OP1.2]
 

 

 

Table 3
Objectives and Functional Statements Attributed to the
Acceptable Solutions in Part 3 of Division B

 

 

Acceptable Solution Objectives and Functional Statements
SECTION 3.1 GENERAL
Subsection 3.1.1. Scope
3.1.1.1. Note1
SECTION 3.2 WOOD PRODUCTS
Subsection 3.2.1. Woodworking Plants
3.2.1.1. Note1
3.2.1.2. [F01-OS1.1,OP1.1]
3.2.1.3. Note1
3.2.1.4. [F01,F81-OS1.1,OP1.1]
3.2.1.5. [F02,F12-OS1.2,OP1.2]
3.2.1.6. Note1
3.2.1.7. Note1
Subsection 3.2.2. Outdoor Storage of Lumber and Forest Products
3.2.2.1. Note1
3.2.2.2.        (1)
 
[F03,F12-OP1.2,OP3.1]
[F04-OS1.3,OP1.2]
                     (2) Note1
3.2.2.3.        (1)
 
[F03,F12-OP1.2,OP3.1]
[F04-OS1.3,OP3.1]
                     (2) Note1
3.2.2.4.        (1) [F03-OP1.2,OP3.1]
                     (2) [F03-OP1.2,OP3.1]
                     (3) [F12-OS1.2,OP1.2]
3.2.2.5.        (1) [F03-OP3.1]
                     (2) Note1
3.2.2.6. [F03-OP1.2,OP3.1]
3.2.2.7. [F03-OP1.2,OP3.1]
3.2.2.8.
 
[F02-OP3.1,OS1.2]
[F03-OP1.2]
3.2.2.9.

 

[F01-OS1.1]
[F06-OS1.4,OP1.4]
[F32-OS3.3]
3.2.2.10. [F02-OS1.2,OP1.2]
3.2.2.11. [F02,F12-OS1.2,OP1.2]
3.2.2.12.      (1) [F12-OS1.2,OP3.1]
                     (2) [F12-OS1.2,OP1.2,OP3.1]
3.2.2.13.      (1) [F12-OS1.2,OP1.2,OP3.1]
                     (2) [F12-OS1.2,OP1.2,OP3.1]
3.2.2.14.
 
[F02,F03-OP1.2]
[F12-OS1.2,OP1.2,OP3.1]
3.2.2.15. [F12-OS1.2,OP1.2,OP3.1]
3.2.2.16. Note1
3.2.2.17. [F01-OS1.1,OP1.1,OP3.1]
3.2.2.18.
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP3.1]
3.2.2.19.
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2,OP3.1]
3.2.2.20. [F03-OS1.2,OP1.2]
3.2.2.21. Note1
3.2.2.22. [F01-OS1.1,OP1.1]
3.2.2.23. [F13-OS1.2,OP1.2,OP3.1]
3.2.2.24.      (1) [F02,F12-OS1.2,OP1.2]
                     (2) [F12,F81-OS1.4,OP1.4]
                     (3) [F12-OS1.2,OP1.2]
                     (4) [F02,F12-OS1.2,OP1.2]
3.2.2.25 Note1
3.2.2.26. [F12-OS1.2,OS1.3,OP1.2,OP3.1]
3.2.2.27. [F12-OS1.2,OP1.2,OP3.1]
Subsection 3.2.3. Outdoor Storage of Wood Chips
3.2.3.1. Note1
3.2.3.2. [F12-OP1.2,OP3.1]
3.2.3.3. [F03-OP1.2,OP3.1]
3.2.3.4.        (1) [F03-OP1.2,OP3.1]
                     (2) Note1
3.2.3.5. [F12-OS1.2,OP1.2,OP3.1]
3.2.3.6.        (1)
 
[F03-OP1.2]
[F12-OS1.2,OP1.2,OP3.1]
                     (2)
 
[F03-OP1.2]
[F12-OS1.2,OP1.2,OP3.1]
3.2.3.7. [F12-OS1.2,OP1.2,OP3.1]
3.2.3.8.        (1) [F12-OS1.2,OP1.2,OP3.1]
                     (2) Note1
3.2.3.9. [F12-OS1.2,OP1.2,OP3.1]
3.2.3.10. Note1
3.2.3.11. [F12-OS1.2,OP1.2]
3.2.3.12.      (1) [F12-OS1.2,OP1.2,OP3.1]
                     (2)
 
[F02-OS1.2,OP1.2]
[F12-OP1.2,OP3.1]
                     (3)
 
[F02,OS1.2]
[F12-OP1.2,OP3.1]
3.2.3.13. Note1
SECTION 3.3 STORAGE
Subsection 3.3.1. Indoor Tire Storage
3.3.1.1. Note1
3.3.1.2. [F02,F12-OS1.2,OP1.2]
3.3.1.3.        (1) [F02-OS1.2,OP1.2]
                     (2) [F02-OS1.2,OP1.2]
3.3.1.4. [F02-OS1.2,OP1.2]
3.3.1.5. [F03,F12-OS1.2,OP1.2]
3.3.1.6. [F04-OS1.3,OP1.3]
3.3.1.7. Note1
3.3.1.8.        (1) [F02,F04-OS1.2,OP1.2]
                     (2) [F02,F04-OS1.2,OP1.2]
3.3.1.9. [F12-OS1.2,OP1.2]
3.3.1.10.      (1)

 

 

 

Note1
Applies to the following text in the Fire Code: “In addition to the requirements of Section 6.2”.

[F02,F12-OS1.2,OP1.2]
Applies to the following text in the Fire Code: “multi-purpose dry chemical portable extinguishers … does not exceed 25 m”.

Subsection 3.3.2. Indoor General Storage
3.3.2.1.       (1) Note1
                    (2) Note1
3.3.2.2.       (1) [F02,F12-OS1.2,OP1.2]
                    (2) [F02,F12-OS1.2,OP1.2]
                    (3) [F02,F12-OS1.2,OP1.2]
                    (4) [F04-OS1.2,OP1.2,OS1.5]
3.3.2.3.       (1) [F02-OS1.2,OP1.2]
                    (2) [F02,F04-OS1.2,OS1.3,OP1.2,OP1.3]
3.3.2.4. [F12-OS1.2,OP1.2]
3.3.2.5. [F12-OS1.2,OP1.2]
3.3.2.6.       (1) [F12-OS1.2,OP1.2]
                    (2)

 

[F10-OS1.5]
[F12-OS1.2,OP1.2]
[F82-OS1.4]
                    (3)
 
[F10-OS1.5]
[F12-OS1.2,OP1.2]
                    (4)
 
[F06-OS1.5]
[F12-OS1.2,OP1.2]
                    (5) Note1
                    (6) [F12-OS1.2,OP1.2]
3.3.2.7. [F04-OS1.3,OP1.3]
3.3.2.8. [F03-OS1.2,OP1.2]
3.3.2.9.
 
[F02-OS1.2,OP1.2]
[F03-OP3.1]
3.3.2.10.    (1) [F02-OS1.2,OP1.2]
                   (2) [F02-OS1.2,OP1.2]
                   (3) [F02-OS1.2,OP1.2]
3.3.2.11. [F01-OS1.1,OP1.1]
Subsection 3.3.3. Indoor Storage of Ammonium Nitrate
3.3.3.1. Note1
3.3.3.2.      (1) Note1
                   (2) Note1
                   (3)
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2]
                   (4)
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
                   (5) [F1,F81-OS1.1,OP1.1]
                   (6) [F03-OP3.1]
                   (7) Note1
                   (8) Note1
                   (9) Note1
                   (10) [F03-OS1.2,OP1.2]
3.3.3.3.      (1) [F01,F81-OS1.1,OP1.1]
                   (2) Note1
                   (3)
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2]
                   (4) [F01-OS1.1,OP1.1]
3.3.3.4. [F02,F12-OS1.2,OP1.2]
3.3.3.5.      (1)
 
[F02-OS1.2,OP1.2]
[F04-OS1.3]
                   (2) [F02,F12-OS1.2,OP1.2]
                   (3) Note1
                   (4)
 
[F12-OS1.2,OP1.2]
[F81-OS1.1,OP1.1]
                   (5) [F01-OS1.1,OP1.1]
                   (6) [F81-OS1.1,OP1.1]
3.3.3.6.      (1) [F02-OS1.2,OP1.2]
                   (2) Note1
3.3.3.7.      (1) Note1
                   (2) [F01-OS1.1,OP1.1]
                   (3) [F01-OS1.1,OP1.1]
                   (4) [F01-OS1.1,OP1.1]
                   (5) [F01-OS1.1,OP1.1]
3.3.3.8. Note1
3.3.3.9.      (1) Note1
                   (2) [F81-OS1.1,OP1.1]
3.3.3.10. [F01-OS1.1,OP1.1]
SECTION 3.4 INDUSTRIAL TRUCKS
Subsection 3.4.1. General
3.4.1.1. [F01-OS1.1,OP1.1]
Subsection 3.4.2. Industrial Trucks
3.4.2.1.      (1) [F03-OS1.2,OP1.2]
                   (2) [F01-OS1.1,OP1.1]
                   (3) [F01-OS1.1,OP1.1]
                   (4) [F02,F12-OS1.2,OP1.2]
                   (5) Note1
3.4.2.2.      (1)
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2]
                   (2) [F02,F12-OS1.2,OP1.2]
                   (3) [F01,F81-OS1.1,OP1.1]
3.4.2.3.      (1) [F01,F81-OS1.1,OP1.1]
SECTION 3.5 SALVAGE SHOPS AND SALVAGE YARDS
Subsection 3.5.1. General
3.5.1.1. [F03-OS1.2,OP1.2]
3.5.1.2. Note1
3.5.1.3.
 
[F01-OS1.1,OP1.1]
[F02-OS1.2]
3.5.1.4. [F12-OS1.2,OP1.2]
3.5.1.5. [F02,F12-OS1.2,OP1.2]
3.5.1.6. Note1
3.5.1.7. [F12-OS1.2,OP1.2]
3.5.1.8. Note1
3.5.1.9. [F01-OS1.1,OP1.1]
3.5.1.10. [F13-OP1.2,OS1.2]
Subsection 3.5.2. Piling
3.5.2.1.
 
[F02,F12-OS1.2,OP1.2,OP3.1]
[F03-OP3.1]
3.5.2.2.
 
[F03-OP1.2,OP3.1]
[F12-OS1.2,OP1.2,OP3.1]
3.5.2.3.
 
[F03-OS1.2,OP1.2,OP3.1]
[F12-OP1.2,OP3.1]
3.5.2.4.      (1) [F02,F12,F81-OS1.2,OP1.2]
                   (2) [F12-OS1.2,OP1.2]
                   (3) [F12-OS1.2,OP1.2]
Subsection 3.5.3. Outdoor Tire Storage Yards
3.5.3.1.      (1) Note1
                   (2) Note1
3.5.3.2.      (1) Note1
                   (2) Note1
                   (3) [F01-OS1.1,OH5,OP1.1]
                   (4)

 

[F01-OS1.1,OH5,OP1.1]
[F06-OS1.2]
[F12-OS1.2,OS3.3,OP1.2]
3.5.3.3.      (1) Note1
                   (2) [F12-OS1.2,OH5,OP1.2]
                   (3) [F12-OS1.2,OH5,OP1.2]
                   (4) [F13-OS1.2,OH5,OP1.2]
3.5.3.4.      (1)
 
[F02,F12-OS1.2,OH5,OP1.2]
[F04-OS1.3]
                   (2) [F03,F12-OS1.2,OH5,OP1.2]
3.5.3.5.      (1)
 
[F01-OH5,OP1.1]
[F03-OP3.1]
                   (2)
 
[F01-OH5]
[F03-OP3.1]
                   (3) [F03,F12-OH5,OP1.2,OP3.1]
3.5.3.6.      (1) [F03-OH5,OP1.2,OP3.1]
3.5.3.7.      (1) [F03-OH5,OP1.2,OP3.1]
                   (2) [F02-OH5,OP1.2,OP3.1]
                   (3) [F03-OH5,OP1.2,OP3.1]
3.5.3.8. Note1
3.5.3.9.      (1) [F12-OS1.2,OH5,OP1.2,OP3.1]
                   (2) [F12-OS1.2,OH5,OP1.2,OP3.1]
                   (3) Note1
3.5.3.10.    (1) [F34-OH5,OP1.1]
                   (2) [F34-OH5,OP1.1]
                   (3) [F12-OS1.2,OH5,OP1.2]
                   (4) [F12-OS1.2,OH5,OP1.2]
                   (5) [F12-OS1.2,OH5,OP1.2]
                   (6) [F34-OH5,OP1.1]
3.5.3.11.    (1) [F12-OS1.2,OH5,OP1.2]
                   (2) [F02-OS1.2,OH5,OP1.2]
                   (3) [F02-OS1.2,OH5,OP1.2]
                   (4) [F12-OS1.2,OH5,OP1.2]
3.5.3.12. Note1
3.5.3.13. [F02,F12-OS1.2,OH5,OP1.2]
SECTION 3.6 DRY CLEANING AND DYEING PLANTS
Subsection 3.6.1. Dry Cleaning and Dyeing Plants
3.6.1.1.      (1)
 

 

[F01-OS1.1,OP1.1]
[F02-OS1.2,OS1.3,OP1.2,OP1.3]
[F03-OS1.2,OP1.2]
[F81-OS1.1,OS1.2,OS1.3,OP1.1,OP1.2,OP1.3]
                   (2) Note1
                   (3)
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
                   (4) Note1
                   (5) Note1
SECTION 3.7 BOWLING ALLEYS
Subsection 3.7.1. Resurfacing
3.7.1.1.
 
[F01-OS1.1,OP1.1]
[F12-OS1.2,OP1.2]
3.7.1.2.
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2]
Subsection 3.7.2. Pin Refinishing
3.7.2.1.      (1)
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2]
                   (2) Note1
                   (3) [F01-OS1.1,OP1.1]
Subsection 3.7.3. Flammable Liquids and Combustible Liquids
3.7.3.1. Note1
3.7.3.2.      (1) [F01-OS1.1,OP1.1]
                   (2) [F03-OS1.2,OP1.2]
 

 

 

Table 4
Objectives and Functional Statements Attributed to the
Acceptable Solutions in Part 4 of Division B
 

 

 

Acceptable Solution Objectives and Functional Statements
SECTION 4.1 APPLICATION
Subsection 4.1.1. Scope and Application
4.1.1.1.       (1) Note1
                    (2) Note1
4.1.1.2.       (1) Note1
                    (2) Note1
4.1.1.3. Note1
4.1.1.4.       (1) Note1
                    (2) Note1
                    (3) Note1
                    (4) Note1
Subsection 4.1.2. Classification
4.1.2.1.       (1) Note1
                    (2) Note1
                    (3) Note1
4.1.2.2. Note1
4.1.2.3.       (1) Note1
                    (2) Note1
Subsection 4.1.3. Flash Point
4.1.3.1.       (1) [F01-OS1.1]
                    (2) [F01-OS1.1]
                    (3) [F01-OS1.1]
                    (4) [F01-OS1.1]
Subsection 4.1.4. Electrical Installations
4.1.4.1.       (1) [F01-OS1.1,OP1.1]
                    (2) [F01-OS1.1,OP1.1]
Subsection 4.1.5. Fire Prevention and Protection
4.1.5.1. Note1
4.1.5.2. RESERVED
4.1.5.3. [F01-OS1.1,OP1.1]
4.1.5.4. [F01-OS1.1,OP1.1]
4.1.5.5.        (1) [F01-OS1.1,OP1.1]
                     (2) Note1
4.1.5.6. Note1
4.1.5.7. [F12-OS1.2,OP1.2,OP3.1]
4.1.5.8. Note1
4.1.5.9.         (1) [F01,F43-OS1.1,OP1.1]
                      (2) [F01,F43-OS1.1]
                      (3)
 
[F02-OS1.2,OP1.2]
[F43-OS1.1,OP1.1]
                      (4)(a) [F01-OS1.1,OP1.1]
                           (b)
 
[F01-OS1.1,OP1.1]
[F13-OS1.4,OP1.4]
                           (c) [F03-OS1.2,OP1.2]
                           (d)
 
[F01-OS1.1]
[F12-OS1.2,OS1.5,OP1.2]
                           (e) [F02-OS1.2,OP1.2]
                           (f) [F02,F20-OS1.2,OS1.3,OP1.2,OP1.3]
                           (g) [F13-OS1.1,OP1.1]
                       (5) Note1
4.1.5.10. [F82-OS1.1,OS1.2,OS1.4,OP1.1,OP1.2,OP1.4]
Subsection 4.1.6. Spill Control and Drainage Systems
4.1.6.1.          (1) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2,OP3.1]
                       (2) Note1
                       (3) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                       (4)(a) [F44-OS1.2,OP3.1]
                            (b) [F44-OH5,OP3.1]
                            (c) [F44-OS1.5]
                            (d) [F44-OS1.2,OP3.1]
                            (e) [F44-OS1.4,OP1.4]
                            (f) [F44-OS1.2,OP1.2]
                            (g) [F44-OS1.2,OP1.2]
                            (h) [F44-OS1.2,OP1.2]
                            (i) [F44-OS1.2,OP1.2]
                            (j) [F44-OS1.2,OP1.2]
4.1.6.2.          (1)(a) [F44-OS1.1,OS1.2,OS1.4,OH5,OP1.1,OP1.2,OP1.4]
                            (b) [F44-OS1.1,OS1.2,OS1.4,OP1.1,OP1.2,OP1.4,OP3.1]
                       (2) [F03-OS1.2,OP1.2]
4.1.6.3.          (1) [F44,F82-OS1.1,OS1.2,OP1.1,OP1.2]
                       (2) [F44-OS1.1,OS1.2,OP1.1,OP1.2]
                       (3)(a)
 
[F03-OP3.1]
[F44-OS1.1,OS1.2,OP1.1,OP1.2]
                            (b)

 

[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
[F44-OS1.1,OS1.2,OP1.1,OP1.2]
                       (4) Note1
4.1.6.4.          (1)
 
[F02-OS1.2,OP1.2]
[F44-OS1.2,OP1.2,OP3.1]
                       (2)(a) [F43,F81-OS1.1,OP1.1]
                            (b) [F01-OS1.1,OP1.1]
                            (c) [F01-OS1.1,OP1.1]
                            (d)

 

[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
[F44-OS1.1,OS1.2,OP1.1,OP1.2]
                            (e) [F12-OS1.2,OP1.2]
                            (f) [F12-OS1.2,OP1.2]
                            (g) [F82-OS1.1,OS1.2,OP1.1,OP1.2]
                            (h) [F12-OS1.1,OS1.2,OP1.1,OP1.2]
                        (3) [F12-OS1.1,OS1.2,OP1.1,OP1.2]
Subsection 4.1.7. Ventilation
4.1.7.1. [F01-OS1.1,OP1.1]
4.1.7.2.           (1) [F01-OS1.1,OP1.1]
                        (2) Note1
                        (3) [F01-OS1.1,OP1.1]
                        (4) [F01-OS1.1,OP1.1]
                        (5) [F01,F11-OS1.1,OP1.1]
                        (6) [F01-OS1.1,OP1.1]
4.1.7.3.           (1) Note1
                        (2) [F01-OS1.1,OP1.1]
                        (3) [F01-OS1.1,OP1.1]
4.1.7.4.           (1)(a) [F01-OS1.1,OP1.1]
                             (b)
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2,OP3.1]
4.1.7.5.           (1) [F03-OS1.2,OP1.2]
                        (2) [F01-OS1.1,OP1.1]
                        (3) [F01,F44-OS1.1,OP1.1]
4.1.7.6.           (1) [F01,F11-OS1.1,OP1.1]
4.1.7.7. Note1
4.1.7.8. [F82-OS1.1,OP1.1]
Subsection 4.1.8. Handling of Flammable and Combustible Liquids
4.1.8.1.           (1) Note1
                        (2) [F43-OS1.1,OP1.1]
                        (3) Note1
4.1.8.2.           (1) [F01-OS1.1,OP1.1]
                        (2) [F01-OS1.1,OP1.1]
                        (3) Note1
                        (4) [F22-OS1.1,OP1.1]
4.1.8.3.           (1) [F43-OS1.1,OP1.1]
                        (2) [F01,F20,F81-OS1.1,OP1.1]
4.1.8.4.           (1) [F01,F43,F81-OS1.1]
                        (2) [F43-OS1.1,OP1.1]
SECTION 4.2 CONTAINER STORAGE AND HANDLING
Subsection 4.2.1. Scope
4.2.1.1.           (1) Note1
                        (2) Note1
                        (3) Note1
                        (4) Note1
                        (5) Note1
Subsection 4.2.2. General
4.2.2.1.           (1) Note1
                        (2) Note1
4.2.2.2.
 
[F04-OS1.2,OS1.5,OH5,OP1.2]
[F20 OS1.1,OS1.2,OH5,OP1.1,OP1.2]
4.2.2.3.           (1)

 

[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
[F43-OS3.4]
                        (2) Note1
Subsection 4.2.3. Containers and Portable Tanks
4.2.3.1.           (1) [F01,F04,F20,F43,F80,F81-OS1.1,OP1.1]
4.2.3.2.           (1)
 
[F01,F81-OS1.1,OP1.1]
[F12-OS1.1,OS1.2,OP1.1,OP1.2]
                        (2)
 
[F01,F81-OS1.1,OP1.1]
[F12-OS1.1,OS1.2,OP1.1,OP1.2]
4.2.3.3.           (1) Note1
Subsection 4.2.4. Assembly and Residential Occupancies
4.2.4.1.           (1) Note1
4.2.4.2.           (1) Note1
                        (2) [F02-OS1.2,OP1.2]
                        (3) [F02-OS1.2,OP1.2]
                        (4) [F02,F03-OS1.2,OP1.2]
4.2.4.3.
 
[F01-OS1.1,OP1.1]
[F12-OS1.2,OP1.2]
4.2.4.4. [F03-OS1.2,OP1.2]
4.2.4.5. [F02-OS1.2,OP1.2]
4.2.4.6. [F02-OS1.2,OP1.2]
Subsection 4.2.5. Mercantile Occupancies
4.2.5.1.           (1) Note1
                        (2) [F02-OS1.2,OP1.2]
                        (3) [F02-OS1.2,OP1.2]
                        (4) Note1
                        (5) [F02,F03-OS1.2,OP1.2]
4.2.5.2.           (1) [F01,F43-OS1.1,OP1.1]
                        (2)
 
[F04-OS1.5,OP1.2]
[F20-OS1.1,OS1.2,OP1.1]
                        (3) Note1
4.2.5.3.
 
[F01-OS1.1,OP1.1]
[F02,F03,F44-OS1.2,OP1.2]
Subsection 4.2.6.
 
Business and Personal Services, Educational and Care or Detention Occupancies
4.2.6.1.           (1) Note1
4.2.6.2.           (1)

 

 

 

 

 

[F01,F43-OS1.1,OP1.1]
Applies to the following text in the opening line of Sentence (1) in the Fire Code: “Except as permitted in Article 4.2.6.3., flammable liquids and combustible liquids shall be kept in closed containers”.

[F02,F03-OS1.2,OP1.2]
Applies to the following text in the Fire Code:“Except as permitted in Article 4.2.6.3., flammable liquids and combustible liquids shall be __ stored (a) …, or (b) … Subsection 4.2.9.”

4.2.6.3.           (1) Note1
                        (2) Note1
4.2.6.4.
 
[F01,F04,F43-OS1.1,OP-1]
[F02-OS1.2,OP1.2]
4.2.6.5. Note1
Subsection 4.2.7. Industrial Occupancies
4.2.7.1. Note1
4.2.7.2.           (1) [F02,F03-OS1.2,OP1.2]
4.2.7.3. [F03-OS1.2,OP1.2]
4.2.7.4.           (1)
 
[F01-OS1.1]
[F02,F03-OS1.2,OP1.2]
                        (2)
 
[F01-OS1.1,OP1.1]
[F02,OS1.2,OP1.2]
4.2.7.5.           (1)


 

[F01-OS1.1]
[F02,F03-OS1.2,OP1.2]
[F04-OS1.2,OS1.5,OH5,OP1.2]
[F20-OS1.1,OS1.2]
                        (2) [F03-OS1.2,OP1.2]
                        (3) Note1
                        (4) Note1
4.2.7.6. Note1
4.2.7.7.           (1) [F02-OS1.2,OP1.2]
4.2.7.8.           (1)

 

 

 


 

[F02,F81-OS1.2,OP1.2]
Applies to the following text in the Fire Code: “The clearance between the top of storage and the __ sprinkler head deflectors or other overhead fire protection system components shall be not less than 450 mm”.

[F04-OS1.3,OP1.3]
Applies to the following text in the Fire Code: “The clearance between the top of storage and the lowest structural members __ shall be not less than 450 mm”.

                         (2)
 
[F10-OS1.5]
[F81,F82-OS1.1,OP1.1]
4.2.7.9. Note1
4.2.7.10. Note1
4.2.7.11. Note1
4.2.7.12. Note1
4.2.7.13. Note1
Subsection 4.2.8. Incidental Use
4.2.8.1. Note1
4.2.8.2.           (1) [F02-OS1.2,OP1.2]
                        (2) [F02-OS1.2,OP1.2]
                        (3) [F02-OS1.2,OP1.2]
4.2.8.3.           (1)(a) [F01-OS1.1,OP1.1]
                             (b) Note1
                             (c) Note1
                             (d) Note1
                             (e) Note1
4.2.8.4.           (1) [F02,F03-OS1.2,OP1.2]
                        (2) Note1
                        (3) Note1
                        (4) [F02-OS1.2,OP1.2]
                        (5) Note1
                        (6) Note1
Subsection 4.2.9. Rooms for Container Storage and Dispensing
4.2.9.1.           (1) [F02-OS1.2,OP1.2]
                        (2) [F02,F03-OS1.2,OP1.2]
                        (3) Note1
4.2.9.2.           (1) [F44-OS1.1,OS1.2,OP1.1,OP1.2]
                        (2) Note1
4.2.9.3. Note1
4.2.9.4.

 
[F10-OS1.5]
[F12-OS1.2,OP1.2]
[F81,F82-OS1.1,OP1.1]
4.2.9.5. [F01,F43-OS1.1]
4.2.9.6.           (1) [F02-OS1.3,OP1.3]
                        (2) [F02-OS1.3,OP1.3]
4.2.9.7. Note1
4.2.9.8.           (1) Note1
                        (2)
 
[F03-OS1.2,OP1.2]
[F10-OS1.5]
                        (3) [F10-OS1.5]
                        (4) [F05-OS1.5]
                        (5) [F10-OS1.5]
Subsection 4.2.10. Cabinets for Container Storage
4.2.10.1. [F01,F43-OS1.1,OP1.1]
4.2.10.2. [F02-OS1.2,OP1.2]
4.2.10.3.         (1) [F02-OS1.2,OP1.2]
                        (2) [F02-OS1.2,OP1.2]
                        (3) [F02-OS1.2,OP1.2]
4.2.10.4. [F01-OS1.1,OP1.1]
4.2.10.5.         (1)

 

[F01-OS1.1]
[F03-OS1.2,OP1.2]
[F44-OS1.1,OP1.1]
4.2.10.6.         (1)
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2]
Subsection 4.2.11. Outdoor Container Storage
4.2.11.1.         (1) [F02,F03-OS1.2,OP3.1]
                        (2) [F02,F03-OS1.2,OP3.1]
4.2.11.2. Note1
4.2.11.3. [F12-OP3.1]
4.2.11.4. Note1
4.2.11.5.         (1) [F34-OS1.1]
SECTION 4.3 TANK STORAGE
Subsection 4.3.1. Design, Construction and Use of Storage Tanks
4.3.1.1. Note1
4.3.1.2.           (1) [F01,F20,F43,F80,F81-OS1.1,OP1.1]
                        (2) Note1
                        (3) Note1
                        (4) Note1
                        (5) Note1
                        (6) Note1
                        (7) Note1
                        (8)
 
[F20,F80,F81-OP1.1]
[F43-OS1.1,OP1.1,OP3.1]
                        (9) Note1
4.3.1.3.           (1) [F01,F20,F43,F80,F81-OS1.1,OP1.1]
                        (2) [F01,F20,F43,F80,F81-OS1.1,OP1.1]
                        (3) Note1
4.3.1.4. Note1
4.3.1.5. [F80-OS1.1,OP1.1]
4.3.1.6. [F04-OS1.2,OP1.2]
4.3.1.7.
 
[F12-OS1.2,OP1.2]
[F81-OS1.1,OP1.1]
4.3.1.8.           (1) [F43-OS1.1,OP1.1]
4.3.1.9. [F01,F20,F43,F80,F81-OS1.1,OP1.1]
4.3.1.10.         (1) [F01,F20,F43-OS1.1,OP1.1]
                        (2) [F01,F20,F43-OS1.1,OP1.1]
                        (3) [F01,F20,F43-OS1.1,OP1.1]
                        (4) Note1
Subsection 4.3.2. Installation of Outside Aboveground Storage Tanks
4.3.2.1.           (1) Note1
                        (2) [F03-OS1.2,OP3.1]
                        (3) [F03-OS1.2,OP3.1]
                        (4) [F03-OS1.2,OP3.1]
                        (5) [F03-OS1.2,OP3.1]
                        (6) Note1
                        (7) Note1
                        (8) [F03-OS1.2,OP3.1]
4.3.2.2.           (1)
 

 

 

 

 

 

 

Note1
Applies to the following text in the Fire Code: “Except as required in Sentences (2) and (3) and in Article 4.3.2.3.”

[F03,F12-OP1.2]
Applies to the following text in the Fire Code: “the minimum distance between every combination of two aboveground storage tanks shall be 0.25 times the sum of their diameters”.

[F82-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “the minimum distance between every combination of two aboveground storage tanks shall be __ not less than 1 m”.

                        (2) [F82-OS1.1,OP1.1]
                        (3) [F03-OP1.2]
4.3.2.3.           (1) [F03-OS1.2,OP1.2]
                        (2)
 

 

 

 

 

Note1
Applies to the following text in the Fire Code: “Secondary containments for flammable liquid or combustible liquid storage tanks shall not contain any liquefied petroleum gas cylinder or tank”.

[F02,F03,F12-OS1.2,OP1.2]
Applies to the following text in the Fire Code: “the centre line of the secondary containment wall shall be … from a liquefied petroleum gas storage tank”.

4.3.2.4.           (1) [F12-OP1.2]
                        (2) [F12-OP1.2]
                        (3) [F02,F03,F12-OP1.2]
4.3.2.5.           (1) Note1
                        (2) [F2,F3,F12-OS1.2,OP1.2]
4.3.2.6. Note1
Subsection 4.3.3.
 
Supports, Foundations and Anchorage for Aboveground Storage Tanks
4.3.3.1.           (1)
 

 

 

 

[F02-OS1.2,OP1.2]
Applies to the following opening text in Sentence (1) of the Fire Code: “Storage tanks shall rest on the ground or on foundations, supports or piling made of concrete, masonry or steel”.

[F20,F22,F81-OS1.1,OP1.1]
Applies to Clauses (a) and (b) in the Fire Code.

                        (2) [F22,F80-OS1.1,OP1.1]
                        (3) [F04-OS1.2,OP1.2]
                        (4) [F20-OS1.1,OP1.1]
4.3.3.2.           (1) [F22-OS1.1,OP1.1]
4.3.3.3. [F22-OS1.1,OP1.1]
Subsection 4.3.4.
 
Normal and Emergency Venting for Aboveground Storage Tanks
4.3.4.1.           (1)
 
[F04-OS1.2,OP1.2]
[F20-OS1.1,OS1.2,OP1.1,OP1.2]
4.3.4.2.
 
[F04-OS1.2,OP1.2]
[F20-OS1.1,OS1.2,OP1.1,OP1.2]
Subsection 4.3.5. Vent Piping for Aboveground Storage Tanks
4.3.5.1. Note1
4.3.5.2.           (1) [F01,F43-OS1.1,OP1.1]
                        (2) [F01,F43-OS1.1,OP1.1]
                        (3) [F44-OS1.2,OP1.2]
4.3.5.3.           (1) [F20,F81-OS1.1,OP1.1]
                        (2) [F01,F81-OS1.1,OP1.1]
Subsection 4.3.6. Openings Other than Vents in Aboveground Storage Tanks
4.3.6.1.           (1) [F43-OS1.1,OP1.1]
                        (2) [F43-OS1.1,OP1.1]
4.3.6.2.           (1) [F04-OS1.2,OP1.2]
[F20-OS1.1,OP1.1]
                        (2) [F04,F20-OS1.1,OP1.1]
4.3.6.3. [F01,F43,F81-OS1.1,OP1.1]
4.3.6.4.           (1) [F01-OS1.1,OP1.1]
                        (2) [F43-OS1.1,OP1.1]
                        (3) [F01-OS1.1,OP1.1]
Subsection 4.3.7.
 
Secondary Containment for Aboveground Storage Tanks
4.3.7.1.           (1) Note1
                        (2) Note1
                        (3) Note1
4.3.7.2.           (1)
 




 

 

 

 

 

 

 

 

Note1
Applies to the following text in the opening line of Sentence (1) in the Fire Code: “Except as provided in Sentence (2)”.

[F04-OS1.2,OP1.2]
Applies to the following text in the opening line of Sentence (1) in the Fire Code: “the base and walls of a secondary containment shall be made of noncombustible materials”.

[F04-OH5]
[F20-OS1.1,OP1.1,OP3.1]
Applies to the following text in the Fire Code “the base and walls of a secondary containment __ shall be designed, constructed and maintained to (a) withstand full hydrostatic head”.

[F04-OP3.1]
[F44-OS1.1,OP1.1]
Applies to the following text in the Fire Code “the base and walls of a secondary containment __ shall be designed, constructed and maintained to __ (b) provide a permeability of not more than 10-6 cm/s to the flammable liquids or combustible liquids contained in the storage tanks. ”

                        (2) [F44-OS1.1,OP1.1]
                        (3) Note1
                        (4) Note1
4.3.7.3.           (1) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2,OP3.1]
                        (2) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2,OP3.1]
                        (3) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2,OP3.1]
4.3.7.4.           (1) [F01,F82-OS1.1,OP1.1]
[F81-OS1.2,OP1.2,OP3.1]
                        (2) [F01,F82-OS1.1,OP1.1]
[F81-OS1.2,OP1.2,OP3.1]
4.3.7.5.           (1)(a)
 
[F12-OS1.2,OP1.2]
[F82-OS1.1,OP1.1]
                             (b) [F10-OS1.5]
                             (c) [F12-OS1.2,OP1.2]
                        (2) [F12-OS1.1,OP1.1]
4.3.7.6. [F04-OS1.2,OP1.2]
4.3.7.7. [F82-OS1.1,OP1.1]
4.3.7.8.           (1)
 

 

 

 

 

 

[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
Applies to the following text in the Fire Code: “Liquids, debris __ shall not be permitted to accumulate in the contained space created by the secondary containment”.

[F12-OS1.2,OP1.2]
[F44-OS1.1,OS1.2,OP1.1,OP1.2,OP3.1]
[F82-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “liquids, debris and precipitation shall not be permitted to accumulate in the contained space created by the secondary containment”.

                        (2) Note1
                        (3)(a) [F44-OS1.1,OP1.1,OS1.2,OP1.2,OP3.1]
                             (b) [F12-OS1.2,OH5,OP1.2,OP3.1]
                             (c) [F12-OS1.2,OH5,OP1.2,OP3.1]
4.3.7.9. Note1
Subsection 4.3.8. Installation of Underground Storage Tanks
4.3.8.1.           (1) [F81-OS1.1,OP1.1]
                        (2)(a) [F21-OS1.1,OP1.1]
                             (b) [F01,F20,F21,F81-OS1.1,OP1.1]
                             (c) [F20,F81-OS1.1,OP1.1]
4.3.8.2.           (1) [F20,F81-OS1.1,OP1.1]
                        (2) [F20,F81-OS1.1,OP1.1]
                        (3) [F20,F81-OS1.1,OP1.1]
                        (4)
 
[F04-OS1.2,OP1.2]
[F20,F81-OS1.1,OP1.1]
4.3.8.3.           (1) [F82-OS1.1,OP1.1]
                        (2) [F82-OS1.1,OP1.1]
4.3.8.4.           (1) [F81-OS1.1,OP1.1]
                        (2) Note1
4.3.8.5.           (1) [F81-OS1.1,OP1.1]
                        (2) [F81-OS1.1,OP1.1]
                        (3) [F20-OS1.1,OP1.1]
4.3.8.6.           (1) Note1
4.3.8.7.           (1) [F43-OS1.1,OP1.1]
4.3.8.8. Note1
4.3.8.9.           (1) [F22-OS1.1,OP1.1]
                        (2) [F80,F81-OS1.1,OP1.1]
Subsection 4.3.9.
 
Corrosion Protection of Underground Steel Storage Tanks
4.3.9.1.           (1) [F80-OS1.1,OP1.1]
                        (2) [F80-OS1.1,OP1.1]
Subsection 4.3.10. Vents for Underground Storage Tanks
4.3.10.1. [F20,F81-OS1.1,OP1.1]
4.3.10.2. Note1
4.3.10.3.         (1) [F01,F43-OS1.1,OP1.1]
                        (2) [F01,F43-OS1.1,OP1.1]
                        (3) [F20,F81-OS1.1,OP1.1]
                        (4) [F11,F20,F81-OS1.1,OP1.1]
                        (5) [F20,F22,F81-OS1.1,OP1.1]
4.3.10.4.         (1) [F20,F81-OS1.1,OP1.1]
                        (2) [F20-OS1.1,OP1.1]
                        (3) [F01,F81-OS1.1,OP1.1]
Subsection 4.3.11.
 
Openings Other than Vents in Underground Storage Tanks
4.3.11.1. [F01-OS1.1] [F43-OS1.1,OP1.1]
4.3.11.2. [F01,F43,F81-OS1.1,OP1.1]
4.3.11.3.         (1) [F43-OS1.1,OP1.1]
                        (2) Note1
                        (3) [F01-OS1.1,OP1.1,OP3.1]
                        (4) [F43-OS1.1,OP1.1,OP3.1]
                        (5) [F01,F43-OS1.1,OP1.1]
Subsection 4.3.12. Installation of Storage Tanks Inside Buildings
4.3.12.1. Note1
4.3.12.2.

 

[F01-OS1.1,OP1.1]
[F02,F03,F04-OS1.2,OP1.2]
[F43,F81-OS1.1,OS1.2,OP1.1,OP1.2]
4.3.12.3. [F20-OS1.1,OP1.1]
4.3.12.4.         (1)(a)
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
                             (b)
 
[F01,F44-OS1.1,OP1.1]
[F02,F03-OS1.2,OP1.2]
                        (2)
 
[F01-OS1.1,OP1.1]
[F02,F12-OS1.2,OP1.2]
                        (3) Note1
4.3.12.5. [F03-OS1.2,OP1.2]
4.3.12.6.         (1) Note1
4.3.12.7.         (1)(a) [F44-OS1.1,OH5,OP1.1]
                             (b) Note1
                             (c) Note1
4.3.12.8.         (1) Note1
                        (2) Note1
4.3.12.9.         (1) Note1
                        (2)
 
[F04-OS1.3,OP1.3]
[F20,F22,F80,F81-OS1.1,OP1.1]
4.3.12.10.       (1) [F01-OS1.1,OP1.1]
Subsection 4.3.13. Rooms for Storage Tanks
4.3.13.1.          (1)(a) [F03-OS1.2,OP1.2]
                              (b) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                              (c) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                              (d) Note1
                              (e) [F01-OS1.1,OP1.1]
4.3.13.2. [F82-OS1.1,OP1.1]
4.3.13.3. [F02-OS1.2,OP1.2]
[F04-OS1.3,OP1.3]
4.3.13.4.         (1) [F12-OS1.2,OP1.2]
                        (2) Note1
4.3.13.5.         (1) [F12-OS1.2,OP1.2]
                        (2) [F12-OS1.2,OP1.2]
                        (3) Note1
                        (4) Note1
                        (5) Note1
                        (6) [F12-OS1.2,OP1.2]
Subsection 4.3.14.
 
Openings Other than Vents in Storage Tanks in Buildings
4.3.14.1.         (1)
 
[F01-OS1.1]
[F43-OS1.1,OP1.1]
                        (2) [F44-OS1.1,OP1.1]
4.3.14.2.         (1) [F01,F43,F81-OS1.1,OP1.1]
Subsection 4.3.15. Leakage Testing of Storage Tanks
4.3.15.1.         (1) [F82-OS1.1,OP1.1]
                        (2) [F82-OS1.1,OP1.1]
                        (3) [F01,F82-OS1.1,OP1.1]
                        (4) [F01,F82-OS1.1,OP1.1]
4.3.15.2. Note1
4.3.15.3.         (1) [F43,F82-OS1.1,OP1.1]
                        (2)
 
[F12-OS1.2,OP1.2]
[F43,F82-OS1.1,OP1.1]
4.3.15.4.         (1) Note1
                        (2) Note1
                        (3) Note1
                        (4) [F82-OS1.1,OP1.1]
                        (5) [F20,F82-OS3.4]
                        (6) [F20,F82-OS1.1,OP1.1]
                        (7) [F01-OS1.1,OP1.1]
4.3.15.5.         (1) Note1
                        (2) [F20,F82-OS1.1,OP1.1]
Subsection 4.3.16. Leakage Detection of Storage Tanks
4.3.16.1.         (1) [F82-OS1.1,OP1.1]
                        (2) [F82-OS1.1,OP1.1]
                        (3) [F82-OS1.1,OP1.1]
                        (4) Note1
4.3.16.2.         (1) [F01,F82-OS1.1,OP1.1]
4.3.16.3.         (1) [F43,F82-PS1.1,OP1.1]
Subsection 4.3.17. Out of Service
4.3.17.1.         (1)(a) [F82-OS1.1,OP1.1]
                             (b) [F01,F34-OS1.1,OP1.1]
                             (c) [F20,F81-OS1.1]
                        (2)(a) [F01,F43-OS1.1,OP1.1]
                             (b) [F01-OS1.1]
                             (c) [F82-OS1.1,OP1.1]
                             (d) [F01,F34-OS1.1,OP1.1]
                        (3)(a)(i) [F82-OS1.1,OP1.1]
                                 (ii) [F82-OS1.1,OP1.1]
                                 (iii) [F01,F34-OS1.1]
                              (b) [F82-OS1.1,OP1.1]
                        (4) [F82-OS1.1,OP1.1]
4.3.17.2.         (1) [F34-OS1.1,OP1.1]
                        (2) [F82-OS1.1,OP1.1]
                        (3)(a) [F01,F43-OS1.1,OP1.1]
                             (b) [F81-OS1.1,OP1.1]
4.3.17.3. [F81-OS1.1,OP1.1]
4.3.17.4.         (1)(a) [F01,F43-OS1.1,OP1.1]
                             (b) [F01-OS1.1,OP1.1]
                             (c) [F81-OS1.1,OP1.1]
                        (2) [F44-OS1.1,OP1.1]
4.3.17.5.         (1) [F81-OS1.1,OP1.1]
                        (2) [F81-OS1.1,OP1.1]
4.3.17.6. [F80-OS1.1,OP1.1]
SECTION 4.4 PIPING AND TRANSFER SYSTEMS
Subsection 4.4.1. Scope
4.4.1.1.           (1) Note1
                        (2) Note1
Subsection 4.4.2. Materials for Piping, Valves and Fittings
4.4.2.1.           (1)

 

 

 

 

[F20-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “Materials for piping systems containing flammable liquids or combustible liquids shall be suitable for the maximum anticipated working pressures and operating temperatures”.

[F80-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “Materials for piping systems containing flammable liquids or combustible liquids shall be suitable __ for the chemical properties of the contained liquid”.

                        (2) Note1
                        (3)
 
[F04-OS1.2,OH5,OP1.2]
[F20,F81-OS1.1,OP1.1]
                        (4) [F20,F80,F81-OS1.1,OP1.1]
                        (5) [F20,F80,F81-OS1.1,OP1.1]
                        (6) Note1
4.4.2.2. [F20,F80,F81-OS1.1,OP1.1]
Subsection 4.4.3. Corrosion Protection of Piping Systems
4.4.3.1.           (1) [F80-OS1.1,OP1.1]
                        (2) [F80-OS1.1,OP1.1]
Subsection 4.4.4. Identification of Piping Systems
4.4.4.1.           (1)
 
[F12-OS1.2,OP1.2]
[F81-OS1.1,OP1.1]
                        (2)
 
[F12-OS1.2,OP1.2]
[F81-OS1.1,OP1.1]
                        (3)
 
[F12-OS1.1,OS1.2,OP1.1,OP1.2]
[F81-OS1.1,OP1.1]
4.4.4.2.           (1) [F12-OS1.2,OP1.2]
                        (2) [F12-OS1.2,OP1.2]
Subsection 4.4.5. Joints in Piping Systems
4.4.5.1. [F43,F81-OS1.1,OP1.1]
4.4.5.2.           (1)

 

 

 

 

Note1
Applies to the following text in the Fire Code: “Welding of piping for flammable liquids or combustible liquids shall conform to Section 5.17”.

[F04-OS1.2,OH5,OP1.2]
[F20,F81-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “Welding of piping for flammable liquids or combustible liquids shall conform __ to (a) … (b) … Welding Practices”.”

                        (2) [F01-OS1.1,OP1.1]
4.4.5.3.           (1) [F20,F81-OS1.1,OP1.1]
                        (2) Note1
4.4.5.4. [F04-OS1.1,OH5,OP1.1]
4.4.5.5. [F04-OS1.2,OH5,OP1.2]
[F20-OS1.1,OP1.1]
4.4.5.6.           (1) [F80,F82-OS1.1,OP1.1]
Subsection 4.4.6. Leakage Testing of Piping Systems
4.4.6.1.           (1) Note1
                        (2) [F82-OS1.1,OP1.1]
                        (3) [F82-OS1.1,OP1.1]
4.4.6.2. Note1
4.4.6.3. [F82-OS1.1,OP1.1]
4.4.6.4.           (1) [F82-OS1.1,OP1.1]
                        (2) [F82-OS1.1,OP1.1]
4.4.6.5.           (1) [F20-OS1.1,OP1.1]
                        (2) [F20,F81-OS1.1,OP1.1]
                        (3) [F81-OS1.1,OS3.1,OS3.4,OP1.1]
4.4.6.6. [F43-OS1.1,OP1.1]
4.4.6.7. [F81,F82-OS1.1,OP1.1]
Subsection 4.4.7. Location and Arrangement of Piping
4.4.7.1.           (1) [F43-OS1.1,OP1.1]
                        (2) [F43-OS1.1,OP1.1]
                        (3) Note1
                        (4) [F81-OS1.1,OP1.1]
4.4.7.2.           (1) [F20,F22-OS1.1,OP1.1]
                        (2) [F81-OS1.1,OP1.1]
                        (3) [F80,F82-OS1.1,OP1.1]
4.4.7.3.           (1)(a) [F02,F04-OS1.2,OP1.2]
                             (b)
 
[F04-OS1.2,OP1.2]
[F44-OS1.1,OP1.1]
                        (2)
 
[F02-OS1.2,OP1.2]
[F44-OS1.1,OP1.1]
                        (3) [F81-OS1.1,OP1.1]
                        (4)
 
[F04-OS1.2,OH5,OP1.2]
[F21-OS1.1,OP1.1]
4.4.7.4.           (1) [F21,F22-OS1.1,OP1.1]
                        (2) [F20-OS1.1,OP1.1]
                        (3) [F21,F22-OS1.1,OP1.1]
                        (4) [F21,F22-OS1.1,OP1.1]
4.4.7.5.           (1)(a) [F21,F22-OS1.1,OP1.1]
                             (b) [F20,F21-OS1.1,OP1.1]
                        (2) [F21,F22-OS1.1,OP1.1]
4.4.7.6. Note1
4.4.7.7.           (1) [F21,F82-OS1.1,OP1.1]
                        (2) [F44-OS1.1,OP1.1]
                        (3) [F21-OS1.1,OP1.1]
4.4.7.8.           (1) [F81-OS1.1,OP1.1]
                        (2)
 
[F02-OS1.2,OP1.2]
[F04-OS1.1,OP1.1]
4.4.7.9.           (1) Note1
                        (2) [F01-OS1.1,OP1.1]
4.4.7.10.         (1) [F81-OS1.1,OP1.1]
                        (2) [F20-OS1.1,OP1.1]
                        (3) [F20-OS1.1,OP1.1]
                        (4) [F20-OS1.1,OP1.1]
4.4.7.11.         (1) [F20-OS1.1,OP1.1]
                        (2) [F20-OS1.1,OP1.1]
4.4.7.12.         (1) [F81-OS1.1,OP1.1]
4.4.7.13.         (1) [F21-OS1.1,OP1.1]
                        (2) [F20,F21,F81-OS1.1,OP1.1]
Subsection 4.4.8. Valves in Piping Systems
4.4.8.1.           (1) [F20,F81-OS1.1,OP1.1]
                        (2) [F20,F81-OS1.1,OP1.1]
                        (3) [F20,F81-OS1.1,OP1.1]
                        (4) Note1
4.4.8.2.           (1) [F44-OS1.1,OS1.2,OP1.1,OP1.2]
                        (2) [F12,F44-OS1.1,OS1.2,OP1.1,OP1.2]
                        (3)

 

 





 

[F04-OS1.2,OH5,OP1.2]
[F20-OS1.1,OP1.1]
Applies to the following text in the opening line of Sentence (3) of the Fire Code: “steel shut-off valves shall be provided”.

[F12,F44-OS1.1,OS1.2,OP1.1,OP1.2]
Applies to Clauses (a) to (e) in the Fire Code.

[F82-OS1.1,OP1.1]
Applies to Clause (f) in the Fire Code.

                        (4) Note1
4.4.8.3. Note1
4.4.8.4. [F20-OS1.1,OP1.1]
4.4.8.5. [F12-OS1.1,OS1.2,OP1.1,OP1.2]
4.4.8.6.           (1) [F12,F81-OS1.1,OH5,OP1.1]
                        (2) [F12,F81-OS1.1,OP1.1]
Subsection 4.4.9. Heating of Piping Systems
4.4.9.1. [F01,F20,F81-OS1.1,OP1.1]
4.4.9.2.           (1) [F20,F81-OS1.1,OP1.1]
                        (2) [F20,F81-OS1.1,OP1.1]
                        (3) [F01,F81-OS1.1,OP1.1]
4.4.9.3. Note1
4.4.9.4.           (1) Note1
                        (2)

 

 

 

 

 

 

[F82-OS1.1,OP1.1]
Applies to the following text in the opening line of Sentence (2) of the Fire Code: “Systems permitted in Sentence (1) shall be installed and tested as complete units”.

[F01-OS1.1,OP1.1]
Applies to Clause (a) in the Fire Code.

[F20,F81-OS1.1,OP1.1]
Applies to Clause (b) in the Fire Code.

[F01-OS1.1,OP1.1]
Applies to Clauses (c) and (d) in the Fire Code.

                        (3) [F82-OS1.1,OP1.1]
4.4.9.5.           (1) Note1
                        (2) [F01,F81-OS1.1,OP1.1]
Subsection 4.4.10. Method of Transfer in Piping Systems
4.4.10.1.         (1) [F01-OS1.1,OP1.1,OP3.1]
4.4.10.2.         (1) Note1
                        (2)
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
4.4.10.3.         (1) [F20,F81-OS1.1,OP1.1]
                        (2)
 

 

 

 

 

[F02-OS1.2,OP1.2]
[F82-OS1.1,OS1.2,OP1.1,OP1.2]
Applies to the following text in the Fire Code: “Pits provided in conformance with Sentence (1) shall not be larger than necessary for inspection and maintenance”.

[F81-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “Pits provided in conformance with Sentence (1) __ shall be provided with a cover”.

4.4.10.4.

 

 

 

 

[F12,F44-OS1.1,OS1.2,OP1.1,OP1.2]
Applies to the following text in the Fire Code: “Pumps for piping systems shall be provided with duplicate control switches __ with one located in the operating area and the other at a remote location”.

[F44-OS1.1,OS1.2,OP1.1,OP1.2]
Applies to the following text in the Fire Code: “to shut down the pumps in case of emergency”.

4.4.10.5.         (1) Note1
                        (2) [F20,F81,F82-OS1.1,OP1.1]
                        (3) [F20,F81-OS1.1,OP1.1]
                        (4) [F20,F81-OS1.1,OP1.1]
                        (5)
 
[F43-OS1.1,OP1.1]
[F44-OS1.2,OP1.2]
                        (6) [F81-OS1.1,OP1.1]
4.4.10.6.         (1) [F20,F81,F82-OS1.1,OP1.1]
                        (2) [F20,F81-OS1.1,OP1.1]
                        (3) [F20,F81-OS1.1,OP1.1]
                        (4) [F04,F81-OS1.2,OH5,OP1.2]
4.4.10.7.         (1) [F01-OS1.1,OP1.1]
                        (2) [F01-OS1.1,OP1.1]
Subsection 4.4.11. Method of Transfer in Piping Systems
4.4.11.1.
 
[F12-OS1.1,OS1.2,OP1.1,OP1.2]
[81-OS1.1,OP1.1]
4.4.11.2.         (1)(a) [F12-OS1.1,OP1.1]
                             (b) [F12,F43-OS1.1,OP1.1]
                             (c) [F12-OS1.2,OP1.2]
                             (d)
 
[F12-OS1.1,OS1.2,OP1.1,OP1.2]
[F81-OS1.1,OP1.1]
                        (2)

 

 

 

 

 

 

[F12-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “Employees engaged in the operation of equipment for the transfer of flammable liquids or combustible liquids shall be trained in the location, function and operation of __ manual emergency shut-off valves”.

[F12-OS1.2,OP1.2]
Applies to the following text in the Fire Code: “Employees engaged in the operation of equipment for the transfer of flammable liquids or combustible liquids shall be trained in the location, function and operation of valves used for the operation of fire protection equipment”.

4.4.11.3. [F12-OS1.1,OS1.2,OP1.1,OP1.2]
4.4.11.4. [F02,F12-OS1.2,OP1.2]
4.4.11.5.         (1) [F82-OS1.1,OP1.1]
                        (2) [F82-OS1.1,OP1.1]
                        (3) [F82-OS1.1,OP1.1]
                        (4) Note1
4.4.11.6. [F82-OS1.1,OP1.1]
4.4.11.7.         (1) [F01,F43-OS1.1,OP1.1]
                        (2) [F43-OS1.1,OP1.1]
                        (3) [F01-OS1.1,OP1.1]
                        (4) [F81-OS1.1,OP1.1]
                        (5) [F43-OS1.1,OP1.1]
                        (6) [F01,F43-OS1.1,OP1.1]
SECTION 4.5 FUEL DISPENSING STATIONS
Subsection 4.5.1. Scope
4.5.1.1.           (1) Note1
                        (2) [F01,F03,F81-OS1.1]
                        (3) Note1
Subsection 4.5.2. Storage and Handling
4.5.2.1.           (1) Note1
                        (2) [F02-OS1.2,OP1.2]
                        (3) [F34,F81-OS1.1,OP1.1]
4.5.2.2.           (1) Note1
4.5.2.3.           (1) [F02-OS1.2,OP1.2]
                        (2)(a) Note1
                             (b)
 
[F01-OS1.1,OP1.1]
[F12-OS1.2,OP1.2]
4.5.2.4. Note1
4.5.2.5. Note1
4.5.2.6. [F22,F81-OS1.1,OP1.1]
4.5.2.7. Note1
Subsection 4.5.3. Dispensing Systems
4.5.3.1. [F01,F43-OS1.1]
4.5.3.2. [F20,F43,F80,F81-OS1.1]
4.5.3.3. (1)
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[F01,F43-OS1.1]
Applies to the following text in the opening line of Sentence (1) in the Fire Code: “Fixed dispensers for Class I liquids shall be installed outside buildings”.

[F01-OP3.1]
Applies to the following text in the Fire Code: “Fixed dispensers for Class I liquids shall be installed __ not less than (a) 3 m from any right-of-way and any property line”.

[F01,F81-OS1.1]
Applies to the following text in the Fire Code: “Fixed dispensers for Class I liquids shall be installed __ not less than __ (b) 3 m from any propane gas dispenser”.

[F01,F81-OS1.1]
Applies to the following text in the Fire Code: “Fixed dispensers for Class I liquids shall be installed __ not less than __ (c) 1.5 m from any natural gas dispenser”.

[F01-OS1.1]
Applies to the following text in the Fire Code: “Fixed dispensers for Class I liquids shall be installed __ not less than __ (d) 6 m horizontally from any fixed source of ignition”.

[F02-OS1.2]
Applies to the following text in the Fire Code: “Fixed dispensers for Class I liquids shall be installed __ not less than __ (e) 6 m horizontally from any liquefied petroleum gas cylinder or tank”.

[F01-OS1.1]
Applies to the following text in the Fire Code: “Fixed dispensers for Class I liquids shall be installed __ not less than __ (f) 3 m from any building opening, except those openings in buildings for the shelter of operating personnel in which electrical installations conform to Article 4.1.4.1.”

                        (2)(a) [F43,F81-OS1.1,OP1.1]
                             (b) [F01-OS1.1,OP1.1]
[F12,F44-OS1.2,OP1.2]
                             (c) Note1
                             (d)
 

 

 

 

Note1
Applies to the following text in the Fire Code: “ventilation is provided in conformance with Subsection 4.1.7.”

[F01-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “with the requirements for storage garages in Part 6 in Division B of the Building Code”.

4.5.3.4.           (1) [F81-OS1.1,OP1.1]
4.5.3.5. [F81-OS1.1]
Subsection 4.5.4. Shut-Off Devices
4.5.4.1.           (1)

 

 

 

 

[F06-OS1.2,OH5,OP1.2]
Applies to the following text in the Fire Code: “A device to shut off power to all dispensers and pumps”.

[F44-OS1.1,OH5,OP1.1]
Applies to the following text in the Fire Code: “shall be provided at a remote location on the site of the fuel dispensing station and shielded from any fire that might occur in the dispensing area”.

                        (2) [F12-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
4.5.4.2.           (1) [F12,F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                        (2) [F12-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
4.5.4.3. [F12-OS1.1,OH5,OP1.1]
Subsection 4.5.5. Delivery Hose and Nozzles
4.5.5.1.           (1) [F01-OS1.1]
[F20,F43,F81-OS1.1,OP1.1]
                        (2) [F43-OS1.1,OH5,OP1.1]
                        (3) [F43-OS1.1,OH5,OP1.1]
                        (4) Note1
4.5.5.2.           (1) [F01-OS1.1]
[F20,F43,F81-OS1.1,OP1.1]
                        (2) [F43-OS1.1,OP1.1]
                        (3) [F43-OS1.1,OP1.1]
                        (4) [F81-OS1.1,OP1.1]
                        (5) [F81-OS1.1,OP1.1]
Subsection 4.5.6. Remote Pumping Systems
4.5.6.1. Note1
4.5.6.2.           (1) [F20,F81-OS1.1,OP1.1]
                        (2) [F20,F22,F81-OS1.1,OP1.1]
4.5.6.3.           (1)
 
[F04-OS1.1,OP1.1]
[F43,F81-OS1.1,OH5,OP1.1]
                        (2) [F82-OS1.1,OH5,OP1.1]
4.5.6.4.           (1) [F01-OS1.1,OP3.1]
                        (2) Note1
4.5.6.5. Note1
4.5.6.6.           (1) [F12,F20,F22,F81-OS1.1,OP1.1]
                        (2)
 
[F02-OS1.2,OP1.2]
[F44-OS1.1,OP1.1]
                        (3) [F22-OS1.1,OP1.1]
                        (4) Note1
                        (5) [F43,F81-OS1.1,OH5,OP1.1]
                        (6)
 
[F01-OS1.1,OP1.1]
[F43-OS1.1,OP1.1]
Subsection 4.5.7. Spill Control
4.5.7.1.           (1)(a) Note1
                             (b) [F44-OS1.2,OP1.3]
Subsection 4.5.8. Supervision and Dispensing Procedures
4.5.8.1.           (1)
 
[F01-OS1.1,OP1.1]
[F43,F44-OS1.1,OH5,OP1.1]
                        (2)
 
[F01-OS1.1,OP1.1]
[F34,F43-OS1.1,OH5,OP1.1]
                        (3)
 
[F01-OS1.1,OP1.1]
[F43-OS1.1,OH5,OP1.1]
                        (4) [F81-OS1.1,OH5,OP1.1]
4.5.8.2.           (1) [F81-OS1.1,OH5,OP1.1]
                        (2) [F01,F12,F43,F44-OS1.1,OH5,OP1.1]
                        (3) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                        (4)
 
[F01-OS1.1,OP1.1]
[F43,F44-OS1.1,OH5,OP1.1]
                        (5)
 
[F01-OS1.1,OP1.1]
[F12,F43,F44-OS1.1,OH5,OP1.1]
4.5.8.3.
 
[F01-OS1.1,OP1.1]
[F12,F44-OS1.1,OH5,OP1.1]
4.5.8.4.           (1) Note1
                        (2) Note1
                        (3) [F34-OS1.1,OH5,OP1.1]
                        (4) [F81-OS1.1,OH5,OP1.1]
                        (5) [F13-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                        (6)(a) [F12-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                             (b) [F13-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
4.5.8.5.           (1)(a) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                             (b) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                             (c)
 
[F01-OS1.1,OP1.1]
[F43-OS1.1,OP1.1,OS1.2,OP1.2]
                             (d) [F01-OS1.1]
                             (e) [F01-OS1.1,OP1.1]
                             (f) [F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                        (2)(a) [F01,F44-OS1.1]
                             (b)(i) [F43-OS1.1]
                                  (ii) [F01,F44-OS1.1]
                        (3) [F12,F81-OS1.1,OS1.2,OP1.1,OP1.2]
4.5.8.6.           (1) [F01-OS1.1]
                        (2) [F01-OS1.1]
                        (3) Note1
                        (4)(a) [F43-OS1.1]
                             (b) [F43-OS1.1]
                             (c) [F44-OS1.1]
                             (d) [F01-OS1.1]
                             (e) [F43-OS1.1]
                             (f) [F01-OS1.1.]
4.5.8.7. [F01-OS1.1]
4.5.8.8.           (1)

 

 

 

 

[F01-OS1.1]
Applies to the following text in the Fire Code: “At least one __ sign conforming to Sentences (2) to (4) shall be provided for each dispenser in a location visible to every driver approaching the dispenser”.

[F80-OS1.1]
Applies to the following text in the Fire Code: “weather-resistant”.

                        (2) [F01-OS1.1]
                        (3) [F01-OS1.1]
                        (4) [F01-OS1.1]
Subsection 4.5.9. Leakage Detection
4.5.9.1. Note1
Subsection 4.5.10. Fire Prevention and Protection
4.5.10.1. [F02,F12-OS1.2,OP1.2]
4.5.10.2. Note1
SECTION 4.6 BULK PLANTS
Subsection 4.6.1. Scope
4.6.1.1. Note1
Subsection 4.6.2. Storage
4.6.2.1.           (1) [F43-OS1.1,OP1.1]
4.6.2.2.
 
[F03-OS1.2,OH5,OP1.2]
[F21,F22,F81-OS1.1,OP1.1]
4.6.2.3. [F20,F82-OS1.1,OP1.1]
4.6.2.4.           (1) Note1
                        (2) Note1
4.6.2.5. Note1
4.6.2.6.           (1) [F01,F34-OH5,OP3.1]
Subsection 4.6.3. Dispensing
4.6.3.1. Note1
4.6.3.2.           (1) [F34-OS1.1,OP1.1]
                        (2) [F43,F81-OS1.1,OP1.1]
4.6.3.3. Note1
4.6.3.4. Note1
Subsection 4.6.4. Loading and Unloading Facilities
4.6.4.1.           (1)
 
[F01-OS1.1,OP3.1]
[F03-OS1.2,OP1.2,OP3.1]
                        (2)
 
[F03-OS1.2,OH5,OP1.2]
[F21,F22,F81-OS1.1,OP1.1]
                        (3) Note1
4.6.4.2. [F01-OS1.1]
4.6.4.3.           (1) [F01,F43-OS1.1,OP1.1]
                        (2) [F43,F82-OS1.1,OP1.1]
4.6.4.4.           (1) [F43-OS1.1,OP1.1]
                        (2) [F43,F81-OS1.1,OP1.1]
4.6.4.5.           (1) [F01-OS1.1,OP1.1]
                        (2) [F01-OS1.1,OP1.1]
                        (3) [F01-OS1.1,OP1.1]
                        (4) [F01-OS1.1,OP1.1]
                        (5) [F01-OS1.1,OP1.1]
4.6.4.6. Note1
Subsection 4.6.5. Fire Protection
4.6.5.1. [F02,F12-OS1.2,OP1.2]
Subsection 4.6.6. Spill Control
4.6.6.1. Note1
SECTION 4.7 PIERS AND WHARVES
Subsection 4.7.1. Scope
4.7.1.1. Note1
Subsection 4.7.2. General
4.7.2.1.           (1) [F03-OS1.2,OP3.1]
                        (2) [F03-OS1.2,OP3.1]
4.7.2.2.
 
[F04-OS1.2,OH5,OP1.2]
[F20,F21,F80-OS1.1,OP1.1]
Subsection 4.7.3. Storage Tanks
4.7.3.1.           (1)
 
[F04-OS1.2,OH5,OP1.2]
[F20-OS1.1,OP1.1]
                        (2)
 
[F04-OS1.2,OH5,OP1.2]
[F20,F43-OS1.1,OP1.1]
                        (3)
 
[F04-OS1.2,OH5,OP1.2]
[F20,F43-OS1.1,OP1.1]
Subsection 4.7.4. Piping, Valves and Fittings
4.7.4.1. Note1
4.7.4.2.           (1) [F20,F22-OS1.1,OP1.1]
                        (2) [F04-OS1.2,OH5,OP1.2]
                        (3) [F04-OS1.2,OH5,OP1.2]
4.7.4.3. [F81-OS1.1,OP1.1]
4.7.4.4. [F21-OS1.1,OP1.1]
4.7.4.5. [F12,F44-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
4.7.4.6.           (1) [F82-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
                        (2) [F82-OS1.2,OH5,OP1.2]
4.7.4.7. [F12-OS1.1,OS1.2,OH5,OP1.1,OP1.2]
[F81-OS1.1,OP1.1]
4.7.4.8.           (1) Note1
                        (2) [F82-OS1.1,OP1.1]
Subsection 4.7.5. Bonding and Grounding
4.7.5.1.           (1) [F01-OS1.1,OP1.1]
                        (2) [F01-OS1.1,OP1.1]
Subsection 4.7.6. Fire Protection
4.7.6.1.           (1) [F02,F12-OS1.2,OP1.2]
                        (2)

 

 

 

 

[F12-OS1.2,OP1.2]
Applies to the following text in the Fire Code: “Portable extinguishers shall be kept in the pump house or other suitable location where they will be accessible in the event of an emergency”.

[F34-OS1.2,OP1.2]
Applies to the following text in the Fire Code: “not accessible to the public”.

                        (3) [F02,F12-OS1.2,OP1.2]
                        (4) Note1
4.7.6.2. [F12,F13-OS1.2,OP1.2]
Subsection 4.7.7. Bulk Transfer Stations
4.7.7.1.           (1) [F01,F81-OS1.1,OH5,OP1.1]
                        (2) [F34-OS1.1,OP1.1]
4.7.7.2.           (1) Note1
                        (2) [F43-OS1.1,OP1.1]
4.7.7.3.           (1)

 
[F12-OS1.1,OS1.2,OP1.1,OP1.2]
[F22,F43-OS1.1,OP1.1]
[F44-OS1.2,OP1.2]
                        (2) [F22,F43-OS1.1,OP1.1]
                        (3) Note1
Subsection 4.7.8. Cargo Hose
4.7.8.1.           (1) [F20,F22,F81-OS1.1,OP1.1]
4.7.8.2. [F20,F82-OS1.1,OP1.1]
4.7.8.3. [F20,F22-OS1.1,OP1.1]
Subsection 4.7.9. Cargo Pumps
4.7.9.1. Note1
4.7.9.2. [F20,F81-OS1.1,OP1.1]
4.7.9.3.           (1)(a) [F02-OS1.2,OP1.2]
                             (b)
 
[F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2,OP3.1]
                        (2)


 

[F01-OS1.1]
[F02-OS1.2,OP3.1]
[F03-OS1.2]
[F44-OS1.1,OP3.1]
Subsection 4.7.10. Pump Houses
4.7.10.1.
 

 

 

 

 

[F02-OS1.2,OP1.2]
Applies to the following text in the Fire Code: “Pump houses shall be of noncombustible construction”.

[F44-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “with floors that are chemically resistant to the liquid being handled, liquid-tight and equipped with curbs or flashings around the base of the wall not less than 100 mm in height to contain any spilled liquid”.

4.7.10.2. Note1
Subsection 4.7.11. Transfer Operations
4.7.11.1.         (1)

 

[F01,F12-OS1.1,OP1.1]
[F02,F44-OS1.2,OP1.2]
[F43-OS1.1,OH5,OP1.1]
                        (2)
 
[F12,F44-OS1.1,OP1.1]
[F43-OS1.1,OH5,OP1.1]
                        (3)(a) [F01-OS1.1,OP1.1]
                             (b) [F43-OS1.1,OP1.1]
                             (c)

 

 

 

[F43-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “inspect the hose and connections for leakage”.

[F44-OS1.1,OP1.1]
Applies to the following text in the Fire Code: “if leakage occurs, stop the operations”.

4.7.11.2.         (1) [F01-OS1.1,OP1.1]
                        (2) [F01-OS1.1,OP1.1]
4.7.11.3.         (1) [F21-OS1.1,OP1.1]
                        (2) [F43-OS1.1,OP1.1]
                        (3) [F43-OS1.1,OP1.1]
                        (4) [F44-OS1.1,OP1.1]
4.7.11.4.         (1) [F43-OS1.1,OP1.1]
                        (2) [F43-OS1.1,OP1.1]
SECTION 4.8 PROCESS PLANTS
Subsection 4.8.1. Scope
4.8.1.1.           (1) Note1
                        (2) Note1
Subsection 4.8.2. Outdoor Processing Equipment
4.8.2.1.           (1) Note1
                        (2) [F03-OS1.2,OP3.1]
                        (3) [F03-OS1.2,OP3.1]
                        (4) [F03-OS1.2,OP3.1]
Subsection 4.8.3. Processing Buildings
4.8.3.1. [F02-OS1.3,OP1.3]
4.8.3.2. [F03-OS1.2,OP1.2]
4.8.3.3.           (1) Note1
                        (2) [F01-OS1.1,OP1.1]
                        (3) [F01-OS1.1,OP1.1]
4.8.3.4.           (1) Note1
                        (2) [F01-OS1.1,OP1.1]
Subsection 4.8.4. Fire Prevention and Protection
4.8.4.1.           (1)(a) [F01,F43-OS1.1,OP1.1]
                             (b) [F43-OS1.1,OP1.1]
                        (2) Note1
4.8.4.2.           (1)(a) [F02,F20-OS1.2,OS1.3,OP1.2,OP1.3]
                             (b) [F02,F20-OS1.2,OS1.3,OP1.2,OP1.3]
                             (c) [F01-OS1.1,OP1.1]
4.8.4.3.           (1)

 

 

[F01,F20-OS1.1,OP1.1,OP3.1]
[F02,F03,F43-OS1.2,OP1.2,OP3.1]
[F04-OS1.3,OP1.3,OP3.1]
[F44-OS1.2,OH5,OP1.2,OP3.1]
[F81-OS1.1,OS1.2,OP1.1,OP1.2,OP3.1]
                        (2)

 

 

[F01,F20-OS1.1,OP1.1,OP3.1]
[F02,F03,F43-OS1.2,OP1.2,OP3.1]
[F04-OS1.3,OP1.3,OP3.1] [
F44-OS1.2,OH5,OP1.2,OP3.1]
[F81-OS1.1,OS1.2,OP1.1,OP1.2,OP3.1]
                        (3)
 
[F81-OS1.1,OS1.2,OS1.3,OH5,OP1.1,OP1.2,OP1.3,OP3.1]
                        (4) Note1
                        (5) Note1
SECTION 4.9 DISTILLERIES
Subsection 4.9.1. Scope
4.9.1.1.           (1) Note1
                        (2) Note1
                        (3) Note1
                        (4) Note1
Subsection 4.9.2. General
4.9.2.1.           (1) Note1
                        (2) Note1
Subsection 4.9.3. Storage Tanks and Containers
4.9.3.1. [F20,F43,F80-OS1.1,OP1.1]
4.9.3.2.           (1) [F02,F04-OS1.2,OP1.2]
                        (2) [F04-OS1.2,OP1.2]
                        (3) [F02-OS1.2,OP1.2]
4.9.3.3.
 
[F01-OS1.1,OP1.1]
[F20,F81-OS1.1,OH5,OP1.1]
Subsection 4.9.4. Storage
4.9.4.1.           (1)
 
[F02-OS1.2,OP1.2]
[F11-OS1.5]
                        (2) [F02-OS1.2,OP1.2]
4.9.4.2. Note1
Subsection 4.9.5. Piping and Pumping Systems
4.9.5.1. [F20,F80-OS1.1,OP1.1]
Subsection 4.9.6. Ventilation
4.9.6.1.           (1) [F01-OS1.1]
                        (2) Note1
Subsection 4.9.7. Spill Control
4.9.7.1. Note1
Subsection 4.9.8. Fire Protection
4.9.8.1.           (1) Note1
                        (2) [F02,F12-OS1.2,OP1.2]
                        (3) [F02,F12-OS1.2,OP1.2]
                        (4) [F02,F12-OS1.2,OP1.2]
4.9.8.2.           (1)
 
[F01-OS1.1,OP1.1]
[F02,F12-OS1.2,OP1.2]
                        (2) Note1
SECTION 4.10 RESERVED
SECTION 4.11 TANK VEHICLES
Subsection 4.11.1. Scope
4.11.1.1. Note1
Subsection 4.11.2. General
4.11.2.1.         (1) [F02,F12-OS1.2,OP1.2]
                        (2) [F12-OS1.2,OP1.2]
4.11.2.2. Note1
4.11.2.3.         (1)(a) [F01,F43,F44-OS1.1,OH5,OP1.1]
[F02,F03-OS1.2,OP1.2]
                             (b) [F21-OS1.1,OP1.1]
                             (c) Note1
4.11.2.4.         (1)
 
[F02-OS1.2,OP3.1]
[F34,F81-OS1.1]
                        (2)
 
[F03-OS1.2,OP3.1]
[F81-OS1.1,OP3.1]
Subsection 4.11.3.
 
Loading, Unloading and Dispensing from Tank Vehicles
4.11.3.1. Note1
4.11.3.2. [F01-OS1.1,OP1.1]
4.11.3.3. [F01-OS1.1,OP1.1]
4.11.3.4. [F44-OS1.1,OS1.2,OP1.1,OP1.2]
4.11.3.5. [F01-OS1.1,OP1.1]
4.11.3.6. [F01-OS1.1,OP1.1]
4.11.3.7.         (1) [F43-OS1.1,OP1.1]
                        (2) [F20,F43,F81-OS1.1,OP1.1]
                        (3) Note1
4.11.3.8.         (1) [F01,F43-OS1.1,OP1.1]
                        (2)(a)
 
[F01-OS1.1,OP3.1]
[F03-OS1.2,OP3.1]
                             (b) [F02,F12-OP1.2]
                             (c) Note1
                             (d) [F43,F44-OS1.1]
                             (e) [F44-OS1.1]
SECTION 4.12 LABORATORIES
Subsection 4.12.1. Scope
4.12.1.1. Note1
Subsection 4.12.2. Separation
4.12.2.1.         (1) [F03-OS1.2,OP1.2]
                        (2) Note1
Subsection 4.12.3. Maximum Quantities
4.12.3.1.         (1)
 
[F02-OS1.2,OP1.2]
[F43-OS1.1,OP1.1]
                        (2) [F02-OS1.2,OP1.2]
                        (3) [F03-OS1.2,OP1.2]
                        (4) [F01,F43-OS1.1,OP1.1]
Subsection 4.12.4. Emergency Planning
4.12.4.1.         (1) Note1
                        (2) [F12-OS1.5]
                        (3) [F01,F12-OS1.1,OP1.1]
                        (4) [F34-OS1.1,OP1.1]
Subsection 4.12.5. Spill Control
4.12.5.1. Note1
Subsection 4.12.6. Electrical Equipment
4.12.6.1. Note1
Subsection 4.12.7. Inspection and Maintenance
4.12.7.1.         (1) [F82-OS1.1,OS1.2,OP1.1,OP1.2]
                        (2) [F82-OS1.1,OS1.2,OP1.1,OP1.2]
Subsection 4.12.8. Ventilation
4.12.8.1.         (1) Note1
                        (2) Note1
                        (3) Note1
                        (4) Note1
4.12.8.2.         (1) [F01-OS1.1,OP1.1]
                        (2) [F01,F81-OS1.1,OP1.1]
4.12.8.3.         (1) [F01-OS1.1,OP1.1]
4.12.8.4.         (1) [F01-OS1.1,OP1.1]
                        (2)(a) [F82-OS1.1,OS1.2,OP1.1,OP1.2]
                             (b) [F02-OS1.2,OP1.2]
4.12.8.5.         (1)(a)
 
[F01,F80-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
                             (b) [F82-OS1.1,OP1.1]
                             (c) [F81-OS1.1,OP1.1]
                             (d) Note1
                        (2)(a) [F80-OS1.1,OP1.1]
                             (b) [F02-OS1.2,OP1.2]
                        (3) Note1
Subsection 4.12.9. Refrigerated Storage
4.12.9.1.         (1) [F81-OS1.1,OP1.1]
                        (2) [F01,F43-OS1.1,OP1.1]
 

 

Table 5
Objectives and Functional Statements Attributed to the
Acceptable Solutions in Part 5 of Division B
 

 

Acceptable Solution Objectives and Functional Statements
SECTION 5.1 GENERAL
Subsection 5.1.1. Application
5.1.1.1. Note1
Subsection 5.1.2. Means of Egress
5.1.2.1. [F10-OS1.5]
Subsection 5.1.3. Electrical Installations
5.1.3.1. [F01-OS1.1]
Subsection 5.1.4. Ventilation
5.1.4.1. [F01-OS1.1]
SECTION 5.2 EXPLOSIVES, FIREWORKS AND PYROTECHNICS
Subsection 5.2.1. Explosives
5.2.1.1.
 
[F01-OS1.1]
[F02,F03-OS1.2]
5.2.1.2            (1)(a) [F12-OS1.2,OP1.2]
                             (b) [F12-OS1.2,OP1.2]
                             (c) [F12-OS1.2,OP1.2]
Subsection 5.2.2. Fireworks and Pyrotechnics
5.2.2.1.
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
5.2.2.2.

 

[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
[F03-OP3.1]
SECTION 5.3 MATCHES
Subsection 5.3.1. Storage
5.3.1.1.
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
5.3.1.2. [F03-OS1.2,OP1.2]
5.3.1.3. [F02,F03-OS1.2,OP1.2]
5.3.1.4. [F03-OS1.2,OP1.2]
5.3.1.5. [F03-OS1.2,OP1.2]
SECTION 5.4 CELLULOSE NITRATE PLASTICS
Subsection 5.4.1. Displays
5.4.1.1. [F02,F03-OS1.2,OP1.2]
5.4.1.2. [F01-OS1.1,OP1.1]
Subsection 5.4.2. Manufacture
5.4.2.1.
 
[F01-OS1.1,OP1.1]
[F02,F12-OS1.2,OP1.2]
5.4.2.2. [F02-OS1.2,OP1.2]
5.4.2.3.
 
[F01-OS1.1,OP1.1]
[F02,F03-OS1.2,OP1.2]
5.4.2.4.
 
[F01-OS1.1,OP1.1]
[F02,F03-OS1.2,OP1.2]
5.4.2.5. [F81-OS1.1,OP1.1]
5.4.2.6. [F02-OS1.2,OP1.2]
5.4.2.7. [F02-OS1.2,OP1.2]
5.4.2.8. [F81-OS1.1,OP1.1]
Subsection 5.4.3. Storage of Finished Products
5.4.3.1. [F01-OS1.1,OP1.1]
5.4.3.2.           (1) [F01-OS1.1,OP1.1]
5.4.3.3.           (1) [F01-OS1.1,OP1.1]
[F03-OS1.2,OP1.2]
                        (2) [F02-OS1.2,OP1.2]
5.4.3.4.           (1)

 

[F01-OS1.1,OP1.1]
[F02,F03-OS1.2,OP1.2]
[F04-OS1.3,OP1.3]
5.4.3.5.           (1)

 

[F01-OS1.1,OP1.1]
[F02,F03-OS1.2,OP1.2]
[F04-OS1.3,OP1.3]
Subsection 5.4.4. Cellulose Nitrate Motion Picture Film
5.4.4.1. Note1
5.4.4.2. [F02,F03-OS1.2,OP1.2]
5.4.4.3.
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
Subsection 5.4.5. Fire Protection
5.4.5.1. [F02-OS1.2,OP1.2]
SECTION 5.5 RESERVED
SECTION 5.6 COMPRESSED GAS CYLINDERS
Subsection 5.6.1. General
5.6.1.1.           (1) Note1
                        (2) Note1
                        (3) Note1
                        (4) Note1
                        (5) Note1
5.6.1.2.           (1) [F01,F43-OS1.1,OP1.1]
                        (2) [F01,F43-OS1.1,OP1.1]
5.6.1.3. [F01,F43-OS1.1,OP1.1]
5.6.1.4. [F01,F43,F81-OS1.1,OP1.1]
5.6.1.5. [F20-OS1.1,OP1.1]
5.6.1.6.           (1)(a) [F80-OS1.1,OP1.1]
                             (b) [F01-OS1.1,OP1.1]
5.6.1.7. [F01-OS1.1,OP1.1]
Subsection 5.6.2. Storage
5.6.2.1.           (1)
 
[F01,F34,F80,F81-OS1.1]
[F02-OS1.2]
                        (2) [F02-OS1.2]
5.6.2.2.           (1) [F12-OS1.2]
[F34-OS1.1]
                        (2) [F01-OS1.1]
[F03-OS1.2]
5.6.2.3.           (1) [F44-OS1.1,OP1.1]
                        (2) Note1
5.6.2.4.           (1)(a) [F03-OS1.2,OP1.2]
                             (b) [F03,F12-OS1.2,OP1.2]
[F44-OS1.1,OS1.2,OP1.1,OP1.2]
                             (c) [F03,F12-OS1.2,OP1.2]
[F44-OS1.1,OS1.2,OP1.1,OP1.2]
                             (d) [F02-OS1.2,OP1.2]
[F04-OS1.3,OP1.3]
                             (e) [F01-OS1.1,OP1.1]
                             (f) [F01-OS1.1,OP1.1]
                             (g) [F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
                        (2) [F02-OS1.2,OP1.2]
                        (3) Note1
                        (4) [F01-OS1.1,OP1.1]
                        (5)
 
[F01,F81-OS1.1,OP1.1]
[F02,F03-OS1.2,OP1.2]
5.6.2.5. RESERVED
5.6.2.6. Note1
5.6.2.7.           (1)
 
[F01-OS1.1,OP1.1]
[F02-OS1.2,OP1.2]
                        (2) Note1
                        (3) Note1
5.6.2.8. [F12-OS1.2,OP1.2]
SECTION 5.7 RESERVED
SECTION 5.8 RESERVED
SECTION 5.9 RESERVED
SECTION 5.10